Plan Review Details - Permit 20090986
Plan Review Stops For Permit 20090986
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By rmcdouga Date 2020-10-08 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2020-10-08 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-01 Cont ID  
Sent By rmcdouga Date 2020-10-01 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2020-10-01 Time 15:34 Sent To  
Notes
2020-10-01 16:01:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 DOUBLE HUNG WINDOWS IS FOR NOT IMPACT RATED WINDOWS.
 SPECIFY ON THE DRAWING THAT THERE ARE EXISTING IMPACT
 PROTECTION DEVICES. FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-08 Cont ID  
Sent By rmcdouga Date 2020-10-08 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2020-10-03 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-01 Cont ID  
Sent By rmcdouga Date 2020-10-01 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2020-09-25 Time 08:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-01 Cont ID  
Sent By rmcdouga Date 2020-10-01 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2020-10-01 Time 15:35 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved