Plan Review Details - Permit 20091012
Plan Review Stops For Permit 20091012
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 08:53 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 10:16 Sent To  
Notes
2020-11-04 10:41:55COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2020-10-07 Time 10:01 Sent To  
Notes
2020-10-07 11:38:02COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 10:16 Sent To  
Notes
2020-11-04 10:45:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091012
 ADD: 1683 FORUM PLACE
 CONT: HALLMARK CONSTRUCTION
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. NOV. 04TH/ 2020
 ACTION: DENIED
 4X FEE / NOTICE LONLY!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 NO TRANSMITTAL LETTER WAS SUBMITTED. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 1) SHEET A-1:
 1A) 2ND REQUEST. UNDER THE HEADING APPLICABLE CODES &
 BUILDING CLASSIFICATION THE PLAN STATES IT IS AN
 INTERIOR ALTERATION LEVEL 2. UNDER THE HEADING TENANT
 INFORMATION FOR NEW TENANT SPACE # 1683 THE PLAN STATES
 THE PREVIOUS TENANT WAS OCCUPIED BY THE SPICE,
 RESTAURANT AN A-2 OCCUPANCY. THE NEW OCCUPANCY IS TO BE
 A CHIROPRACTIC OFFICE A BUSINESS OCCUPANCY. PLEASE NOTE
 THAT INSTEAD OF A LEVEL 2 ALTERATION THE EXIST.
 BUILDING CODE WOULD LIST THIS PLAN AS A CHANGE OF
 OCCUPANCY PLEASE REVIEW IN THE 2017 EXIST. BUILD. CODE
 SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. PLEASE
 UPDATE THE PLANS.
  
 1B) 2ND REQUEST. ACCESSIBILITY DETAILS, THE FLOOR PLAN
 OF THE ACCESSIBLE RESTROOMS WITH A INSWING DOOR OF THE
 RESTROOMS, SWINGING IN OVER THE REQUIRED FLOOR SPACE OF
 THE LAV AND WATER CLOSET. 2017 FBC-ACCESSIBILITY CODE
 FIGURE 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE ALSO
 REVIEW SECTION 603.2.3 DOOR SWING AND EXCEPTION 2. I
 BELIEVE THIS IS HOW YOU ARE STRIVING TO SHOW CODE
 COMPLIANCE. WHAT IS MISSING IS THE REQUIRED CLEAR FLOOR
 SPACE 30X48 BEYOND THE ARC OF THE DOOR. IT IS USUALLY
 SHOWN AT A 45-DEGREE ANGLE TO THE ENTRY DOOR.
  
 1C) 2ND REQUEST. GRAB BARS ARE SHOWN WITH THE
 MEASUREMENT TAKEN FROM FINISH FLOOR TO CENTERLINE OF
 THE GRAB BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1D) 2ND REVIEW. MISSING IS A SIDE WALL VIEW OF THE REST
 ROOM THE TOILET PAPER HOLDER LOCATION, DISTANCE FROM
 THE FRONT OF THE WATER CLOSET. TOILET PAPER DISPENSERS.
 ACCESS. CODE 604.7. THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 1E) 2ND REVIEW. THE BACK WALL SHOWS A FRAMED MIRROR. IT
 APPEARS THE MEASUREMENT FROM THE FINISH FLOOR IS TO THE
 BOTTOM OF THE MIRRORS FRAME NOT THE REFLECTIVE SURFACE
 OF THE MIRROR. 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY
 CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 1F) 2ND REVIEW. PLEASE NOTE ON THE REAR WALL THERE IS A
 STATEMENT EPOXY PAINT ALL SIDES AS SELECTED BY TENANT.
 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
  
 FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
  
  
 PLEASE NOTE!!! 2017 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1G) 2ND REVIEW. PLEASE NOTE IN BOTH DETAILS STAFF
 CABINET ELEV. 1 AND IN EXAM CABINET ELEV. 2 BOTH THE
 SINKS ARE AT A ELEVATION 34 INCHES BUT THE COUNTER TOP
 IN THE NEXT ADJOINING CABINETRY, THE COUNTERTOP IS 36
 INCHES IN HEIGHT. THE 2017 FBC-ACCESS. CODE SECTION
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 1H) 2ND REVIEW. THE FLOOR PLAN FOR BOTH THE STAFF SINK
 AND EXAM ROOM SINK DOES NOT INDICATE THE CLEAR FLOOR
 SPACE REQUIRED. 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305, POSITIONED FOR A FORWARD
 APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN.
 1I) 2ND REVIEW. THE LIFE SAFETY FLOOR PLAN SHOWS AN
 RECEPTIONIST DESK BUT THERE ARE NO DETAILS SHOWING THE
 HEIGHT OF THE COUNTER TOP AND WITH THE ACCESSIBLY
 REQUIREMENTS.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 1J) 2ND REVIEW. THE LIFE SAFETY PLAN SHOWS EXIT LIGHTS
 AT BOTH THE FRONT AND REAR OF THE BUILDING, BUT THE
 PLAN DOES NOT INDICATE IF THESE EXITS ARE ACCESSIBLE?
 ACCESS. CODE 404.2.5. THRESHOLDS. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE? INCH HIGH MAXIMUM.
 RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS
 SHALL COMPLY WITH 302 & 303.
  
 2)2ND REVIEW. DEMOLITION PLAN: THE DEMOLITION PLAN FOR
 THE ROOF INDICATES TO ABANDON AND CAP OFF ROOF
 EQUIPMENT CURBS. NO DETAILS PROVIDED FOR THE CONTRACTOR
 TYPE OF MATERIAL, THICKNESS OF MATERIAL AND SIZE AND
 SPACING OF THE FASTENERS TO ANCHOR THE NEW COVER TO THE
 CURB. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By jwitmer Date 2020-10-07 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2020-10-07 Time 10:01 Sent To  
Notes
2020-10-07 10:03:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091012
 ADD: 1683 FORUM PLACE
 CONT: HALLMARK CONSTRUCTION
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 07TH/ 2020
 ACTION: DENIED
 1) SHEET A-1:
 1A) UNDER THE HEADING APPLICABLE CODES & BUILDING
 CLASSIFICATION THE PLAN STATES IT IS AN INTERIOR
 ALTERATION LEVEL 2. UNDER THE HEADING TENANT
 INFORMATION FOR NEW TENANT SPACE # 1683 THE PLAN STATES
 THE PREVIOUS TENANT WAS OCCUPIED BY ? THE SPICE?
 RESTAURANT AN A-2 OCCUPANCY. THE NEW OCCUPANCY IS TO BE
 A CHIROPRACTIC OFFICE A BUSINESS OCCUPANCY. PLEASE NOTE
 THAT INSTEAD OF A LEVEL 2 ALTERATION THE EXIST.
 BUILDING CODE WOULD LIST THIS PLAN AS A CHANGE OF
 OCCUPANCY PLEASE REVIEW IN THE 2017 EXIST. BUILD. CODE
 SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. PLEASE
 UPDATE THE PLANS.
  
 1B) ACCESSIBILITY DETAILS, THE FLOOR PLAN OF THE
 ACCESSIBLE RESTROOMS WITH A INSWING DOOR OF THE
 RESTROOMS, SWINGING IN OVER THE REQUIRED FLOOR SPACE OF
 THE LAV AND WATER CLOSET. 2017 FBC-ACCESSIBILITY CODE
 FIGURE 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE ALSO
 REVIEW SECTION 603.2.3 DOOR SWING AND EXCEPTION 2. I
 BELIEVE THIS IS HOW YOU ARE STRIVING TO SHOW CODE
 COMPLIANCE. WHAT IS MISSING IS THE REQUIRED CLEAR FLOOR
 SPACE 30X48 BEYOND THE ARC OF THE DOOR. IT IS USUALLY
 SHOWN AT A 45-DEGREE ANGLE TO THE ENTRY DOOR.
  
 1C) GRAB BARS ARE SHOWN WITH THE MEASUREMENT TAKEN FROM
 FINISH FLOOR TO CENTERLINE OF THE GRAB BAR. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 1D) MISSING IS A SIDE WALL VIEW OF THE REST ROOM THE
 TOILET PAPER HOLDER LOCATION, DISTANCE FROM THE FRONT
 OF THE WATER CLOSET. TOILET PAPER DISPENSERS. ACCESS.
 CODE 604.7. THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
  
 1E) THE BACK WALL SHOWS A FRAMED MIRROR. IT APPEARS THE
 MEASUREMENT FROM THE FINISH FLOOR IS TO THE BOTTOM OF
 THE MIRRORS FRAME NOT THE REFLECTIVE SURFACE OF THE
 MIRROR. 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 1F) PLEASE NOTE ON THE REAR WALL THERE IS A STATEMENT
 EPOXY PAINT ALL SIDES AS SELECTED BY TENANT. FBC-B
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
  
  
 PLEASE NOTE!!! 2017 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1G) PLEASE NOTE IN BOTH DETAILS STAFF CABINET ELEV. 1
 AND IN EXAM CABINET ELEV. 2 BOTH THE SINKS ARE AT A
 ELEVATION 34 INCHES BUT THE COUNTER TOP IN THE NEXT
 ADJOINING CABINETRY, THE COUNTERTOP IS 36 INCHES IN
 HEIGHT. THE 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1H) THE FLOOR PLAN FOR BOTH THE STAFF SINK AND EXAM
 ROOM SINK DOES NOT INDICATE THE CLEAR FLOOR SPACE
 REQUIRED. 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
 1I) THE LIFE SAFETY FLOOR PLAN SHOWS AN RECEPTIONIST
 DESK BUT THERE ARE NO DETAILS SHOWING THE HEIGHT OF THE
 COUNTER TOP AND WITH THE ACCESSIBLY REQUIREMENTS.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 1J) THE LIFE SAFETY PLAN SHOWS EXIT LIGHTS AT BOTH THE
 FRONT AND REAR OF THE BUILDING, BUT THE PLAN DOES NOT
 INDICATE IF THESE EXITS ARE ACCESSIBLE? ACCESS. CODE
 404.2.5. THRESHOLDS. THRESHOLDS, IF PROVIDED AT
 DOORWAYS, SHALL BE ? INCH HIGH MAXIMUM. RAISED
 THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS SHALL
 COMPLY WITH 302 & 303.
  
 2) DEMOLITION PLAN: THE DEMOLITION PLAN FOR THE ROOF
 INDICATES TO ABANDON AND CAP OFF ROOF EQUIPMENT CURBS.
 NO DETAILS PROVIDED FOR THE CONTRACTOR TYPE OF
 MATERIAL, THICKNESS OF MATERIAL AND SIZE AND SPACING OF
 THE FASTENERS TO ANCHOR THE NEW COVER TO THE CURB.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By jleahy Date 2020-12-09 Time 16:00 Rev Time 0.00
Received By jleahy Date 2020-12-09 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 14:01 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 14:02 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 14:02 Sent To  
Notes
2020-10-28 14:03:16LOW VOLTAGE FOR DATA/PHONE JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-11-25 Cont ID  
Sent By pleduc Date 2020-11-25 Time   Rev Time 0.00
Received By pleduc Date 2020-11-25 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-04 Cont ID  
Sent By pleduc Date 2020-11-04 Time   Rev Time 0.00
Received By pleduc Date 2020-11-04 Time 16:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By pleduc Date 2020-09-25 Time   Rev Time 0.00
Received By pleduc Date 2020-09-25 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-09 Cont ID  
Sent By jleahy Date 2020-12-09 Time 16:00 Rev Time 0.00
Received By jleahy Date 2020-11-24 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By lmarchan Date 2020-11-19 Time 14:01 Rev Time 0.00
Received By lmarchan Date 2020-11-03 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 14:03 Rev Time 0.00
Received By jleahy Date 2020-09-24 Time 14:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By lmarchan Date 2020-12-16 Time 11:38 Rev Time 0.00
Received By lmarchan Date 2020-12-10 Time 08:15 Sent To  
Notes
2020-12-16 11:38:48MU-2020-48590 - $0.00 DUE - IMPACT OFFICE COULD NOT
 STAMP PLANS - UPLOADED EMAIL FOR REFERENCE
2020-12-10 08:15:1612/10/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By rbrown Date 2020-10-30 Time 10:32 Rev Time 0.00
Received By rbrown Date 2020-10-30 Time 10:32 Sent To  
Notes
2020-10-30 10:35:18CHANGE OF OCCUPANCY: PLANS MAY REQUIRE PAYMENT OF
 IMPACT FEES TO PALM BEACH CONTY IMPACT FEE OFFICE.
 PLANS SHALL BE ASSESSED BY THAT OFFICE AND CONFIRMATION
 PROVIDED THAT EITHER IMPACT FEES HAVE BEEN PAID, OR NO
 IMAPCT FEES ARE DUE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By medwards Date 2020-12-08 Time 11:27 Rev Time 0.00
Received By medwards Date 2020-12-08 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 10:38 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By tklarge Date 2020-12-08 Time 12:29 Rev Time 0.00
Received By tklarge Date 2020-12-08 Time 06:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-13 Cont ID  
Sent By tklarge Date 2020-10-13 Time 07:28 Rev Time 0.00
Received By tklarge Date 2020-10-09 Time 05:05 Sent To  
Notes
2020-10-09 09:50:221) SHT. A.1 - H.C.T.R. DETAIL PLAN - NOTES #1 & #3 -
 THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FBC-ACCESS. SEC. 609.4. REVISE THE
 NOTES.
 2) THE TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9
 INCHES IN FRONT OF THE WATER CLESET MEASURED TO THE
 CENTERLINE OF THE DISPENSER PER FBC-ACCESS. SEC. 604.7.
 3) SHT. A.1 - H.C.T.R. DETAIL - THE DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
 FOR ANY FIXTURE PER FBC-ACCESS. SEC.603.2.3. (SEE
 EXCEPTION #2).
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE STAFF
 AND EXAM SINK PER FBC-ACCESS.SEC.606.2. A MINIMUM 30
 INCH WIDE CLEAR FLOOR SPACE COMPLYING WITH
 FBC-ACCESS.SEC. 305 POSITIONED FOR A FORWARD APPROACH,
 SHALL BE PROVIDED FOR THE EXAM ROOM SINK. A PARALLEL
 APPROACH COMPLYNG WITH SEC. 305 SHALL BE PERMITTED TO
 THE STAFF ROOM SINK.
 5) EPOXY PAINT ON THE TOILET ROOM WALLS DOES NOT COMPLY
 WITH FBC-BUILDING SEC.12110.2.2. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE WALLS
 AROUND THE JANITOR SINK SHALL ALSO COMPLY.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE
 TOILET ROOMS PER FBC-PLUMBING SEC.416.5.TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 8) SIZE THE DRAINS FOR THE STAFF AND EXAM SINKS ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) ONLY THE PLUMBING FIXTURES WITHIN THE BATHROOM GROUP
 ARE PERMITTED TO BE VENTED BY A HORIZONTAL WET VENT PER
 FBC-PLUMBING SEC.912.1. AS DRAWN, THE SANITARY RISER
 DIAGRAM DOES NOT COMPLY.
 10) THE RISER DIAGRAM REFERS TO THE USE OF OFFSET
 FLANGES.THESE FLANGES CANNOT BE USED PER FBC-PLUMBING
 SEC.706.2.
 11) SHOW THE SIZE OF THE EXISTING SANITARY DRAIN
 PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 10:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-07 Cont ID  
Sent By jwitmer Date 2020-10-07 Time 11:43 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***