Plan Review Details - Permit 20090912
Plan Review Stops For Permit 20090912 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-09-30 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-09-30 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-09-30 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-09-29 |
Time |
15:36 |
Sent To |
|
|
Notes |
2020-09-30 09:17:31 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A FLOOR PLAN SHOWING THE SIZE AND LOCATION OF | | THE OPENINGS. FBC 107.2.1 | | | | 2) THIS PROJECT IS IN A HIGH RISE BUILDING WITH A MEAN | | ROOF HEIGHT OF MORE THAN 60 FEET AND LOCATED IN | | EXPOSURE CATEGORY D. A FLORIDA LICENSED ENGINEER IS | | REQUIRED TO DETERMINE THE DESIGN PRESSURES FOR THE | | OPENINGS. SUBMIT SIGNED AND SEALED WIND LOAD PRESSURES | | FOR THE OPENINGS WITH THE DESIGN DATA (WIND SPEED, ROOF | | HEIGHT, WALL ZONE, ETC.) SPECIFIED ON THE DRAWING. FBC | | 1609 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-11-01 |
|
|
Cont ID |
|
Sent By |
ccarvaja |
Date |
2020-11-01 |
Time |
18:48 |
Rev Time |
0.00 |
Received By |
ccarvaja |
Date |
2020-11-01 |
Time |
18:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-09-30 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-09-22 |
Time |
07:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-11-03 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-11-03 |
Time |
14:47 |
Sent To |
|
|
Notes |
2020-11-03 15:09:22 | ANTHONY LYNN MILLER PE. RATIONAL ANALYSIS WITH DIGITAL | | SIGNATURE. | | ENGINEER'S EMERGENCY RULE | | EMERGENCY RULE APPLIED 61G15ER20-4 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-10-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-10-14 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-10-14 |
Time |
15:35 |
Sent To |
|
|
Notes |
2020-10-14 16:14:02 | 1- THE RATIONAL ANALYSIS CALCULATIONS SEEM TO HAVE A | | COLOR COPY OF THE ENGINEER'S SEAL AND SIGNATURE. | | ENGINEER CALCULATIONS SUBMITTED DON'T HAVE THE | | ENGINEER'S ORIGINAL SIGNATURE. CALCULATIONS NEED TO | | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF | | RECORD AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER | | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | | | IN ORDER TO EXPEDITE THE REVIEW PROCESS, IT IS | | PREFERABLE TO UPLOAD THE ENGINEERING CALCULATIONS WITH | | A DIGITAL SIGNATURE TO PROJECTDOX. OTHERWISE, HARD COPY | | WITH ORIGINAL SEAL/SIGNATURE IS REQUIRED. | | | | NOTE: | | ENGINEERING EXPRESS DESIGN PRESSURES SUBMITTED HAVE | | ENGINEER'S EMBOSSED SEAL AND ORIGINAL SIGNATURE. | | | | THERE ARE THERE TWO OPTIONS TO ADDRESS THIS ISSUE: | | (1)SUBMIT PLAN AND CALCULATIONS WITH ENGINEER'S | | ORIGINAL SEAL/SIGNATURE OR | | (2) UPLOAD TO PROJECTDOX PLAN AND CALCULATIONS WITH | | ENGINEER'S DIGITAL SIGNATURE. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-09-30 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-09-29 |
Time |
15:36 |
Sent To |
|
|
Notes |
2020-09-30 09:07:17 | THE WIND LOAD PRESSURES AND THE RATIONAL ANALYSIS FROM | | THE ENGINEERS WILL HAVE TO BE SIGNED AND SEALED. | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER | | VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE | | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS | | REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER | | FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 & | | 61G15 |
|
|
|