Plan Review Details - Permit 20090918
Plan Review Stops For Permit 20090918
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By pvalenti Date 2020-10-22 Time 09:48 Rev Time 0.00
Received By pvalenti Date 2020-10-22 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-09 Cont ID  
Sent By pvalenti Date 2020-10-09 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2020-10-09 Time 07:00 Sent To  
Notes
2020-10-09 08:09:16PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PLEASE CONFIRM THAT THE WIDTH OF THE
 GENERATOR SLAB IS ACCEPTABLE TO MEET THE REQUIREMENTS
 OF THE MANUFACTURER'S SPECIFICATIONS AS THE GENERAC
 SPECIFICATION NOTES RECOMMEND A 49" WIDTH AND THE
 SUBMITTED PAD INFORMATION IS FOR A 46" WIDTH.
 2) FBC B/WPB AMENDMENTS 109.3, PLEASE PROVIDE A COST
 BREAK DOWN OF THE VALUATION OF THE JOB.
 3) FBC B 107.2.5, PLEASE PROVIDE A SITE PLAN INDICATING
 THE SET BACK MEASUREMENTS INCLUDING THE LOCATIONS OF
 ADJACENT STRUCTURES.
 4) FBC B/WPB AMENDMENTS 107.1, PLEASE PROVIDE
 VERIFFIABLE ENGINEER'S SIGNATURE AND SEAL ON GENERATOR
 PAD ENGINEERING SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 16:02 Rev Time 0.00
Received By jleahy Date 2020-10-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-09 Cont ID  
Sent By jleahy Date 2020-10-09 Time 17:09 Rev Time 0.00
Received By jleahy Date 2020-10-09 Time 16:22 Sent To  
Notes
2020-10-09 17:18:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF PERMIT IS TO REFLECT ALL MATERIALS,
 EQUIPMENT AND LABOR FOR A COMPLETE SYSTEM (3100)
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) ATS ARE THEY SERVICE ENTRANCE RATED?
  
 3) 10 X 10 GUUTER AT SERVICE HOW MANY CONDUCTORS ARE
 GOING TO BE IN THIS GUTTER?
  
 4) FEEDER TAP OFF GENERATOR WHICH SECTION DOES IT
 COMPLY WITH IN 240.21?
  
 5) GROUNDING ELECTRODE SHOWN DOES NOT MEET THE CODE IT
 IS EITHER DONE IN THE LINE GITTER AT THE TOP OR IN EACH
 INDIVIDUAL DISCONNECT UNDER THE GUTTER. 250.64(D)
  
 6) SHOW LOCATION OF THE GUTTER AT THE SERVICE IN
 RELATION TOO THE GENERATOR (DISTANCE)
  
 7) FEEDER OF 400A TRANSFER SWICH ONLY 4/0 CONDUCTORS?
  
 8) LOADS BEING FED BY GERNERATOR? LOAD CALCULATION
 REQUIRED.
  
 9) IS THIS LEGALLY REQUIRED SYSTEM? PER 702.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By pleduc Date 2020-10-06 Time   Rev Time 0.00
Received By pleduc Date 2020-10-02 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 16:03 Rev Time 0.00
Received By jleahy Date 2020-10-20 Time 07:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-09 Cont ID  
Sent By jleahy Date 2020-10-09 Time 17:18 Rev Time 0.00
Received By jleahy Date 2020-09-30 Time 16:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By pvalenti Date 2020-10-22 Time 09:48 Rev Time 0.00
Received By pvalenti Date 2020-10-22 Time 09:07 Sent To  
Notes
2020-10-22 09:49:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY SUBMITTED ORIGINAL PAPER
 SIGNATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-09 Cont ID  
Sent By pvalenti Date 2020-10-09 Time 07:34 Rev Time 0.00
Received By pvalenti Date 2020-10-09 Time 07:34 Sent To  
Notes
2020-10-09 07:37:12PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED
 PAPER ORIGINAL WITH A WET SIGNATURE TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6673.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By aaponte Date 2020-10-06 Time 09:42 Rev Time 0.00
Received By elevesqu Date 2020-10-06 Time 09:42 Sent To  
Notes
***NONE***