Plan Review Details - Permit 20090731
Plan Review Stops For Permit 20090731
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By rmcdouga Date 2020-10-06 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2020-10-06 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By rmcdouga Date 2020-09-29 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2020-09-29 Time 10:32 Sent To  
Notes
2020-09-29 11:22:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE
 PLANS. FBC 107.2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-06 Cont ID  
Sent By rmcdouga Date 2020-10-06 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2020-09-30 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-29 Cont ID  
Sent By rmcdouga Date 2020-09-29 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2020-09-17 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-16 Cont ID  
Sent By jgomez Date 2020-11-16 Time 10:28 Rev Time 0.00
Received By jgomez Date 2020-11-16 Time 10:23 Sent To  
Notes
2020-11-16 10:29:54DESIGN PRESSURES CALCULATIONS CALCULATIONS SUBMITTED
 WITH EMBOSSED SEAL AND ENGINEER'S ORIGINAL SIGNATURE
 MATCHES APPROVED ONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-06 Cont ID  
Sent By rmcdouga Date 2020-10-06 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2020-10-06 Time 14:25 Sent To  
Notes
2020-10-06 14:25:36THE WIND LOAD CHART FROM THE ENGINEER IS NOT DIGITALLY
 SIGNED. ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED
 TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU
 ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED
 PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS
 HAVE BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING
 PAPER DRAWINGS AT THE BUILDING DEPARTMENT TO BE
 VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By rmcdouga Date 2020-09-29 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2020-09-29 Time 10:32 Sent To  
Notes
2020-09-29 11:20:43THE WIND LOAD CHART FROM THE ENGINEER IS NOT DIGITALLY
 SIGNED. ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED
 TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU
 ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED
 PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS
 HAVE BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING
 PAPER DRAWINGS AT THE BUILDING DEPARTMENT TO BE
 VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15