Plan Review Details - Permit 20091008
Plan Review Stops For Permit 20091008
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 11:41 Sent To  
Notes
2020-10-19 14:23:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUATION OF THE WORK AT $85,000 APPEARS TO BE
 LOW. SUBMIT A COPY OF THE CONTRACT TO VERIFY THE COST.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE SET IS
 REQUIRED TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED
 DOCUMENTS.
  
 3) SUBMIT FORMS AND DOCUMENTS TO SHOW COMPLIANCE WITH
 FBC ENERGY CONSERVATION SECTION R103.
  
 4) ON SHEET A-3 THE LINTEL SCHEDULE HAS 10'-4" FOR THE
 LENGTH OF L-2 FOR THE 16' GARAGE DOOR OPENING. PLEASE
 CLARIFY. FBC 107
  
 5) THE LENGTH OF THE SOUTH WALL OF THE DETACHED GARAGE
 IS INCORRECTLY SPECIFIED AS 24' ON SHEETS A-2, A-3 AND
 S-1. IT SHOULD BE 22'. PLEASE CORRECT. FBC 107.2.1
  
 6) THE SPACES BETWEEN THE WINDOWS ON THE EAST WALL OF
 THE DETACHED GARAGE IS DIFFERENT ON THE FLOOR PLAN
 (SHEET A-2) AND THE FOUNDATION PLAN ON (SHEET A-3) AND
 SHEET S-1. PLEASE COORDINATE. FBC 107.2.1
  
 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By fgiaquin Date 2020-10-08 Time 22:47 Rev Time 0.00
Received By fgiaquin Date 2020-10-08 Time 21:33 Sent To  
Notes
2020-10-08 22:47:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 2. PANEL SCHEDULE SHOWS 200AMP PANEL BUT INTERIOR PANEL
 SHOWN HAS NO OCP DESIGNATION AND WIRE FOR A 100AMP
 PANEL ONLY? PLEASE CLARIFY SIZE OF INTERIOR PANEL AND
 PROVIDE OCP SIZE. FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By lmarchan Date 2020-11-02 Time 14:53 Rev Time 0.00
Received By lmarchan Date 2020-09-25 Time 09:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 11:49 Sent To  
Notes
2020-10-19 11:57:13THE GYM PORTION OF THE NEW GARAGE ADDITION IS
 CONSIDERED HABITABLE SPACE AND REQUIRES REVIEW BY PALM
 BEACH COUNTY FOR IMPACT FEE ASSESSMENT. PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECTDOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By medwards Date 2020-09-30 Time 16:46 Rev Time 0.00
Received By medwards Date 2020-09-30 Time 16:46 Sent To  
Notes
2020-09-30 16:47:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20091008
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COVER SHEET INDICATES THERE IS NOW 4,334 TOTAL
 SQ. FT. OF AIR CONDITIONED AREA. PLEASE PROVIDE
 MECHANICAL SHEETS SHOWING THE EXISTING MECHANICAL
 SYSTEM AND ALL NEW WORK BEING DONE UNDER THIS PROJECT.
 FBC FS 107.2.1
  
 2) ANY MECHANICAL WORK WILL REQUIRE A MECHANICAL SUB
 PERMIT. FBC
  
 3) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By lcrespo Date 2020-10-05 Time 13:07 Rev Time 0.00
Received By lcrespo Date 2020-10-05 Time 12:46 Sent To  
Notes
2020-10-05 13:07:4310/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 3. ALL SANITARY STUB UP SHALL BE CAPPED OFF BELOW
 CONCRETE WITH HARD CAP AND THE MAIN TIE IN MAY NEED TO
 BE CAPPED OFF WITHOUT INTERRUPTION TO OTHER SANITARY
 SYSTEMS. HARD CAP WATER MAIN IN FRONT OF THE MAIN
 VALVE.
  
 4. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 5. PLEASE PROVIDE A NARRATIVE OF THE SCOPE OF WORK
 BEING DONE IN LAUNDRY ROOM, DRAINAGE SYSTEMS HAVE MAY
 ELEMENT. PROVIDE A DETAILED DRAWING FOR THE NEW
 LOCATION, FEET'S, SIZE OF PIPE, CLEANOUTS IF REQUIRED
 TYPE OF MATERIAL, ETC., PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 11:57 Sent To  
Notes
2020-10-19 13:43:28NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOFING
 MATERIALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-30 Cont ID  
Sent By medwards Date 2020-09-30 Time 16:55 Rev Time 0.00
Received By medwards Date 2020-09-30 Time 16:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By rthermid Date 2020-10-30 Time   Rev Time  
Received By rthermid Date 2020-10-30 Time   Sent To I
Notes
2020-10-30 13:03:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10/30/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED GARAGES WOULD NOT MEET THE REQUIRED
 FRONT SETBACKS OF 25 FEET MINIMUM TO THE GARAGE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved