Plan Review Details - Permit 20090811
Plan Review Stops For Permit 20090811
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By pvalenti Date 2020-10-21 Time 15:51 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 14:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By pvalenti Date 2020-10-07 Time 13:07 Rev Time 0.00
Received By pvalenti Date 2020-10-07 Time 07:52 Sent To  
Notes
2020-10-07 13:08:10ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By pvalenti Date 2020-10-21 Time 14:24 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By pvalenti Date 2020-10-07 Time 13:57 Rev Time 0.00
Received By pvalenti Date 2020-10-07 Time 07:52 Sent To  
Notes
2020-10-07 13:33:11PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE CLARIFY AND ADJUST PLANS, AS
 SHEET A-2 INDICATES THAT THERE ARE FIRE SPRINKLERS THAT
 MAY BE ADJUSTED AND SHEET T-1 INDICATES THAT THERE ARE
 NO FIRE SPRINKLERS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 17:54 Rev Time 0.00
Received By jleahy Date 2020-09-19 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-22 Cont ID  
Sent By pleduc Date 2020-09-22 Time   Rev Time 0.00
Received By pleduc Date 2020-09-22 Time 13:52 Sent To  
Notes
2020-09-22 14:01:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 10:24 Rev Time 0.00
Received By lcrespo Date 2020-10-20 Time 07:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-07 Cont ID  
Sent By pvalenti Date 2020-10-07 Time 14:01 Rev Time 0.00
Received By pvalenti Date 2020-09-18 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By pvalenti Date 2020-10-22 Time 08:13 Rev Time 0.00
Received By pvalenti Date 2020-10-22 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By medwards Date 2020-09-24 Time 07:12 Rev Time 0.00
Received By medwards Date 2020-09-24 Time 06:36 Sent To  
Notes
2020-09-24 07:13:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090811
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.1- PLEASE SHOW THE RETURN AIR PATH FROM
 WAITING 104 TO AHU-2. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 10:23 Rev Time 0.00
Received By lcrespo Date 2020-10-22 Time 09:00 Sent To  
Notes
2020-10-22 10:24:3010/22/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By jesmith Date 2020-09-29 Time 17:08 Rev Time 0.00
Received By jesmith Date 2020-09-29 Time 13:33 Sent To  
Notes
2020-09-29 17:06:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090811 1117 N OLIVE AVE # 101
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER FBC 1210.2.2, WALLS AND PARTITIONS WITHIN 2 FEET
 (610 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PAINTED WALLS DO NOT COMPLY.
 REVISE THE ROOM FINISH SCHEDULE ON PLAN SHEET A-3 TO
 COMPLY.
  
 2.PROVIDE CLEAR FLOOR SPACE FOR BREAKROOM SINK. IF
 PARALLEL APPROACH, SINK SHALL BE CENTERED ON THE SPACE.
 IF FORWARD APPROACH, CABINET AND SINK SHALL BE
 CONSTRUCTED TO COMPLY WITH FBC ACC 306 FOR KNEE AND TOE
 CLEARANCE AND SHALL ACCOMMODATE THE FULL WIDTH OF THE
 REQUIRED 30 X 48 CLEAR FLOOR SPACE.
  
 3.PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT LEAST
 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
 PROVIDE MINIMUM OF ONE ACCESSIBLE EXAM ROOM SINK AND
 PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE SINK.
  
 4.PER WPB FBC 107.2.1, AS A DRINKING FOUNTAIN IS NOT
 REQUIRED BASED ON OCCUPANT LOAD AND NOT BEING PROVIDED,
 DELETE REFERENCES TO SAME ON PLAN SHEET A-3.
  
 5.PER WPB FBC 107.2.1, CLARIFY THE WATER CLOSET SHALL
 BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND
 TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL
 BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION PER FBC ACC 604.2
  
 6.PER WPB FBC 107.2.1, CLARIFY TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS PER FBC ACC 604.8.
  
 7.PLEASE NOTE THAT THE IN-LINE VALVE FOR THE HOT WATER
 RESTROOM WHEN IN THE OFF POSITION EFFECTIVELY KILLS THE
 HOT WATER RECIRCULATION. PROVIDE DEDICATED VALVED HOT
 WATER DROP TO LAVATORY FROM RECIRCULATED LINE TO COMPLY
 WITH FBC PL 606.1.
  
 8.RE: WATER HEATER DETAIL
 A.PER FBC PL 607.3, WHERE A STORAGE WATER HEATER IS
 SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK
 VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER, A
 THERMAL EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO
 THE WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT
 IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING
 VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION
 CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH
 THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM
 SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8.
 B.PER FBC PL 504.6, PROVIDE AN AIR GAP FOR THE T & P
 RELIEF DISCHARGE TO THE PAN.
 C.PER FBC PL 504.2, BOTTOM FED WATER HEATERS AND BOTTOM
 FED TANKS CONNECTED TO WATER HEATERS SHALL HAVE A
 VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF VALVE
 SHALL COMPLY WITH ANSI Z21.22.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS OR DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090811 1117 N OLIVE AVE # 101
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By pvalenti Date 2020-10-21 Time 16:08 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By medwards Date 2020-09-24 Time 07:17 Rev Time 0.00
Received By medwards Date 2020-09-24 Time 07:17 Sent To  
Notes
***NONE***