Plan Review Details - Permit 20090905
Plan Review Stops For Permit 20090905
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-10 Cont ID  
Sent By rmcphers Date 2020-11-10 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-11-10 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-04 Cont ID  
Sent By ppetty Date 2020-11-04 Time 11:51 Rev Time 0.00
Received By ppetty Date 2020-11-04 Time 11:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By ppetty Date 2020-10-02 Time 08:22 Rev Time 0.00
Received By ppetty Date 2020-10-02 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-10 Cont ID  
Sent By rmcphers Date 2020-11-10 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-10-30 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-27 Cont ID  
Sent By cpuell Date 2020-10-27 Time 17:48 Rev Time 0.00
Received By cpuell Date 2020-09-24 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 16:03 Rev Time 0.00
Received By lcrespo Date 2020-11-03 Time 15:54 Sent To  
Notes
2020-11-03 16:04:1511/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-09-28 Cont ID  
Sent By lcrespo Date 2020-09-28 Time 13:54 Rev Time 0.00
Received By lcrespo Date 2020-09-28 Time 13:51 Sent To  
Notes
2020-09-28 13:54:4809/28/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SHEET ONE ON FILTER EQUIPMENT SIZE IT CALLS FOR 200
 SF AND YOU SPEC OUT CS 150 WHICH IS 150 SF PLEASE
 CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. SHEET ONE FOR PUMP EQUIPMENT SIZE CALLS FOR A
 VSFHP165JEP YOU HAVE SPECS FOR A VSFHP185DV2A PLEASE
 CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 4. THE PLANS ARE VERY BLURRY AND MOST NUMBERS CAN?T BE
 MADE OUT SO PLEASE SUBMIT LEGIBLE PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. ALL PAGES NEED TO HAVE A DIGITAL SIGNATURE PER THE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By lcrespo Date 2020-09-29 Time 15:49 Rev Time 0.00
Received By lcrespo Date 2020-09-29 Time 15:49 Sent To  
Notes
2020-09-29 15:50:07DUPLICATE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-10 Cont ID  
Sent By rmcphers Date 2020-11-10 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-11-10 Time 14:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By rmcphers Date 2020-10-08 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2020-10-08 Time 15:34 Sent To  
Notes
2020-10-08 15:35:10SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-26 Cont ID  
Sent By kalexand Date 2020-10-26 Time 12:10 Rev Time 0.00
Received By kalexand Date 2020-10-26 Time 12:10 Sent To I
Notes
***NONE***