Plan Review Stops For Permit 20091013 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-10-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-23 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-23 |
Time |
15:40 |
Sent To |
|
|
Notes |
2020-10-23 16:36:46 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | ALL WORK PER CITY CODES IS SUBJECT TO FIELD INSPECTOR'S | | APPROVAL | | | | AS THERE ARE EXISTING STRUCTURAL CONNECTIONS, THE | | CONTRACTOR IS TO PROVIDE ENGINEER'S SIGNED/SEALED | | CLARIFICATIONS ON ANY CONNECTION DETAILS IF NOT CLEAR | | TO INSPECTOR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-03 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-03 |
Time |
11:19 |
Sent To |
|
|
Notes |
2020-10-03 12:43:08 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, PLEASE PROVIDE A CLEAR CONNECTION | | DETAIL FOR THE STAIR LANDING AREA INCLUDING STAIR | | LANDING, BEAM 10 AND BEAM 11 CONNECTIONS. | | | | 2) FBC B 107.2.1, PLEASE PROVIDE NEW TRUSS TO STRUCTURE | | CONNECTION AND BRACING DETAILS.THIS INFORMATION IS | | REQUIRED TO BE PART OF THIS PLAN. | | NOTE: THE REQUIRED TRUSS ENGINEERING, WHICH IS | | SEPARATE, IS TO BE SUBMITTED ON THE JOB-SITE TO THE | | CITY INSPECTOR AND MUST BE SIGNED AND SEALED BY THE | | TRUSS ENGINEER AND REVIEW STAMP APPROVED BY THE | | DESIGNER OF RECORD FOR THIS PROJECT. | | | | 3) FBC B 107, PLEASE PROVIDE THE WINDOW MULLION PRODUCT | | APPROVALS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-10-27 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-10-27 |
Time |
10:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-30 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-30 |
Time |
08:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-21 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-21 |
Time |
09:48 |
Sent To |
|
|
Notes |
2020-10-21 11:53:32 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | 1. ALL STREET FACING GLASS SHALL HAVE CLEAR GLASS ONLY. | | NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS OR CLEAR | | GLASS WITH LOW-E. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 2. ALL WINDOWS SHALL HAVE A STEPBACK WHERE THE | | TOP-FIXED SASH IS A MINIMUM OF 1-INCH FROM THE EXTERIOR | | WALL FACE. | | 3. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL | | DIMENSIONAL MUNTINS. FOR LAWSON, THIS IS A CROSS | | OGEE/PYRAMID OGEE PROFILE. | | 4. ALL PAIRED WINDOWS WILL REQUIRE A 4-INCH WIDE | | MULLION. THE NORTH (REAR) ELEVATION PAIRED WINDOW IN | | THE FORMER PORCH AREA WILL BE EXEMPTED FOR THE | | FANLIGHT. | | 5. THE NEW STUCCO SHALL FEATURE A TRADITIONAL TEXTURED | | MISSION STUCCO FINISH. | | 6. THE EXISTING BANDING MAY BE REMOVED ENTIRELY OR DONE | | AS PROPOSED ON THE PLANS. | | 7. THE EXTERIOR FRAMES SHALL BE WHITE OR BRONZE. | | 8. THE NORTH ELEVATION ENCLOSED PORCH FANLIGHT SHALL BE | | CONNECTED TO THE PAIRED SINGLE-HUNG WINDOWS WITH A | | MULLION WITH A WIDTH OF 1, 2, OR 3 INCHES WIDE. (THESE | | THREE WINDOWS ARE ONE WINDOW OPENING.) | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-01 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-01 |
Time |
15:35 |
Sent To |
|
|
Notes |
2020-10-01 15:36:39 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. SUBMIT A LANDSCAPING PERMIT. ILLUSTRATING COMPLIANCE | | WITH ILLUSTRATE COMPLIANCE WITH SECTION 94-442(C)(2) A. | | SINGLE FAMILY DWELLING UNITS. THE PERMIT DOES NOT NEED | | TO BE APPROVED OR REVIEWED. THE PERMIT MUST BE | | SUBMITTED, AND FEES PAID FOR. THE VALUE OF THE PERMIT | | EXCEEDS 50% OF THE IMPROVEMENT VALUE OF THE PROPERTY. | | 2. PROVIDE PRODUCT APPROVALS FOR THE ROOFING TILE. AN | | EARTH TONE COLOR WILL BE REQUIRED. | | 3. NOTE OR HIGHLIGHT WHERE THE ROOFING TILE WILL BE | | INSTALLED. | | 4. REVISE THE REAR PORCH WINDOW TO BE SIZED FULLY TO | | THE ORIGINAL WINDOW FRAME OPENING WITH A TOP FANLIGHT | | WITH A 5-LITE PROFILE. THE FANLIGHT MAY ALSO BE A | | SINGLE-LITE. | | 5. PROVIDE MATERIAL OF RAILING. IT MUST BE ALUMINUM. | | 6. REVISE THE SITE PLAN TO ILLUSTRATE THE REAR PORCH | | ADDITION. | | | | PROPOSED CHANGES, SUBJECT TO CHANGE: | | 1. ALL STREET FACING GLASS SHALL HAVE CLEAR GLASS ONLY. | | NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS OR CLEAR | | GLASS WITH LOW-E. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 2. ALL WINDOWS SHALL HAVE A STEPBACK WHERE THE | | TOP-FIXED SASH IS A MINIMUM OF 1-INCH FROM THE EXTERIOR | | WALL FACE. | | 3. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL | | DIMENSIONAL MUNTINS. FOR LAWSON, THIS IS A CROSS | | OGEE/PYRAMID OGEE PROFILE. | | 4. ALL PAIRED WINDOWS WILL REQUIRE A 4-INCH WIDE | | MULLION. THE NORTH (REAR) ELEVATION PAIRED WINDOW IN | | THE FORMER PORCH AREA WILL BE EXEMPTED FOR THE | | FANLIGHT. | | 5. THE NEW STUCCO SHALL FEATURE A TRADITIONAL TEXTURED | | MISSION STUCCO FINISH. | | 6. THE EXISTING BANDING MAY BE REMOVED ENTIRELY OR DONE | | AS PROPOSED ON THE PLANS. | | 7. THE EXTERIOR FRAMES SHALL BE WHITE OR BRONZE. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-27 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-16 |
Time |
12:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-03 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-09-23 |
Time |
09:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2020-09-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-29 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-29 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-09-25 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-25 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-25 |
Time |
09:56 |
Sent To |
|
|
Notes |
2020-09-25 10:09:01 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20091013 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THIS CHANGE OF SCOPE WILL REQUIRE A MECHANICAL | | SUB-PERMIT. FBC FS 107.2.1 | | | | 2) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC | | 101.5.1.1.2 | | | | 3) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC | | RES M403.7 | | | | 4) PLEASE PROVIDE CODE COMPLIANT MECHANICAL DRAWINGS | | WITH THE DESIGNERS DIGITAL SIGNATURE. FBC FS 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2020-10-19 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-10-19 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-10-19 |
Time |
11:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2020-09-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-09-29 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-09-29 |
Time |
12:06 |
Sent To |
|
|
Notes |
2020-09-29 12:07:43 | 2ND REVIEW FBC-2017 RES. PLUMBING. | | PERMIT-20091013 | | 9/29/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS P-2 & P-3: THE SELECTED RHEEM RETEX-18 IS | | UNDERSIZED FOR REQUIRED HOT WATER GPM FLOW TO THE | | FIXTURES. THE MANUFACTURER'S TEMPERATURE RISE CHART FOR | | THE SELECTED RHEEM RETEX-18 SHOWS A MAX 4.0 GPM FLOW AT | | A 31-DEGREE F TEMPERATURE RISE. PLEASE NOTE HOT WATER | | AT A TEMPERATURE OF 110 DEGREES F SHALL BE PROVIDED TO | | THE FIXTURES WHERE REQUIRED- SECTION P2801.1 FBC RES. | | REFER TO TABLE P2903.1 FBC P AND SELECT A WATER HEATER | | WITH THE CAPACITY TO PROVIDE THE REQUIRED GPM HOT WATER | | FLOW TO ALL FIXTURES AND APPLIANCES. INDICATE THE MAKE | | AND MODEL ON THE CORRECTED PLANS AND SUBMIT | | MANUFACTURER'S SPECIFICATIONS THAT INCLUDE THE | | TEMPERATURE RISE CHART. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-09-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-09-28 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-09-28 |
Time |
15:22 |
Sent To |
|
|
Notes |
2020-09-28 15:34:40 | 1ST REVIEW FBC-2017 RES. PLUMBING. | | PERMIT-20091013 | | 9/28/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) BASED ON THE SUBMITTED REVISION APPLICATION AND THE | | NEW SCOPE OF WORK, PLEASE PROVIDE COMPLETE PLUMBING | | PLANS AND A PLUMBING SUB-PERMIT- SECTIONS 105.1 AND | | 107.2.1 WPB. PLEASE PROVIDE ON THE PLANS A SCOPE OF | | WORK OUTLINE, LOCATIONS OF ALL NEW OR RELOCATED | | PLUMBING FIXTURES, RISER DRAWINGS, AREAS OF SLAB DEMO | | OUTLNED, SLAB REPAIR DETAIL, AND EQUIPMENT SCHEDULE AND | | SUBMITTAL FOR A NEW WATER HEATER IF PROVIDED. | | | | 2) SUBMIT A PLUMBING SUB-PERMIT APPLICATION- SECTION | | 105.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-10-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-23 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-23 |
Time |
15:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-09-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-09-29 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-09-28 |
Time |
14:34 |
Sent To |
|
|
Notes |
2020-09-29 10:05:04 | DRAWINGS CVR, A1, A2, A3, S1, S2, S3, S4, S5 AND S6 | | HAVE ENGINEER'S ORIGINAL SEAL/SIGNATURE. JG. | | DRAWINGS E-1, M-1, M-2, P-1, P-2 AND P-3 HAVE | | ENGINEER'S ORIGINAL SEAL/SIGNATURE. JG | | MANUAL J CALCULATIONS HAVE ENGINEER'S ORIGINAL | | SEAL/SIGNATURE. JG |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-09-25 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-25 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-25 |
Time |
10:26 |
Sent To |
|
|
Notes |
2020-09-25 10:27:23 | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-21 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-21 |
Time |
11:52 |
Sent To |
|
|
Notes |
2020-10-21 11:53:18 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | 1. ALL STREET FACING GLASS SHALL HAVE CLEAR GLASS ONLY. | | NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS OR CLEAR | | GLASS WITH LOW-E. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 2. ALL WINDOWS SHALL HAVE A STEPBACK WHERE THE | | TOP-FIXED SASH IS A MINIMUM OF 1-INCH FROM THE EXTERIOR | | WALL FACE. | | 3. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL | | DIMENSIONAL MUNTINS. FOR LAWSON, THIS IS A CROSS | | OGEE/PYRAMID OGEE PROFILE. | | 4. ALL PAIRED WINDOWS WILL REQUIRE A 4-INCH WIDE | | MULLION. THE NORTH (REAR) ELEVATION PAIRED WINDOW IN | | THE FORMER PORCH AREA WILL BE EXEMPTED FOR THE | | FANLIGHT. | | 5. THE NEW STUCCO SHALL FEATURE A TRADITIONAL TEXTURED | | MISSION STUCCO FINISH. | | 6. THE EXISTING BANDING MAY BE REMOVED ENTIRELY OR DONE | | AS PROPOSED ON THE PLANS. | | 7. THE EXTERIOR FRAMES SHALL BE WHITE OR BRONZE. | | 8. THE NORTH ELEVATION ENCLOSED PORCH FANLIGHT SHALL BE | | CONNECTED TO THE PAIRED SINGLE-HUNG WINDOWS WITH A | | MULLION WITH A WIDTH OF 1, 2, OR 3 INCHES WIDE. (THESE | | THREE WINDOWS ARE ONE WINDOW OPENING.) | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-01 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-01 |
Time |
15:36 |
Sent To |
|
|
Notes |
2020-10-01 15:36:56 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. SUBMIT A LANDSCAPING PERMIT. ILLUSTRATING COMPLIANCE | | WITH ILLUSTRATE COMPLIANCE WITH SECTION 94-442(C)(2) A. | | SINGLE FAMILY DWELLING UNITS. THE PERMIT DOES NOT NEED | | TO BE APPROVED OR REVIEWED. THE PERMIT MUST BE | | SUBMITTED, AND FEES PAID FOR. THE VALUE OF THE PERMIT | | EXCEEDS 50% OF THE IMPROVEMENT VALUE OF THE PROPERTY. | | 2. PROVIDE PRODUCT APPROVALS FOR THE ROOFING TILE. AN | | EARTH TONE COLOR WILL BE REQUIRED. | | 3. NOTE OR HIGHLIGHT WHERE THE ROOFING TILE WILL BE | | INSTALLED. | | 4. REVISE THE REAR PORCH WINDOW TO BE SIZED FULLY TO | | THE ORIGINAL WINDOW FRAME OPENING WITH A TOP FANLIGHT | | WITH A 5-LITE PROFILE. THE FANLIGHT MAY ALSO BE A | | SINGLE-LITE. | | 5. PROVIDE MATERIAL OF RAILING. IT MUST BE ALUMINUM. | | 6. REVISE THE SITE PLAN TO ILLUSTRATE THE REAR PORCH | | ADDITION. | | | | PROPOSED CHANGES, SUBJECT TO CHANGE: | | 1. ALL STREET FACING GLASS SHALL HAVE CLEAR GLASS ONLY. | | NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS OR CLEAR | | GLASS WITH LOW-E. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 2. ALL WINDOWS SHALL HAVE A STEPBACK WHERE THE | | TOP-FIXED SASH IS A MINIMUM OF 1-INCH FROM THE EXTERIOR | | WALL FACE. | | 3. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL | | DIMENSIONAL MUNTINS. FOR LAWSON, THIS IS A CROSS | | OGEE/PYRAMID OGEE PROFILE. | | 4. ALL PAIRED WINDOWS WILL REQUIRE A 4-INCH WIDE | | MULLION. THE NORTH (REAR) ELEVATION PAIRED WINDOW IN | | THE FORMER PORCH AREA WILL BE EXEMPTED FOR THE | | FANLIGHT. | | 5. THE NEW STUCCO SHALL FEATURE A TRADITIONAL TEXTURED | | MISSION STUCCO FINISH. | | 6. THE EXISTING BANDING MAY BE REMOVED ENTIRELY OR DONE | | AS PROPOSED ON THE PLANS. | | 7. THE EXTERIOR FRAMES SHALL BE WHITE OR BRONZE. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|