Plan Review Details - Permit 20090726
Plan Review Stops For Permit 20090726
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 13:35 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 12:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By cthroop Date 2020-10-08 Time 14:27 Rev Time 0.00
Received By cthroop Date 2020-10-08 Time 14:05 Sent To  
Notes
2020-10-08 14:45:01PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) VALUE
 CITY OF WPB CHPT. 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2) PROVIDE COMPLETE SET OF GENERATOR SPECIFICATIONS FOR
 THE PROPOSED GENERAC 21KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3) THE PROPOSED PRE-CAST GEN PAD REQUIRES STRUCTURAL
 DESIGN DETAILS PREPARED BY A DESIGN PROFESSIONAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4) PROVIDE WIND DESIGN WIND LOADS FOR THE GENERATOR PER
 FBC 107.3.5.3 AND R301.2
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 5) PROVIDE SITE SPECIFIC DESIGN WIND LOADS.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 A THOROUGH REVIEW CANNOT BE COMPLETED AT THIS TIEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By jleahy Date 2020-11-13 Time 11:59 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By jleahy Date 2020-10-06 Time 15:30 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 07:38 Sent To  
Notes
2020-10-06 10:05:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FEED OFF LOAD SIDE TRANSFER SWITCH IS NOT CLEAR ON
 WHAT IIT IS FEEDING?
  
 2) VALUE OF PERMIT IS LOW FOR THIS SIZE GENERATOR,
 PLEASE SUBMIT A SIGNED CONTRACT FOR THE WORK INVOLVED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) PLANS ARE NOT SIGNED, PLEASE SIGN PLANS (PRINT NSME,
 SIGN NAME, DATE)
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-27 Cont ID  
Sent By jleahy Date 2020-10-27 Time 10:07 Rev Time 0.00
Received By jleahy Date 2020-09-25 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-24 Cont ID  
Sent By lmarchan Date 2020-09-24 Time 11:13 Rev Time 0.00
Received By lmarchan Date 2020-09-23 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By lmarchan Date 2020-09-23 Time 13:22 Rev Time 0.00
Received By lmarchan Date 2020-09-22 Time 15:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-11-07 Cont ID  
Sent By medwards Date 2020-11-07 Time 08:39 Rev Time 0.00
Received By medwards Date 2020-11-07 Time 08:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 13:34 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 12:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By cthroop Date 2020-10-08 Time 14:24 Rev Time 0.00
Received By cthroop Date 2020-10-08 Time 14:06 Sent To  
Notes
2020-10-08 14:26:10A PRE-CAST GEN PAD IS PROPOSED. THIS REQUIRES A
 STRUCTURAL DESIGN BY A DESIGN PROFESSIONAL. 2ND
 SIGNATURE REVIEW REQUIRED. CT
2020-10-06 15:31:17ELECTRICAL PAGES ARE GOOD JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By kalexand Date 2020-11-24 Time 08:29 Rev Time 0.00
Received By kalexand Date 2020-11-24 Time 08:29 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-23 Cont ID  
Sent By kalexand Date 2020-10-23 Time 08:16 Rev Time 0.00
Received By kalexand Date 2020-10-23 Time 08:16 Sent To I
Notes
2020-10-26 08:18:33ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10/23/20
 ________________________________________
  
 REVIEW STATUS: PASSED
 ________________________________________
  