Plan Review Details - Permit 20091008
Plan Review Stops For Permit 20091008 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-19 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-19 |
Time |
11:41 |
Sent To |
|
|
Notes |
2020-10-19 14:23:48 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE VALUATION OF THE WORK AT $85,000 APPEARS TO BE | | LOW. SUBMIT A COPY OF THE CONTRACT TO VERIFY THE COST. | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL | | MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE SET IS | | REQUIRED TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED | | DOCUMENTS. | | | | 3) SUBMIT FORMS AND DOCUMENTS TO SHOW COMPLIANCE WITH | | FBC ENERGY CONSERVATION SECTION R103. | | | | 4) ON SHEET A-3 THE LINTEL SCHEDULE HAS 10'-4" FOR THE | | LENGTH OF L-2 FOR THE 16' GARAGE DOOR OPENING. PLEASE | | CLARIFY. FBC 107 | | | | 5) THE LENGTH OF THE SOUTH WALL OF THE DETACHED GARAGE | | IS INCORRECTLY SPECIFIED AS 24' ON SHEETS A-2, A-3 AND | | S-1. IT SHOULD BE 22'. PLEASE CORRECT. FBC 107.2.1 | | | | 6) THE SPACES BETWEEN THE WINDOWS ON THE EAST WALL OF | | THE DETACHED GARAGE IS DIFFERENT ON THE FLOOR PLAN | | (SHEET A-2) AND THE FOUNDATION PLAN ON (SHEET A-3) AND | | SHEET S-1. PLEASE COORDINATE. FBC 107.2.1 | | | | 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-08 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-10-08 |
Time |
22:47 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-10-08 |
Time |
21:33 |
Sent To |
|
|
Notes |
2020-10-08 22:47:16 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | 2. PANEL SCHEDULE SHOWS 200AMP PANEL BUT INTERIOR PANEL | | SHOWN HAS NO OCP DESIGNATION AND WIRE FOR A 100AMP | | PANEL ONLY? PLEASE CLARIFY SIZE OF INTERIOR PANEL AND | | PROVIDE OCP SIZE. FBC 107.2.1 | | | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-11-02 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-09-25 |
Time |
09:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-10-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-19 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-19 |
Time |
11:49 |
Sent To |
|
|
Notes |
2020-10-19 11:57:13 | THE GYM PORTION OF THE NEW GARAGE ADDITION IS | | CONSIDERED HABITABLE SPACE AND REQUIRES REVIEW BY PALM | | BEACH COUNTY FOR IMPACT FEE ASSESSMENT. PLANS WILL BE | | REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA | | PROJECTDOX UPON NOTIFICATION BY THIS OFFICE. | | NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL | | FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT | | (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT | | FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE | | FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN | | BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT | | ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-30 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-30 |
Time |
16:46 |
Sent To |
|
|
Notes |
2020-09-30 16:47:09 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20091008 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE COVER SHEET INDICATES THERE IS NOW 4,334 TOTAL | | SQ. FT. OF AIR CONDITIONED AREA. PLEASE PROVIDE | | MECHANICAL SHEETS SHOWING THE EXISTING MECHANICAL | | SYSTEM AND ALL NEW WORK BEING DONE UNDER THIS PROJECT. | | FBC FS 107.2.1 | | | | 2) ANY MECHANICAL WORK WILL REQUIRE A MECHANICAL SUB | | PERMIT. FBC | | | | 3) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC | | 101.5.1.1.2 | | | | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC R403.7 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-10-05 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-10-05 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-10-05 |
Time |
12:46 |
Sent To |
|
|
Notes |
2020-10-05 13:07:43 | 10/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | TO THE FBC SEC. 105.1. | | | | 2. SIGNED AND SEALED DRAWINGS NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | ASKING FOR THE FORM. | | | | 3. ALL SANITARY STUB UP SHALL BE CAPPED OFF BELOW | | CONCRETE WITH HARD CAP AND THE MAIN TIE IN MAY NEED TO | | BE CAPPED OFF WITHOUT INTERRUPTION TO OTHER SANITARY | | SYSTEMS. HARD CAP WATER MAIN IN FRONT OF THE MAIN | | VALVE. | | | | 4. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | PLUMBING. | | | | 5. PLEASE PROVIDE A NARRATIVE OF THE SCOPE OF WORK | | BEING DONE IN LAUNDRY ROOM, DRAINAGE SYSTEMS HAVE MAY | | ELEMENT. PROVIDE A DETAILED DRAWING FOR THE NEW | | LOCATION, FEET'S, SIZE OF PIPE, CLEANOUTS IF REQUIRED | | TYPE OF MATERIAL, ETC., PER THE WPB FBC 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-10-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-19 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-19 |
Time |
11:57 |
Sent To |
|
|
Notes |
2020-10-19 13:43:28 | NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOFING | | MATERIALS. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-30 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-30 |
Time |
16:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-10-30 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-10-30 |
Time |
|
Sent To |
I |
|
Notes |
2020-10-30 13:03:59 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 10/30/2020 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. THE PROPOSED GARAGES WOULD NOT MEET THE REQUIRED | | FRONT SETBACKS OF 25 FEET MINIMUM TO THE GARAGE. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|
|