Plan Review Details - Permit 20090894
Plan Review Stops For Permit 20090894
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-11-12 Cont ID  
Sent By shill Date 2020-11-12 Time 09:16 Rev Time 0.00
Received By shill Date 2020-11-12 Time 09:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By jwitmer Date 2020-10-21 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2020-10-21 Time 08:33 Sent To  
Notes
2020-10-21 09:13:52COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-28 Cont ID  
Sent By jwitmer Date 2020-11-28 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2020-11-28 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By jwitmer Date 2020-10-21 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2020-10-21 Time 08:32 Sent To  
Notes
2020-10-21 09:54:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090894
 ADD: 1100 25TH ST.
 CONT: NORTHLAKE CONSTRUCTION CO.
 TEL: 561-202-7044
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 21ST/ 2020
 ACTION: DENIED
  
 1) THE STRUCTURAL SHEETS SHOW LARGER OVERHEAD DOOR
 OPENINGS BEING MODIFIED. SHEET S-3 AND S-4 SHOW THE
 EXISTING AND PROPOSED NEW OVERHEAD DOOR OPENINGS. NONE
 OF THE STRUCTURAL PLANS PROVIDE THE WIND DESIGN
 CRITERIA FOR THESE OPENINGS.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 2A) THE PRODUCT APPROVAL SUBMITTED FL 19313-R1
 MANUFACTURER ROLLING DOOR HAS NOT BEEN REVIEWED BY THE
 DESIGNER OF RECORD. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING(SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD
 HAS INDICATED WITHIN THE PRODUCT APPROVAL REPORT # FL
 19313R-1 WHICH SLAT IS GOING TO BE INSTALLED SLAT 1 OR
 SLAT 1A, SEE PAGE 3 OF 6 IN THE TECHNICAL SHEETS.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET S-4 WEST ELEVATIONS, CLARIFICATION NEEDED, IT
 WOULD APPEAR THERE IS A EXISTING UPPER TIE BEAM AND
 LOWER TIE BEAM. THE PLANS INDICATE TO CUT 4 FEET FROM
 THE OVERALL TIE BEAM. NOTE STATES THE CONTRACTOR IS TO
 X-RAY AND CONFIRM AT LEAST 3 LEVELS OF STEEL TIED INTO
 COLUMNS ON BOTH SIDES. THE QUESTION IS THE LOWER TIE
 BEAM WOULD HAVE NORMALLY BEEN DESIGNED WITH HOOPS TO
 CARRY THE LOADS OVER THE DOOR OPENING. THE CONCERN IS
 IF THERE IS NO HOOPS OR STIRRUPS IN THE UPPER BEAM,
 WILL VERIFICATION OF THE NUMBER OF HORIZONTAL BARS BE
 ENOUGH? IS THE WEST WALL CARRYING THE ROOF FRAMING
 MEMBERS OR ARE THE ROOF FRAMING MEMBERS PARALLELING THE
 WEST WALL WITH MINIMUM ROOF LOADING? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED TO DETERMINE
 VERIFICATION OF JOBSITE CONDITIONS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 08:37 Rev Time 0.00
Received By equinone Date 2020-12-04 Time 08:37 Sent To  
Notes
2020-12-04 08:39:38CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: APPROVED. SEE COMMENTS BELOW.
  
 1) THERE ARE SOME DISCREPANCIES REGARDING THE NUMBER
 AND LOCATION OF AHUS AND A/C UNITS ON THE DRAWINGS: E5
 SHOWS TWO AHU AND TWO A/C UNITS ON PANEL SCHEDULES, E1
 SHOWS THREE AHUS AND ONE A/C, E7 SHOWS ONE UNIT AND
 MECHANICAL SHEET M1 SHOWS ONE UNIT E7. PLEASE CLARIFY
 AND ADJUST DRAWINGS, PANEL SCHEDULES AND CALCULATIONS
 AS REQUIRED. FBC 107.
  
 CORRECTED: CUSTOMER CLARIFIED THAT ONLY ONE AC AND ONE
 AHU ARE BEING INSTALLED AS SHOWN ON PANEL SCHEDULE.
 THIS MATCHES THE CORRECTED MECHANICAL DRAWINGS.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By equinone Date 2020-11-02 Time 10:09 Rev Time 0.00
Received By equinone Date 2020-11-02 Time 08:52 Sent To  
Notes
2020-11-02 10:27:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) THERE ARE SOME DISCREPANCIES REGARDING THE NUMBER
 AND LOCATION OF AHUS AND A/C UNITS ON THE DRAWINGS: E5
 SHOWS TWO AHU AND TWO A/C UNITS ON PANEL SCHEDULES, E1
 SHOWS THREE AHUS AND ONE A/C, E7 SHOWS ONE UNIT AND
 MECHANICAL SHEET M1 SHOWS ONE UNIT E7. PLEASE CLARIFY
 AND ADJUST DRAWINGS, PANEL SCHEDULES AND CALCULATIONS
 AS REQUIRED. FBC 107.
  
 2) ALL OF A/C AND AHUS SHOULD HAVE ONE GFCI RECEPTACLE
 WITHIN 25 FEET. ONCE CORRECTIONS MENTIONED ABOVE ARE
 MADE PLEASE MAKE SURE TO INCLUDE THESE RECEPTACLES ON
 DRAWINGS. NEC 210.63.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By pleduc Date 2020-10-08 Time   Rev Time 0.00
Received By pleduc Date 2020-10-08 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-01-22 Time   Rev Time 0.00
Received By ccarvaja Date 2021-01-05 Time 19:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-12-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-08 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-08 Cont ID  
Sent By lmarchan Date 2020-12-08 Time 07:42 Rev Time 0.00
Received By lmarchan Date 2020-11-24 Time 18:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-23 Cont ID  
Sent By lmarchan Date 2020-11-23 Time 14:58 Rev Time 0.00
Received By medwards Date 2020-10-01 Time 09:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-10-21 Cont ID  
Sent By jwitmer Date 2020-10-21 Time 09:14 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By medwards Date 2020-12-07 Time 17:28 Rev Time 0.00
Received By medwards Date 2020-12-07 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 09:38 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 08:15 Sent To  
Notes
2020-10-28 09:38:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090894
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTSIDE AIR CALCULATIONS. FBC M TABLE
 403.3.1.1
  
 2) SHEET M-2 PROVIDES A DETAIL OF THE AHU HANGING ABOVE
 THE CEILING, PLEASE SHOW RETURN AIR PATH FOR OFFICE 1,4
 AND 5. PLEASE PROVIDE A DETAIL SHOWING THE RETURN AIR
 DUCT FROM AHU ABOVE CEILING TO LAY IN CEILING. FBC M
 602.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 07:38 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-12-22 Cont ID  
Sent By ccole Date 2020-12-22 Time 09:44 Rev Time 0.00
Received By ccole Date 2020-12-22 Time 07:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By ccole Date 2020-12-01 Time 16:29 Rev Time 0.00
Received By ccole Date 2020-12-01 Time 14:34 Sent To  
Notes
2020-12-01 16:29:252ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20090894
 12/1/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2 & P3: THE DRINKING FOUNTAIN FIXTURE SHALL
 CONNECT TO THE 4 IN. DRAIN AT A POINT DOWNSTREAM OF THE
 WATER CLOSET AND THE BATHROOM WET VENT SYSTEM- SECTION
 912.1 FBC P.
  
 2) P1 & P3: PLEASE LABEL THE HWR LINE FOR CLARITY-
 SECTION 107.2.1 WPB.
  
 3) P1 & P3: PROVIDE KEYNOTE #2 TMV AT ALL LAVATORY
 LOCATIONS- SECTION 416.5 FBC P.
  
 4) P3: PROVIDE A WATER HAMMER ARRESTOR FOR THE CW LINE
 TO THE DRINKING FOUNTAINS- SECTION 604.9 FBC P.
  
 5) P1, P2, P3: THE "TYPICAL WATER ISOMETRIC" SHOWS A
 WASHING MACHINE THAT IS NOT SHOWN ON THE OTHER PLUMBING
 DRAWINGS. PLEASE ADD THE WASHING MACHINE OR REMOVE IT
 FROM THE ISO- SECTION 107.2.1 WPB.
  
 6) P3 WATER HEATER DETAILS: PLEASE CORRECT THE DETAIL
 IN COMPLIANCE WITH SECTIONS 607.2.2 & 607.3 FBC P.
  
 A) SECTION 607.2.2: IT APPEARS THAT A MASTER TMV IS
 BEING INSTALLED WHICH REQUIRES THE HOT WATER OR
 TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
  
 B) SECTION 607.3: WHERE A STORAGE WATER HEATER IS
 SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK
 VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER
 (CHECK VALVE), A THERMAL EXPANSION CONTROL DEVICE SHALL
 BE CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE
 AT A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES,
 PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS.
 THERMAL EXPANSION CONTROL DEVICES SHALL BE SIZED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND
 SHALL BE SIZED SUCH THAT THE PRESSURE IN THE WATER
 DISTRIBUTION SYSTEM SHALL NOT EXCEED THAT REQUIRED BY
 SECTION 604.8. PLEASE NOTE THAT PRESSURE OR TEMPERATURE
 RELIEF VALVES SHALL NOT BE USED AS A MEANS OF
 CONTROLLING THERMAL EXPANSION- SECTION 504.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By ccole Date 2020-10-26 Time 18:22 Rev Time 0.00
Received By ccole Date 2020-10-26 Time 17:41 Sent To  
Notes
2020-10-26 18:22:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20090894
 10/26/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET CS-1: THE PLUMBING FIXTURE CALCULATIONS DO NOT
 INCLUDE THE REQUIRED SERVICE SINKS FOR BUSINESS AND
 STORAGE OCCUPANCIES- SECTION 810.1 FBC EX AND TABLE
 403.3 FBC P.
  
 2) PROVIDE PLUMBING PIPING LAYOUT PLANS AND RISER
 DRAWINGS- SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 3) SHEETS A-1: SHOW THE REQUIRED 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC.
 SHOW THE EXISTING DOORS WILL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR THE FIXTURE- 623.3.
  
 4) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 07:39 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 07:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By ccole Date 2020-12-22 Time 10:01 Rev Time 0.00
Received By ccole Date 2020-12-22 Time 10:01 Sent To  
Notes
2020-12-22 10:18:05SIGNATURE REVIEW
 12/22/2020
  
 1) THE NEW PLUMBING PLANS SHEETS- P1. P2. & P3 ARE NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD-
 FL. STATUTE 471.025, AND SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
  
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-26 Cont ID  
Sent By equinone Date 2020-10-20 Time 16:17 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 16:17 Sent To  
Notes
2020-10-20 16:18:07DIGITAL SIGNATURE WILL NEED TO BE VERIFIED AGAIN WHEN
 ARCHITECT RESUBMITS DRAWINGS. EJQ
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By kalexand Date 2020-11-20 Time 16:07 Rev Time 0.00
Received By kalexand Date 2020-11-20 Time 16:07 Sent To I
Notes
***NONE***