Plan Review Details - Permit 20090781
Plan Review Stops For Permit 20090781
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-10-13 Cont ID  
Sent By ccole Date 2020-10-13 Time 08:06 Rev Time 0.00
Received By ccole Date 2020-10-13 Time 07:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 13:23 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 07:59 Sent To  
Notes
2020-10-05 13:23:261ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090781
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPROVED GENERATOR PERMIT AND PLANS UNDER
 PERMIT- 20080051 WAS FOR A 27 KW GENERATOR. PLEASE
 CORRECT THE RISER TO SHOW THE CORRECT 359,000 BTUH LOAD
 AS INDICATED IN THE GENERATOR SPECS SUBMITTED WITH THE
 PERMIT.
  
 2) THE GENERATOR SPECS SHOW A NATURAL GAS INPUT
 PRESSURE OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING
 SHOWS A REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE
 TO THE GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE
 AND MODEL OF THE SELECTED REGULATOR ON THE RISER.
 SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING
 THE MODEL, INLET AND OUTLET PRESSURES, SPRING
 SELECTION, AND ORIFICE SIZE- SECTION G2421.1 & G2421.2.
 SHOW THE REQUIRED PIPE UNIONS AT THE REGULATOR.
  
 3) THERE IS A 0 VALUE FOR THE PROPOSED GAS PIPING
 INSTALLATION. PLEASE SUBMIT A COPY OF A SIGNED CONTRACT
 AND/OR COPIES OF INVOICES AND ESTIMATES SHOWING THE
 TOTAL COST OF THE INSTALLATION INCLUDING VALUE OF
 LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN FEES,
 AND OVERHEAD AND PROFIT- SECTION 109.3 WPB. IF THE COST
 OF THE GAS INSTALLATION WAS INCLUDED IN THE GENERATOR
 PERMIT, PLEASE PROVIDE COPIES OF THE PRIMARY AND
 SUB-CONTRACTS TO VERIFY.
  
 4) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 11:13 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 09:18 Sent To  
Notes
2020-09-24 11:14:001ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090781
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
  
 A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM
 THE METER TO THE 1-1/2" TEE, FROM THE 1-1/2" TEE TO THE
 1-1/4" TEE, AND FROM THE 1-1/4" TEE TO THE PIPE
 ENTRANCE INTO THE BUILDING. PLEASE CLARIFY IF THE
 1-1/4" TEE IS A REDUCER FITTING AND NOT A TEE BECAUSE A
 SECOND BRANCH LINE IS NOT SHOWN ON THE RISER- SECTIONS
 G2413.4.1 FBC RES.
 B) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS
 FOR THE INTERIOR APPLIANCES AND THE POOL HEATER-
 SECTION G2421.1 & G2421.2 FBC RES.
 C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. THE
 UPDATED SPECS FOR THE GENERAC 22KW MODEL INDICATE A
 FULL LOAD OF 306,000 BTUH FOR NATURAL GAS. PLEASE
 CORRECT THE LOAD SHOWN ON THE RISER.
 D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE
 OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING SHOWS A
 REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE TO THE
 GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE AND
 MODEL OF THE SELECTED REGULATOR ON THE RISER. SUBMIT
 MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING THE
 MODEL, INLET AND OUTLET PRESSURES, SPRING SELECTION,
 AND ORIFICE SIZE- SECTION G2421.1 & G2421.2. SHOW THE
 REQUIRED PIPE UNIONS AT THE REGULATOR.
 E) INDICATE HOW THE PE PIPING RISER WILL MAKE
 CONNECTION TO THE EXISTING PIPING AT THE BBQ- SECTIONS
 G2415.17.1 & G2415.17.2. PLEASE NOTE THAT SPECS FOR
 ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL
 BE LISTED AND LABELED.
 F) INDICATE A DRIP LEG WILL BE INSTALLED AND HOW THE
 LOCATION- SECTION G2419.2 FBC RES.
 G) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-10-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-09 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-10-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-30 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-21 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-10-13 Cont ID  
Sent By ccole Date 2020-10-13 Time 08:06 Rev Time 0.00
Received By ccole Date 2020-10-13 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By ccole Date 2020-10-05 Time 13:20 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 07:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 11:15 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 09:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By ccole Date 2020-10-13 Time 08:06 Rev Time 0.00
Received By ccole Date 2020-10-13 Time 07:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 11:15 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 09:18 Sent To  
Notes
***NONE***