Plan Review Stops For Permit 20090998 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-12 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-12 |
Time |
09:44 |
Sent To |
|
|
Notes |
2020-11-12 09:47:31 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. | | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. | | C)DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. | | | | 2- SHEET A4.3: | | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-10 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-10 |
Time |
17:38 |
Sent To |
|
|
Notes |
2020-11-10 17:44:39 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. | | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. | | C)DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. | | | | 2- SHEET A4.3: | | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-06 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-06 |
Time |
13:33 |
Sent To |
|
|
Notes |
2020-11-06 13:44:28 | THIRD BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | ******COMMENTS WERE NOT ADDRESSED AT ALL. | | NO RESPONSE ON THE RESUBMITTAL. | | | | | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED REVISED | | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE | | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES | | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED | | INFORMATION BEFORE PERMIT ISSUANCE. | | | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE. | | | | 1- STOREFRONT IS NOT PART OF THIS PERMIT. | | | | 2- OK | | | | 3- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | RESPONSE: | | DETAIL #16 WAS REVISED BUT STILL SHOWS NO HANDRAILS ON | | BOTH SIDES OF THE RAMP. IT SHOWS ONLY ONE SIDE WITH | | HANDRAIL. REVISE AS REQUIRED. | | | | B) OK. | | | | C)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | RESPONSE: | | NOT ADDRESSED. | | | | D) DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE | | AS REQUIRED. | | | | RESPONSE: | | NOT ADDRESSED. | | | | 4- SHEET A4.3: | | A) OK | | | | B) OK | | | | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. | | | | RESPONSE: | | NOT ADDRESSED. THERE ARE NOT DETAILS/SPECS FOR FOOTINGS | | SIZES, REINFORCEMENT FOR SIGNAGE WALL. | | | | D) OK | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-03 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-02 |
Time |
09:09 |
Sent To |
|
|
Notes |
2020-11-03 09:54:32 | SECOND BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED REVISED | | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE | | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES | | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED | | INFORMATION BEFORE PERMIT ISSUANCE. | | | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE. | | | | 1- STOREFRONT IS NOT PART OF THIS PERMIT. | | | | 2- OK | | | | 3- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | RESPONSE: | | DETAIL #16 WAS REVISED BUT STILL SHOWS NO HANDRAILS ON | | BOTH SIDES OF THE RAMP. IT SHOWS ONLY ONE SIDE WITH | | HANDRAIL. REVISE AS REQUIRED. | | | | B) OK. | | | | C)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | RESPONSE: | | NOT ADDRESSED. | | | | D) DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE | | AS REQUIRED. | | | | RESPONSE: | | NOT ADDRESSED. | | | | 4- SHEET A4.3: | | A) OK | | | | B) OK | | | | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. | | | | RESPONSE: | | NOT ADDRESSED. THERE ARE NOT DETAILS/SPECS FOR FOOTINGS | | SIZES, REINFORCEMENT FOR SIGNAGE WALL. | | | | D) OK | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-10-23 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-10-22 |
Time |
12:49 |
Sent To |
|
|
Notes |
2020-10-23 10:32:42 | BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE. | | | | 1- SCOPE OF WORK IS NOT CLEAR. THE PERMIT APPLICATION | | DESCRIBES "INSTALLATION OF PAVER, STOREFRONT, STAIRS | | AND MONUMENT PER ATTACHED DRAWINGS". | | ON THE OTHER HAND, THE DESCRIPTION OF WORK ON-THE | | ARCHITECTURAL PLANS IS "EXTERIOR COURTYARD WORK, | | COMPOSED OF NEW STAIRS, NEW RAMPS & SIGNAGE TO CREATE | | ADDITIONAL OPEN AIR AREAS AT EXISTING PALM BEACH | | ATLANTIC UNIVERSITY STUDENT CENTER DINING". | | ARCHITECTURAL PLANS DON'T INCLUDE THE STOREFRONTS. I | | FOUND THAT THERE IS A SEPARATE PERMIT APPLICATION | | SUBMITTED FOR STOREFRONT REPLACEMENT (PERMIT | | #20090997). ARE THESE THE SAME STOREFRONTS. IF SO, | | PLEASE REVISE THE SCOPE ON THE PERMIT APPLICATION AND | | STATE THAT STOREFRONT UNDER SEPARATE PERMIT #20090997. | | THIS WILL HELP AVOID CONFUSION/CONFLICTS/DELAYS. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 2-SITE PLAN ON SHEET A1.0 SHOWS TWO NEW TRELLIS | | STRUCTURES ON THE NORTH WEST COURT YARD. PROVIDE | | COMPLETE DESIGN CRITERIA AND COMPLETE FRAMING PLANS, | | DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF | | THOSE STRUCTURES AS REQUIRED BY SEC. 1603.1.1 4 AND | | SEC. 1603.1FBC-BUILDING RESPECTIVELY. | | | | 3- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | B)DETAIL #13 EXTERIOR STAIR DETAIL: NEED TO SHOW | | HANDRAIL ON BOTH SIDES. SEC. 505.2 FBC-ACCESSIBILITY. | | REVISE AS REQUIRED. | | | | C)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | D) DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE | | AS REQUIRED. | | | | 4- SHEET A4.3: | | A)DETAIL #22 EXTERIOR STAIR & PLANTER SECTION: HANDRAIL | | HEIGHT OF 2'-8" DOESN'T COMPLY WITH SEC. 505.4 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | B)DETAIL #21 EXTERIOR STAIR & PLANTER: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS. SEC. 505.2 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | | | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. | | | | D)DETAIL #24 EXTERIOR RAMP SECTION DETAIL: THIS DETAIL | | DOESN'T MATCH WHAT IS SHOWN ON PLAN DETAIL #23 EXTERIOR | | RAMP DETAIL. REVISE AS REQUIRED TO MATCH. ALSO, SHOW | | THE HANDRAIL BOTTOM EXTENSION. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2020-10-20 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2020-10-20 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2020-10-20 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-11-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-11-03 |
Time |
14:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-10-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-10-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-10-23 |
Time |
10:08 |
Sent To |
|
|
Notes |
2020-10-26 10:24:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEETS A11, A21, A 42, A43, DO NOT APPEAR TO | | INDICATE HANDRAILS ON BOTH SIDES OF THE STAIRS. | | | | PER NFPA 101, CH 7 MEANS OF EGRESS | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | 7.2.2.4.1 HANDRAILS. | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | BOTH SIDES, | | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR | | 7.2.2.4.1.6. | | | | PLEASE REVIEW AND CORRECT. | | | | | | 2) SHEET A21 - THE STAIRS BY THE DOUBLE DOORS DOES NOT | | APPEAR TO INDICATE RAILINGS ON BOTH SIDES BUT ALSO NO | | CENTER RAILING. | | | | PER NFPA 101, CH 7 MEANS OF EGRESS | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | 7.2.2.4.1 HANDRAILS. | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | BOTH SIDES, | | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR | | 7.2.2.4.1.6. | | 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT | | THE SIDES OF | | STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS | | SHALL APPLY: | | (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN | | 30 IN. (760 | | MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-12 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-12 |
Time |
09:44 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-10 |
Time |
18:00 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-10 |
Time |
17:39 |
Sent To |
I |
|
Notes |
2020-11-10 17:39:58 | MR. GOMEZ, | | | | PER OUR PHONE CONVERSATION I AM EMAILING YOU TO RELEASE | | PERMIT 20090998 PROVISO. WE WILL COMPLETE THE REVISIONS | | AS THEY RELATE TO ALL OF THE COMMENTS | | AND WILL GET A SIGNATURE ON SP1 AS REQUESTED. THE | | ARCHITECT AND THE DESIGN PLANNER HAVE BOTH BEEN COPIED | | ON THIS EMAIL AS WELL. | | ADDITIONALLY, WE UNDERSTAND THAT NO INSPECTIONS WILL BE | | COMPLETED PRIOR TO ALL COMMENTS BEING ADDRESSED. | | | | THANK YOU IN ADVANCE FOR YOUR GUIDANCE AND ASSISTANCE | | IN THIS MATTER. | | | | BEST REGARDS | | | | BOB BLACK | | SUPERINTENDENT | | HEDRICK BROTHERS CONSTRUCTION | | | | C 561-602-7364 | | E [email protected] | | 2200 CENTREPARK WEST DRIVE | | WEST PALM BEACH, FLORIDA 33409 | CGC013137 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-11-10 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-11-05 |
Time |
15:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-11-03 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-10-27 |
Time |
15:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-10-27 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-10-05 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-12 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-12 |
Time |
09:21 |
Sent To |
|
|
Notes |
2020-11-12 10:15:10 | SIGNATURE REVIEW PROVISO: | | | | 1- SITE PLAN DRAWING SP-1 FROM URBAN DESIGN STUDIO WAS | | UPLOADED WITH COPY OF DESIGN PROFESSIONAL SEAL AND | | SIGNATURE. PROVIDE DRAWING WITH ORIGINAL SIGNATURE AS | | REQUIRED BY F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR | | PUBLIC RECORDS. | | | | 2- SITE ENGINEERING PLAN SHEET C1.0 OF THE ENGINEER'S | | SIGNATURE. PROVIDE DRAWING WITH ORIGINAL SIGNATURE AS | | REQUIRED BY F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR | | PUBLIC RECORDS. | | | | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE | | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL | | AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL | | FOR RECORDS RETENTION. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
F |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-10 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-10 |
Time |
17:53 |
Sent To |
|
|
Notes |
2020-11-10 17:59:54 | SIGNATURE REVIEW COMMENTS | | | | 1- SITE PLAN DRAWING SP-1 FROM URBAN DESIGN STUDIO | | DOESN'T HAVE ANY SEAL AND SIGNATURE. NEEDS TO BE SIGNED | | AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD WHEN | | SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. | | | | | | 2- SITE ENGINEERING PLAN SHEET C1.0 SUBMITTED DON'T | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE. PLANS SUBMITTED | | HAVE A COPY OF THE ENGINEER'S SIGNATURE. PLANS NEED TO | | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF | | RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER | | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | | | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE | | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL | | AND SIGNATURE MAY BE DROPPED IN CITY HALL FOR RECORDS | | RETENTION. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-06 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-06 |
Time |
13:44 |
Sent To |
|
|
Notes |
2020-11-06 13:46:42 | SIGNATURE REVIEW COMMENTS NOT ADDRESSED. | | | | 1- ALL THE LANDSCAPE AND HARDSCAPE PLANS FROM URBAN | | DESIGN STUDIO NEED TO BE PROPERLY SIGNED AND SEALED BY | | THE LICENSED DESIGN PROFESSIONAL. PLANS MAY BE | | SUBMITTED WITH A DIGITAL SIGNATURE OR HARD COPIES WITH | | LICENSED DESIGN PROFESSIONAL SEAL AND SIGNATURE MAY BE | | DROPPED IN CITY HALL FOR RECORDS RETENTION. | | | | NOTE: ACCORDING TO ZONING THESE PLANS ARE TO BE | | SUBMITTED UNDER THE SEPARATE LANDSCAPE PERMIT. SEE | | ZONING COMMENTS. | | | | 2- SITE ENGINEERING PLAN SHEET C1.0 SUBMITTED DON'T | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE. PLANS SUBMITTED | | HAVE A COPY OF THE ENGINEER'S SIGNATURE. PLANS NEED TO | | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF | | RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER | | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE | | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL | | AND SIGNATURE MAY BE DROPPED IN CITY HALL FOR RECORDS | | RETENTION. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-03 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-03 |
Time |
12:47 |
Sent To |
|
|
Notes |
2020-11-03 12:48:36 | SIGNATURE REVIEW COMMENTS NOT ADDRESSED. | | | | 1- ALL THE LANDSCAPE AND HARDSCAPE PLANS FROM URBAN | | DESIGN STUDIO NEED TO BE PROPERLY SIGNED AND SEALED BY | | THE LICENSED DESIGN PROFESSIONAL. PLANS MAY BE | | SUBMITTED WITH A DIGITAL SIGNATURE OR HARD COPIES WITH | | LICENSED DESIGN PROFESSIONAL SEAL AND SIGNATURE MAY BE | | DROPPED IN CITY HALL FOR RECORDS RETENTION. | | | | NOTE: ACCORDING TO ZONING THESE PLANS ARE TO BE | | SUBMITTED UNDER THE SEPARATE LANDSCAPE PERMIT. SEE | | ZONING COMMENTS. | | | | 2- SITE ENGINEERING PLAN SHEET C1.0 SUBMITTED DON'T | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE. PLANS SUBMITTED | | HAVE A COPY OF THE ENGINEER'S SIGNATURE. PLANS NEED TO | | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF | | RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER | | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE | | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL | | AND SIGNATURE MAY BE DROPPED IN CITY HALL FOR RECORDS | | RETENTION. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-10-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-10-23 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-10-23 |
Time |
10:33 |
Sent To |
|
|
Notes |
2020-10-23 10:47:24 | 1- ALL THE LANDSCAPE AND HARDSCAPE PLANS FROM URBAN | | DESIGN STUDIO NEED TO BE PROPERLY SIGNED AND SEALED BY | | THE LICENSED DESIGN PROFESSIONAL. PLANS MAY BE | | SUBMITTED WITH A DIGITAL SIGNATURE OR HARD COPIES WITH | | LICENSED DESIGN PROFESSIONAL SEAL AND SIGNATURE MAY BE | | DROPPED IN CITY HALL FOR RECORDS RETENTION. | | | | NOTE: ACCORDING TO ZONING THESE PLANS ARE TO BE | | SUBMITTED UNDER THE SEPARATE LANDSCAPE PERMIT. SEE | | ZONING COMMENTS. | | | | 2- SITE ENGINEERING PLAN SHEET C1.0 SUBMITTED DON'T | | HAVE THE ENGINEER'S ORIGINAL SIGNATURE. PLANS SUBMITTED | | HAVE A COPY OF THE ENGINEER'S SIGNATURE. PLANS NEED TO | | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF | | RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER | | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE | | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL | | AND SIGNATURE MAY BE DROPPED IN CITY HALL FOR RECORDS | | RETENTION. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2020-11-10 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2020-11-10 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2020-11-03 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2020-11-03 |
Time |
14:43 |
Sent To |
|
|
Notes |
2020-11-03 15:01:46 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 11.03.2020 | | PERMIT NO.: 20090998 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. [ PARTIALLY SATISFIED ] - LANDSCAPE PLANS NEED TO BE | | REMOVED FROM THE MAIN BUILDING PERMIT AND SUBMITTED AS | | A SEPARATE LANDSCAPE PERMIT. | | | | 1.1 [ NEW COMMENT ] - PLEASE PROVIDE THE PERMIT # FOR | | THE LANDSCAPE PERMIT...I WAS UNABLE TO FIND WHERE SUCH | | PERMIT HAD BEEN APPLIED FOR. | | | | 2. [ PARTIALLY SATISFIED ] - SITE PLAN (SHEET SP-1) IS | | LACKING A LOT OF DETAIL. | | | | 2.1. [ PARTIALLY SATISFIED ] - WHAT ARE THE DASHED | | LINES WITH WHAT APPEARS TO BE FOUR (4) POSTS IN THE NEW | | COURTYARD? IS THIS A TRELLIS (AS INDICATED ON THE | | HARDSCAPE AND LANDSCAPE PLAN)? DETAILS NEED TO BE | | PROVIDED. | | | | 2.1.1. [ NEW COMMENT ] - THERE ARE TWO (2) VERSIONS OF | | THE SITE PLAN IN THE SYSTEM. IT APPEARS THAT VERSIONING | | OF THE PLANS WAS NOT DONE PROPERLY WHEN UPLOADING THE | | PLANS. PLEASE REMOVE THE OLD SITE PLAN. THE NEW SITE | | PLAN HAS SATISFIED THE COMMENT. | | | | 2.2. [ PARTIALLY SATISFIED ] - FENCING NEEDS TO BE | | LABELED. | | | | 2.2.1. [ NEW COMMENT ] - [ NEW COMMENT ] - THERE ARE | | TWO (2) VERSIONS OF THE SITE PLAN IN THE SYSTEM. IT | | APPEARS THAT VERSIONING OF THE PLANS WAS NOT DONE | | PROPERLY WHEN UPLOADING THE PLANS. PLEASE REMOVE THE | | OLD SITE PLAN. THE NEW SITE PLAN HAS SATISFIED THE | | COMMENT. | | | | 2.3. [ PARTIALLY SATISFIED ] - DETAILS NEED TO BE | | PROVIDED FOR THE PROPOSED FENCING. | | | | 2.3.1 [ NEW COMMENT ] - THERE ARE TWO (2) VERSIONS OF | | THE SITE PLAN IN THE SYSTEM. IT APPEARS THAT VERSIONING | | OF THE PLANS WAS NOT DONE PROPERLY WHEN UPLOADING THE | | PLANS. PLEASE REMOVE THE OLD SITE PLAN. THE NEW SITE | | PLAN HAS SATISFIED THE COMMENT. | | | | 2.4. [ PARTIALLY SATISFIED ] - VISIBILITY TRIANGLE | | NEEDS TO BE SHOWN AND ENSURE THAT THERE ARE NO | | IMPROVEMENTS WITHIN THE VISIBILITY TRIANGLE THAT ARE | | BETWEEN 18? AND 8? IN HEIGHT. | | | | 2.4.1 [ NEW COMMENT ] - THERE ARE TWO (2) VERSIONS OF | | THE SITE PLAN IN THE SYSTEM. IT APPEARS THAT VERSIONING | | OF THE PLANS WAS NOT DONE PROPERLY WHEN UPLOADING THE | | PLANS. PLEASE REMOVE THE OLD SITE PLAN. THE NEW SITE | | PLAN HAS SATISFIED THE COMMENT. | | | | 3. [ NOT SATISFIED ] - WHY WAS THE HARDSCAPE PLAN FOR | | THE EAST PLAZA (HS-1) INCLUDED IN THIS PERMIT? THERE | | WERE EVEN THREE (3) COPIES OF SHEET HS-1 SUBMITTED. | | THIS AREA WAS PERMITTED SEPARATELY AND SHOULD BE | | REMOVED FROM THIS PLAN SET (PAGE #S MAY NEED TO BE | | ADJUSTED). | | | | 4. [ NOT SATISFIED ] - SURVEY DOES NOT ACCURATELY | | REFLECT THE CURRENT CONDITIONS OF THE SITE. PLEASE | | PROVIDE THE MOST RECENT SURVEY. | | | | 5. [ PARTIALLY SATISFIED ] - PURSUANT TO SEC. | | 94-408.F.2.E. OF THE CITY'S ZONING AND LAND DEVELOPMENT | | REGULATIONS, FREESTANDING SIGNS SHALL BE A MINIMUM OF | | FIVE (5) FEET FROM THE RIGHT-OF-WAY. | | | | 5.1 [ NEW COMMENT ] - THERE ARE TWO (2) VERSIONS OF THE | | SITE PLAN IN THE SYSTEM. IT APPEARS THAT VERSIONING OF | | THE PLANS WAS NOT DONE PROPERLY WHEN UPLOADING THE | | PLANS. PLEASE REMOVE THE OLD SITE PLAN. THE NEW SITE | | PLAN HAS SATISFIED THE COMMENT. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-10-09 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2020-10-09 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2020-10-09 |
Time |
11:20 |
Sent To |
|
|
Notes |
2020-10-09 11:31:38 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 10.09.2020 | | PERMIT NO.: 20090998 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. LANDSCAPE PLANS NEED TO BE REMOVED FROM THE MAIN | | BUILDING PERMIT AND SUBMITTED AS A SEPARATE LANDSCAPE | | PERMIT. | | | | 2. SITE PLAN (SHEET SP-1) IS LACKING A LOT OF DETAIL. | | | | 2.1. WHAT ARE THE DASHED LINES WITH WHAT APPEARS TO BE | | FOUR (4) POSTS IN THE NEW COURTYARD? IS THIS A TRELLIS | | (AS INDICATED ON THE HARDSCAPE AND LANDSCAPE PLAN)? | | DETAILS NEED TO BE PROVIDED. | | | | 2.2. FENCING NEEDS TO BE LABELED. | | | | 2.3. DETAILS NEED TO BE PROVIDED FOR THE PROPOSED | | FENCING. | | | | 2.4. VISIBILITY TRIANGLE NEEDS TO BE SHOWN AND ENSURE | | THAT THERE ARE NO IMPROVEMENTS WITHIN THE VISIBILITY | | TRIANGLE THAT ARE BETWEEN 18? AND 8? IN HEIGHT. | | | | 3. WHY WAS THE HARDSCAPE PLAN FOR THE EAST PLAZA (HS-1) | | INCLUDED IN THIS PERMIT? THERE WERE EVEN THREE (3) | | COPIES OF SHEET HS-1 SUBMITTED. THIS AREA WAS PERMITTED | | SEPARATELY AND SHOULD BE REMOVED FROM THIS PLAN SET | | (PAGE #S MAY NEED TO BE ADJUSTED). | | | | 4. SURVEY DOES NOT ACCURATELY REFLECT THE CURRENT | | CONDITIONS OF THE SITE. PLEASE PROVIDE THE MOST RECENT | | SURVEY. | | | | 5. PURSUANT TO SEC. 94-408.F.2.E. OF THE CITY?S ZONING | | AND LAND DEVELOPMENT REGULATIONS, FREESTANDING SIGNS | | SHALL BE A MINIMUM OF FIVE (5) FEET FROM THE | | RIGHT-OF-WAY. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|