Plan Review Details - Permit 20090652
Plan Review Stops For Permit 20090652
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 16:39 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By cthroop Date 2020-10-27 Time 07:51 Rev Time 0.00
Received By cthroop Date 2020-10-27 Time 07:15 Sent To  
Notes
2020-10-27 08:08:27PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD ENGINEERING:
  
 1.GENERATOR PAD ENGINEERING IS BASED ON VULT OF 186MPH
 AND VASD OF 144MPH, RISK CATEGORY III AND EXPOSURE
 CATEGORY D.
  
 PROVIDE GENERATOR PAD DESIGN USING THE EXISTING SITE
 CONDITIONS:
  
 ASSUMED DESIGN CRITERIA FOR THIS SITE: VULT OF 170MPH,
 (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE R301.2.1.3)
 RISK CATEGORY II AND EXPOSURE CATEGORY C.
  
 2.PROPOSED PRE-CAST PAD DEMENSIONS ARE 33.75 X 49
 INCHES.
 GENERATOR DEMENSIONS FROM SPEIFICATIONS PROVIDED ARE
 29.6 X 48.1 INCHES.
 ANCHORS REQUIRE A MINIMUM OF 3 INCH EDGE DISTANCE.
 IT APPEARS THE PROPOSED PAD IS TOO SMALL.
  
 3.PROVIDE LOCATION OF GENERATOR ON SURVEY. PROVIDE
 DEMENSIONS TO PROPERTY LINES, TO STRUCTURE AND TO
 OPENINGS IN STRUCTURE.
  
 R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-24 Cont ID  
Sent By fgiaquin Date 2020-10-24 Time 11:22 Rev Time 0.00
Received By fgiaquin Date 2020-10-24 Time 11:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By ccole Date 2021-05-04 Time 08:22 Rev Time 0.00
Received By ccole Date 2021-05-04 Time 06:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-28 Cont ID  
Sent By ccole Date 2021-04-28 Time 07:56 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 12:25 Sent To  
Notes
2021-04-28 07:56:373RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090652
 4/28/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RISER SHOWS TWO GAS PIPING OUTLETS AT THE METER
 HOWEVER METERS TYPICALLY HAVE ONE INLET AND ONE OUTLET.
 PLEASE REVISE THE RISER TO SHOW THE TYPE AND SIZE OF
 THE MAIN OUTLET PIPE AND LENGTH OF THE PIPE FROM THE
 METER TOP THE TEE WHERE THE PE RISER IS CONNECTING.
 PLEASE NOTE THAT THE PIPE MUST BE SIZED LARGE ENOUGH TO
 SUPPLY THE INCREASED GAS LOAD OF 875,000 BTUS AT A
 TOTAL DEVELOPED LENGTH OF 110 FT- SECTION G2413.4.1 FBC
 RES.
  
 A) PLEASE SHOW THE DELIVERY PRESSURE AT THE METER AND
 PRESSURE DROP FOR THE SYSTEM- G2413.2 & G2413.5.
  
 B) LIST ALL PIPE SIZING TABLES ON THE RISER DRAWING-
 G2413.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-01-14 Cont ID  
Sent By ccole Date 2021-01-14 Time 15:59 Rev Time 0.00
Received By ccole Date 2021-01-14 Time 14:16 Sent To  
Notes
2021-01-14 16:00:462ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090652
 1/14/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: BASED ON THE SUBMITTED PE PIPE SIZING
 TABLE 402.4(21) FBC FG, THE 1-1/4 IN.PE PIPE IS
 UNDERSIZED TO SUPPLY THE NEW TOTAL LOAD OF 875,000 BTU
 LOAD AT 110 FT. DEVELOPED LENGTH AS INDICATED ON THE
 RISER. PLEASE NOTE THE 110 FT. LENGTH DOES NOT APPEAR
 TO MATCH THE MEASURMENTS ON THE RISER WHICH APPEAR TO
 INDICATE 80 FT. TOTAL LENGTH.THE 1-1/4 IS ALSO
 UNDERSIZED TO PROVIDE THE EXISTING LOAD OF 615 BTU
 BASED ON THE TABLE.
  
 2) GAS RISER: THE NEW 1 IN. PIPE IS LARGE ENOUGH TO
 SUPPLY THE 260,000 BTU GENERATOR LOAD IF THE NEW PIPE
 IS DIRECTLY CONNECTED TO THE METER AND NOT TEEING OFF
 FROM THE EXISTING 1-1/4 IN. PIPE. PLEASE PROVIDE A
 DETAIL SHOWING THE PIPING CONNECTIONS AT THE METER.
 COMMENTS 3 & 4 BELOW PERTAIN TO THE EXISTING PIPING
 WHICH APPEARS TO NOT BE SIZED PROPERLY.
  
 3) GAS RISER: PLEASE PROVIDE THE LENGTH OF THE PE PIPE
 RUN FROM THE METER TO THE CSST TEE- SECTION G2413.4.1
 FBC RES.
  
 4) GAS RISER: BASED ON THE SUBMITTED CSST PIPE SIZING
 TABLE 402.4(15) THE 1 IN. (31 EHD) IS UNDERSIZED TO
 SUPPLY THE INTERIOR 270,000 BTU LOAD AT 110 FT.
 DEVELOPED LENGTH. ACCORDING TO THE TABLE, AN EHD 46
 PIPE IS REQUIRED.
  
 5) THE SUBMITTED SURVEY IS APPEARS TO BE A PHOTO IMAGE
 WITH PRINT TOO SMALL TO READ AND PRINT WHEN ENLARGED
 FOR REVIEW BECOMES BLURRY AND ILLEGIBLE. PLEASE PROVIDE
 THE SURVEY IN A FORMAT THAT CAN BE REVIEWED FOR
 COMPLIANCE- SECTION 107.2.1 WPB. PLEASE MARK THE SURVEY
 TO SHOW GENERATOR'S LOCATION AND CLEARANCE DISTANCES TO
 THE BUILDING, ADJACENT PROPERTY LINES, AND AIR INTAKES
 AND OPERABLE OPENINGS INTO THE BUILDING- SEE SEC. 4.1.4
 NFPA 37, AND SEC. R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 11:41 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 09:20 Sent To  
Notes
2020-10-21 11:42:571ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090652
 10/21/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER
 DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES
 INSTALLED UNDER PERMIT 98003449 INCLUDING THE WATER
 HEATER, DRYER, AND COOKTOP- SECTIONS G2412.3 & G2412.4
 FBC RES.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES. PLEASE NOTE THE GENERATOR SPECS INDICATE A FULL
 LOAD CAPACITY OF 260,000 BTUH FOR NATURAL GAS.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR
 PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF
 THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE- SECTION G2421.
 D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTION
 G2421.2(7).
  
 2) PROVIDE A MARKED UP OR HIGHLIGHTED COPY OF THE
 PROPERTY SURVEY SHOWING THE GENERATOR'S LOCATION AND
 CLEARANCE DISTANCES TO THE BUILDING, ADJACENT PROPERTY
 LINES, AND AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SEE SEC. 4.1.4 NFPA 37, AND SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-05-04 Time   Rev Time 0.00
Received By aoliver Date 2021-05-03 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-28 Time   Rev Time 0.00
Received By aoliver Date 2021-04-19 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-08 Cont ID  
Sent By shill Date 2021-02-08 Time 16:31 Rev Time 0.00
Received By shill Date 2021-01-07 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-06 Cont ID  
Sent By lmarchan Date 2020-11-06 Time 09:23 Rev Time 0.00
Received By lmarchan Date 2020-10-09 Time 14:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-05-04 Cont ID  
Sent By ccole Date 2021-05-04 Time 08:23 Rev Time 0.00
Received By ccole Date 2021-05-04 Time 06:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-04-26 Cont ID  
Sent By ccole Date 2021-04-26 Time 12:25 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-01-14 Cont ID  
Sent By ccole Date 2021-01-14 Time 16:04 Rev Time 0.00
Received By ccole Date 2021-01-14 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 12:31 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 09:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 16:39 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 16:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By cthroop Date 2020-10-27 Time 07:50 Rev Time 0.00
Received By cthroop Date 2020-10-27 Time 07:15 Sent To  
Notes
2020-10-27 07:51:15PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-02-04 Cont ID  
Sent By kalexand Date 2021-02-04 Time 14:14 Rev Time 0.00
Received By kalexand Date 2021-02-04 Time 14:14 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By kalexand Date 2020-11-05 Time 17:03 Rev Time 0.00
Received By kalexand Date 2020-11-05 Time 17:03 Sent To I
Notes
2020-11-05 17:05:17ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  