Plan Review Details - Permit 20090788
Plan Review Stops For Permit 20090788
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By rmcphers Date 2020-10-22 Time 13:31 Rev Time 0.00
Received By rmcphers Date 2020-10-22 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By rmcphers Date 2020-09-30 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2020-09-29 Time 16:03 Sent To  
Notes
2020-09-30 09:57:53SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SHOW THE LOCATION OF THE SMOKE DETECTORS - FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-19 Cont ID  
Sent By jleahy Date 2020-11-19 Time 17:03 Rev Time 0.00
Received By jleahy Date 2020-11-19 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 14:27 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 14:13 Sent To  
Notes
2020-10-28 14:30:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER SHOWS TRANSFER SWITCHES WHERE IS THE
 GENERATOR?
  
 2) GENERATOR REQUIRES A SEPARATE PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jleahy Date 2020-09-23 Time 16:38 Rev Time 0.00
Received By jleahy Date 2020-09-23 Time 16:23 Sent To  
Notes
2020-09-23 16:38:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 DOES NOT LOOK LIKE MINOR CHANGES!!!!
  
 1) OUTLET SPACING ON KITCHEN, PANTRY, AND LAUNDRY ROOM
 COUNTER SPACES.
  
 E3901.4 COUNTERTOP RECEPTACLES.
 IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND
 SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR
 COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTIONS E3901.4.1 THROUGH E3901.4.5
  
 2) SMOKE/CO ALARMS MISSING FROM GUEST ROOM, AND BED
 ROOMS R314, R315 FBC RESIDENTIAL
  
 3) NEED RISER DIAGRAM AND LOAD CALCULATION 215.5
  
 4) DECKS AND BALCONIES NEED OUTLETS. 210.53
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 07:34 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 07:34 Sent To  
Notes
2020-10-21 07:38:29THE GAS PIPING TO THE GENERATOR AND ALL OTHER GAS-FIRED
 EQUIPMENT AND APP;LIANCES SHALL BE UNDER A SEPARATE
 PERMIT. A COMPLETE RISER DRAWING AND EQUIPMENT AND
 APPLIANCE SPECIFICATIONS SHALL BE SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-18 Cont ID  
Sent By shill Date 2020-12-18 Time 11:59 Rev Time 0.00
Received By shill Date 2020-12-01 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-24 Cont ID  
Sent By medwards Date 2020-11-24 Time 15:06 Rev Time 0.00
Received By medwards Date 2020-11-12 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 14:30 Rev Time 0.00
Received By jleahy Date 2020-10-20 Time 13:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-08 Cont ID  
Sent By lmarchan Date 2020-10-08 Time 06:59 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 08:14 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 07:48 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2020-09-30 Cont ID  
Sent By rmcphers Date 2020-09-30 Time 10:15 Rev Time 0.00
Received By rmcphers Date 2020-09-30 Time 10:10 Sent To  
Notes
2020-09-30 10:15:00NOT A SUBSTANTIAL IMPROVEMENT
 5YR = $ 0
 PALM BEACH PROPERTY APPRAISER BUILDING VALUE =
 1,182,016.00 / 2 = 591,008.00
 JOB VALUE = 275,000.00
 AE 7
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 07:31 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 07:12 Sent To  
Notes
2020-10-21 07:33:17NO PLUMBING PLANS WERE SUBMITTED- THE ARCHITECT HAS
 REQUESTED PLUMBING UNDER SERPARATE PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By ccole Date 2020-09-21 Time 15:46 Rev Time 0.00
Received By ccole Date 2020-09-21 Time 15:44 Sent To  
Notes
2020-09-21 15:57:031ST REVIEW FBC-2017 RES.
 PERMIT- 20090788
 9/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE PLUMBING PLANS AND A PLUMBING
 SUB-PERMIT- SECTIONS 105.1, 107.2.1. & 107.3.5.3 WPB.
 THE PLANS SHALL INCLUDE A SCOPE OF WORK OUTLINE,
 PLUMBING RISER DRAWINGS, AND EQUIPMENT SCHEDULES AND
 SPECIFICATIONS FOR NEW OR REPLACED WATER HEATERS.
 PLEASE NOTE THAT A SEPARATE PRIMARY PERMIT IS REQUIRED
 FOR FUEL GAS PIPING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-12-18 Cont ID  
Sent By shill Date 2020-12-18 Time 11:57 Rev Time 0.00
Received By shill Date 2020-12-18 Time 11:57 Sent To  
Notes
2020-12-18 11:58:25PROVISO, CONTRACTOR/OWNER TO PROVIDE S&S DRAWINGS PRIOR
 TO FIRST INSPECTION OR NEW DRAWINGS WILL BE SUBMITTED
 AS A REVISION
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2020-12-18 Time   Rev Time 0.00
Received By shill Date 2020-12-18 Time 11:45 Sent To  
Notes
2020-12-18 11:45:34PLEASE ADDRESS THE PREVIOUS REVIEWERS COMMENTS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-11-24 Cont ID  
Sent By medwards Date 2020-11-24 Time 15:04 Rev Time 0.00
Received By medwards Date 2020-11-24 Time 15:01 Sent To  
Notes
2020-11-24 15:05:33PLEASE ADDRESS THE PREVIOUS REVIEWERS COMMENTS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-22 Cont ID  
Sent By rmcphers Date 2020-10-22 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2020-10-22 Time 13:28 Sent To  
Notes
2020-10-22 13:28:45SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By rmcphers Date 2020-09-30 Time 10:15 Rev Time 0.00
Received By rmcphers Date 2020-09-30 Time 10:15 Sent To  
Notes
2020-09-30 10:16:57SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 3 Status N Date 2020-12-18 Cont ID  
Sent By shill Date 2020-12-18 Time 11:58 Rev Time 0.00
Received By shill Date 2020-12-18 Time 11:58 Sent To  
Notes
2020-12-18 11:58:54INTERIOR ONLY
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By kalexand Date 2020-11-24 Time 08:13 Rev Time 0.00
Received By kalexand Date 2020-11-24 Time 08:13 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-02 Cont ID  
Sent By kalexand Date 2020-10-02 Time 12:06 Rev Time 0.00
Received By kalexand Date 2020-10-02 Time 12:06 Sent To I
Notes
***NONE***