 |
Plan Review Details - Permit 20090644
Plan Review Stops For Permit 20090644 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-05-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-07 |
Time |
15:04 |
Sent To |
|
|
Notes |
2021-05-07 15:15:27 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E) | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY | | CLASSIFICATION | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE TOILET REAR GRAB BAR CENTERLINE | | DIMENSIONS PER FBC ACCESSIBILITY FIGURE 604.5.2 TO | | AVOID INCORRECT INSTALLATION. | | 2) PLEASE SHOW THE GRAB BAR MAXIMUM HEIGHT TO THE TOP | | OF THE GRIPPING SURFACE NOT THE CENTER OF THE BAR PER | | FBC ACCESSIBILITY 609.4 | | 3) THERE IS A NOTE ON DRAWING A 3.0 FROM THE FIRE PLAN | | REVIEWER STATING THAT THE ADDED SLIDING GLASS DOORS | | NEED TO BE ABLE TO SWING OUT - THE PRODUCT APPROVAL FOR | | THE SLIDING GLASS DOOR DOES NOT SHOW THE OPTION TO | | SWING OUT. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-06 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-06 |
Time |
13:05 |
Sent To |
|
|
Notes |
2020-11-06 13:48:02 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E) | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY | | CLASSIFICATION | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) OCCUPANT LOAD SHOULD BE DETERMINED BY ROOM USE PER | | FBC 1004 - SHOW THE USE AND THE OCCUPANT LOAD FOR EACH | | ROOM. | | 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1 | | 3) PLEASE SHOW THAT DOORS THAT SWING INTO THE CORRIDOR | | COMPLY WITH - 1005.7.1 DOORS. | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | THAN ONE-HALF. | | 4) PLEASE SHOW THE GLAZING IN THE FIRE RATED CORRIDOR | | WALLS COMPLIES WITH FBC 716.2 | | 5) PLEASE SHOW THE FIRE RATING, SELF LATCHING AND SELF | | CLOSING OF THE CORRIDOR DOORS TO COMPLY WITH FBC 716 | | 6) EGRESS DOOR IN THE "MULTIPURPOSE ROOM" LEADING TO | | THE EGRESS CORRIDOR NEEDS TO COMPLY WITH FBC 1010.1.2.1 | | DIRECTION OF SWING. | | PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE | | DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA | | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS | | (ASSEMBLY AT 7SQ.FT. PER PERSON = 244 OCCUPANTS) - | | PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION ALSO. | | 7) PLEASE SHOW THE CORRIDOR WALL FIRE RATING TO COMPLY | | WITH FBC 466.8 (FBC 708.4 CONTINUITY. FIRE PARTITIONS | | SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR | | FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE | | FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE | | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING | | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED | | THERETO.) | | 8) PLEASE SHOW FIRE ALARMS TO COMPLY WITH - FBC 466.7 | | -- SHOW LOCATION OF SMOKE DETECTORS TO COMPLY WITH | | 466.7.2DETECTION. | | A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN | | ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN | | EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN | | THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE | | OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN | | LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY | | CARE OCCUPANCY. | | 9) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT | | AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT. | | 10) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON | | RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1 | | 11) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE | | SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED | | AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT | | WITHOUT THE CITY STAMP ON THEM. | | 12) SHOW NEW RESTROOM TO MEET ACCESSIBILITY | | REQUIREMENTS FBC ACCESSIBILITY 213.2 | | 13) SHOW ALL REQUIRED EXIT SIGNS TO COMPLY WITH FBC | | 1013.1 | | 14) SHOW EXIT EMERGENCY LIGHTING TO COMPLY WITH FBC | | 1008.3 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-09-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-18 |
Time |
12:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-18 |
Time |
10:04 |
Sent To |
|
|
Notes |
2020-09-18 11:31:51 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(I-4 ?) | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY | | CLASSIFICATION | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW ON THE DRAWING IF THIS IS AN OCCUPANCY | | CLASSIFICATION (I-4) - - FBC CHAPTER 3 - INSTITUTIONAL | | GROUP I-4 OCCUPANCY SHALL INCLUDE BUILDINGS AND | | STRUCTURES OCCUPIED BY MORE THAN FIVE PERSONS OF ANY | | AGE WHO RECEIVE CUSTODIAL CARE FOR FEWER THAN 24 HOURS | | PER DAY BY PERSONS OTHER THAN PARENTS OR GUARDIANS, | | RELATIVES BY BLOOD, MARRIAGE OR ADOPTION, AND IN A | | PLACE OTHER THAN THE HOME OF THE PERSON CARED FOR. THIS | | GROUP SHALL INCLUDE, BUT NOT BE LIMITED TO, THE | | FOLLOWING: ADULT DAY CARE - CHILD DAY CARE | | 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1 | | 3) PLEASE SHOW FIRE SPRINKLERS TO COMPLY WITH FBC | | 903.2.6 | | 4) PLEASE SHOW THE CORRIDOR FIRE RATING TO COMPLY WITH | | FBC 466.8 | | 5) PLEASE SHOW FIRE ALARMS TO COMPLY WITH FBC 907.2.6 | | 6) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT | | AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT. | | 7) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON | | RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1 | | 8) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE | | SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED | | AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT | | WITHOUT THE CITY STAMP ON THEM. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-05-21 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2021-05-21 |
Time |
11:57 |
Sent To |
|
|
Notes |
2021-05-21 13:36:18 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: FAILED. | | | | 1) SHEET E-1.0: RECEPTACLES ON NEW WALLS ARE SHOWN AS | | EXISTING. PLEASE CORRECT TO PROPERLY DESIGNATE NEW | | RECEPTACLES AND EXISTING ONES. | | 2) SHEET E-2.0: ALL LIGHTING FIXTURES ARE SHOWN AS | | EXISTING WITH NONE TO BE RELOCATED OR NEW. PLEASE | | CONFIRM THIS IS THE CASE. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ PE | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-06 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-06 |
Time |
10:44 |
Sent To |
|
|
Notes |
2020-11-06 10:49:13 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: FAILED. | | | | SAME COMMENTS AS PRIOR REVIEW. SEE BELOW: | | | | 1) NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE | | A GOOD REVIEW OF THE FACILITY. | | | | 2) OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER | | RESISTANT TYPE PER 406.12(C) | | | | 3) 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT | | RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN | | 406.12(A) THROUGH (C). | | 4) (C) CHILD CARE FACILITIES. IN ALL CHILD CARE | | FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND | | 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT | | RECEPTACLES. | | | | 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR | | STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL, | | SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN | | FOUR CHILDREN 7 YEARS OLD OR LESS. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-17 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-17 |
Time |
16:21 |
Sent To |
|
|
Notes |
2020-09-17 16:27:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE A | | GOOD REVIEW OF THE FACILITY. | | | | OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER | | RESISTANT TYPE PER 406.12(C) | | | | 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT | | RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN | | 406.12(A) TH ROUGH (C). | | (C) CHILD CARE FACILITIES. IN ALL CHILD CARE | | FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND | | 20-AMPERE RECEPTAC LES SHALL BE LISTED TAMPER-RESISTANT | | RECEPTACLES. | | | | 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR | | STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL, | | SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN | | FOUR CHILDREN 7 YEARS OLD OR LESS. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-21 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-17 |
Time |
15:29 |
Sent To |
|
|
Notes |
2020-10-21 09:37:38 | SEE COMMENT FROM FIRST REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2021-05-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-05-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-04-29 |
Time |
11:40 |
Sent To |
|
|
Notes |
2021-05-03 14:13:51 | FIRE PROVISO | | | | THERE ARE INDICATION OF SLIDING DOOR ASSEMBLIES IN TWO | | CLASSROOMS. | | | | THEY SHALL MEETING THE FOLLOWING EGRESS REQQUIRMENTS | | WHERE APPLICABLE. | | | | (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE | | PERMITTED UNDER ANY | | OF THE FOLLOWING CONDITIONS: | | (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND | | CORRECTIONAL | | OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 AND 23, SHALL | | BE PERMITTED. | | (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR | | FOLDING DOOR | | ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL BE PERMITTED. | | (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43, | | HORIZONTALSLIDING | | DOOR ASSEMBLIES SERVING A ROOM OR AREA WITH AN OCCUPANT | | LOAD OF FEWER THAN 10 SHALL BE PERMITTED, PROVIDED THAT | | ALL OF THE FOLLOWING CRITERIA ARE MET: | | I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH | | HAZARD | | CONTENTS. | | II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER | | SIDE | | WITHOUT SPECIAL KNOWLEDGE OR EFFORT. | | III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN | | THE | | DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 LBF | | (133 N) | | TO SET THE DOOR LEAF IN MOTION AND IS NOT MORE THAN 15 | | LBF | | (67 N) TO CLOSE THE DOOR ASSEMBLY OR OPEN IT TO THE | | MINIMUM | | REQUIRED WIDTH. | | IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE | | PROTECTION | | RATING, AND, WHERE RATED, IS SELF-CLOSING OR | | AUTOMATICCLOSING | | BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH | | 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80. | | V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE | | SELF-LATCHING HAVE | | A LATCH OR OTHER MECHANISM THAT ENSURES THAT THE DOOR | | LEAF | | WILL NOT REBOUND INTO A PARTIALLY OPEN POSITION IF | | FORCEFULLY | | CLOSED. | | (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL | | AREAS, AND | | STORAGE AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10 | | CONTAIN | | ONLY LOW OR ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO | | SUCH | | AREAS AND PRIVATE GARAGES SHALL BE PERMITTED TO BE | | HORIZONTALSLIDING | | DOOR ASSEMBLIES. | | | | PLEASE REVIEW AND ENSURE COMPLIANCE. | | | | THE FIRE INSPECTOR WILL CONFIRM COMPLIANCE ON | | INSPECTION. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-11-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-11-06 |
Time |
11:37 |
Sent To |
|
|
Notes |
2020-11-06 11:41:49 | PREVIOUS COMMENTS WERE NOT SPECIFICALLY ADDRESS AND ARE | | BEING RESUBMITTED: | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO | | CONDUCT A DETAILED LIFE SAFETY REVIEW. | | | | A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE | | REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE | | PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED. | | | | 16.1 GENERAL REQUIREMENTS. | | 16.1.1* APPLICATION. | | 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY | | TO NEW | | BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE | | OCCUPANCIES. (SEE | | 1.3.1.) | | | | 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5 | | AND | | SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN | | WHICH MORE | | THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND | | SUPERVISION BY | | OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR | | LESS THAN 24 | | HOURS PER DAY. | | | | 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE | | GROUP OR SELFPRESERVATION | | CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO | | ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE | | OCCUPANCY | | OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE | | AREA HOUSING | | SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA. | | | | PLEASE PROVIDE DETAILS | | | | | | | | | | 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM | | BUSINESS TO CHILDCARE | | | | THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE | | LESSON ROOMS AND A PRE-SCHOOLD ROOM. | | | | | | 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4. | | 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, | | KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS | | PRIMARILY | | EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER, | | EVEN THOUGH | | THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL | | AGE, SHALL | | COMPLY WITH THE PROVISIONS OF CHAPTER 14. | | | | | | PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF | | THE CARE, PROPOSED AGES, | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR | | FIRE ALARM SYSTEMS. | | | | PER NFPA 101 | | | | 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN | | DAY-CARE | | OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR | | OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN | | EXTERIOR | | EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE | | PROVIDED | | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION | | 9.6. | | | | 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN | | ACCORDANCE | | WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE | | OCCUPANCIES, OTHER | | THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR | | OPENING | | DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN | | EXTERIOR EXIT ACCESS | | BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL | | COMPLY | | WITH BOTH OF THE FOLLOWING: | | (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT | | OF THE DOORS | | TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS | | OCCUPIED BY | | THE DAY-CARE OCCUPANCY. | | (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION | | AREAS, AND | | SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY. | | | | 16.3.5 EXTINGUISHMENT REQUIREMENTS. | | 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN | | ACCORDANCE WITH | | SECTION 9.7. | | 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED | | IN ACCORDANCE | | WITH 9.7.1.1(1). | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS. | | | | 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE | | CONSTRUCTED OF | | WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE | | RATING IN | | ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED | | BY ANY OF | | THE FOLLOWING: | | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL | | SPACES | | NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN | | ONE | | DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR | | EXIT | | ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. | | (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | 9.7, | | CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, | | PROVIDED THAT | | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH | | SECTION | | 8.4. | | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A | | 1-HOUR FIRE | | RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR | | WALLS | | SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR | | CEILING. | | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED | | FROM CORRIDORS, | | PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES | | BY WALLS | | HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN | | ACCORDANCE WITH SECTION 8.3. | | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED | | FROM CORRIDORS, | | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: | | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN | | APPROVED, | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | WITH | | SECTION 9.7. | | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS | | FORM | | SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. | | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | OF THE ABOVE. | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | | | 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD | | CALCULATION. | | | | 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY | | DOOR IN A | | REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN | | OCCUPANT LOAD OF | | 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED | | WITH A LATCH | | OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR | | FIRE EXIT | | HARDWARE COMPLYING WITH 7.2.1.7. | | | | 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, | | STORAGE | | AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS | | SHALL BE SUCH | | THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR | | AREA. | | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK | | SHALL BE | | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE | | OUTSIDE | | BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE | | TO THE STAFF. | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | | | 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES. | | | | 16.2.11.1 WINDOWS FOR RESCUE. | | 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO | | CLIENT | | OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS | | THAN ONE | | OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH | | ALL OF THE | | FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2: | | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE | | WITHOUT THE | | USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT | | LESS THAN | | 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, | | AND 5.7 | | FT2 (0.5 M2) IN AREA. | | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 | | IN. (1120 | | MM) ABOVE THE FLOOR. | | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, | | WITH A WIDTH | | AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7 | | FT2 (0.5 | | M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510 | | MM), TO | | PASS FULLY THROUGH THE OPENING. | | 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT | | APPLY TO | | EITHER OF THE FOLLOWING: | | (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | 9.7 | | (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY | | TO AN EXIT | | OR DIRECTLY TO THE OUTSIDE OF THE BUILDING | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE | | REQUIRED EGRESS PATH. | | | | ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE | | STAFF RESTROOM. | | | | THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE | | LOBBY. | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | EXISTING BUILDING. | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | WIDTH OF THE STAIR LANDING WHEN THE DOOR | | LEAF IS FULLY OPEN. | | | | PLEASE REIVEW AND CORRECT | | | | | | | | 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE | | TOP. | | | | 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN | | ACCORDANCE WITH | | 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR | | 16.3.2.5. | | | | 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY | | ANOTHER | | SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS | | SHALL BE PROTECTED | | IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION | | CONTROL AND | | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, | | UNLESS SUCH | | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, | | WHICH SHALL BE | | PERMITTED TO BE CONTINUED IN SERVICE. | | | | 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED | | BETWEEN | | FOOD PREPARATION AREAS AND DINING AREAS. | | | | 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR | | FOOD | | WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE | | PROTECTED. | | | | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3 | | | | | | | | 9) THERE IS NO LIFE SAFETY PLAN | | | | 4.6.9 CONDITIONS FOR OCCUPANCY. | | 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL | | BE | | OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE | | PROVISIONS OF THIS | | CODE, UNLESS THE FOLLOWING CONDITIONS EXIST: | | (1) A PLAN OF CORRECTION HAS BEEN APPROVED. | | (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME. | | (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY | | THE | | AUTHORITY HAVING JURISDICTION. | | | | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN | | | | | | | | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-09-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-09-17 |
Time |
14:53 |
Sent To |
|
|
Notes |
2020-09-17 16:18:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO | | CONDUCT A DETAILED LIFE SAFETY REVIEW. | | | | A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE | | REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE | | PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED. | | | | 16.1 GENERAL REQUIREMENTS. | | 16.1.1* APPLICATION. | | 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY | | TO NEW | | BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE | | OCCUPANCIES. (SEE | | 1.3.1.) | | | | 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5 | | AND | | SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN | | WHICH MORE | | THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND | | SUPERVISION BY | | OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR | | LESS THAN 24 | | HOURS PER DAY. | | | | 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE | | GROUP OR SELFPRESERVATION | | CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO | | ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE | | OCCUPANCY | | OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE | | AREA HOUSING | | SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA. | | | | PLEASE PROVIDE DETAILS | | | | | | | | | | 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM | | BUSINESS TO CHILDCARE | | | | THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE | | LESSON ROOMS AND A PRE-SCHOOLD ROOM. | | | | | | 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4. | | 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, | | KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS | | PRIMARILY | | EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER, | | EVEN THOUGH | | THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL | | AGE, SHALL | | COMPLY WITH THE PROVISIONS OF CHAPTER 14. | | | | | | PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF | | THE CARE, PROPOSED AGES, | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR | | FIRE ALARM SYSTEMS. | | | | PER NFPA 101 | | | | 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN | | DAY-CARE | | OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR | | OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN | | EXTERIOR | | EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE | | PROVIDED | | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION | | 9.6. | | | | 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN | | ACCORDANCE | | WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE | | OCCUPANCIES, OTHER | | THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR | | OPENING | | DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN | | EXTERIOR EXIT ACCESS | | BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL | | COMPLY | | WITH BOTH OF THE FOLLOWING: | | (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT | | OF THE DOORS | | TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS | | OCCUPIED BY | | THE DAY-CARE OCCUPANCY. | | (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION | | AREAS, AND | | SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY. | | | | 16.3.5 EXTINGUISHMENT REQUIREMENTS. | | 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN | | ACCORDANCE WITH | | SECTION 9.7. | | 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED | | IN ACCORDANCE | | WITH 9.7.1.1(1). | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS. | | | | 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE | | CONSTRUCTED OF | | WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE | | RATING IN | | ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED | | BY ANY OF | | THE FOLLOWING: | | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL | | SPACES | | NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN | | ONE | | DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR | | EXIT | | ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. | | (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | 9.7, | | CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, | | PROVIDED THAT | | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH | | SECTION | | 8.4. | | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A | | 1-HOUR FIRE | | RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR | | WALLS | | SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR | | CEILING. | | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED | | FROM CORRIDORS, | | PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES | | BY WALLS | | HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN | | ACCORDANCE WITH SECTION 8.3. | | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED | | FROM CORRIDORS, | | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: | | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN | | APPROVED, | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | WITH | | SECTION 9.7. | | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS | | FORM | | SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. | | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | OF THE ABOVE. | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | | | 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD | | CALCULATION. | | | | 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY | | DOOR IN A | | REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN | | OCCUPANT LOAD OF | | 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED | | WITH A LATCH | | OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR | | FIRE EXIT | | HARDWARE COMPLYING WITH 7.2.1.7. | | | | 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, | | STORAGE | | AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS | | SHALL BE SUCH | | THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR | | AREA. | | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK | | SHALL BE | | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE | | OUTSIDE | | BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE | | TO THE STAFF. | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | | | 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES. | | | | 16.2.11.1 WINDOWS FOR RESCUE. | | 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO | | CLIENT | | OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS | | THAN ONE | | OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH | | ALL OF THE | | FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2: | | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE | | WITHOUT THE | | USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT | | LESS THAN | | 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, | | AND 5.7 | | FT2 (0.5 M2) IN AREA. | | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 | | IN. (1120 | | MM) ABOVE THE FLOOR. | | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, | | WITH A WIDTH | | AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7 | | FT2 (0.5 | | M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510 | | MM), TO | | PASS FULLY THROUGH THE OPENING. | | 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT | | APPLY TO | | EITHER OF THE FOLLOWING: | | (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | 9.7 | | (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY | | TO AN EXIT | | OR DIRECTLY TO THE OUTSIDE OF THE BUILDING | | | | PLEASE REIVEW AND PROVIDE DETAILS | | | | | | 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE | | REQUIRED EGRESS PATH. | | | | ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE | | STAFF RESTROOM. | | | | THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE | | LOBBY. | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | EXISTING BUILDING. | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | WIDTH OF THE STAIR LANDING WHEN THE DOOR | | LEAF IS FULLY OPEN. | | | | PLEASE REIVEW AND CORRECT | | | | | | | | 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE | | TOP. | | | | 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN | | ACCORDANCE WITH | | 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR | | 16.3.2.5. | | | | 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY | | ANOTHER | | SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS | | SHALL BE PROTECTED | | IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION | | CONTROL AND | | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, | | UNLESS SUCH | | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, | | WHICH SHALL BE | | PERMITTED TO BE CONTINUED IN SERVICE. | | | | 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED | | BETWEEN | | FOOD PREPARATION AREAS AND DINING AREAS. | | | | 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR | | FOOD | | WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE | | PROTECTED. | | | | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3 | | | | | | | | 9) THERE IS NO LIFE SAFETY PLAN | | | | 4.6.9 CONDITIONS FOR OCCUPANCY. | | 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL | | BE | | OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE | | PROVISIONS OF THIS | | CODE, UNLESS THE FOLLOWING CONDITIONS EXIST: | | (1) A PLAN OF CORRECTION HAS BEEN APPROVED. | | (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME. | | (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY | | THE | | AUTHORITY HAVING JURISDICTION. | | | | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN | | | | | | | | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2021-05-24 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2021-04-28 |
Time |
13:00 |
Sent To |
|
|
Notes |
2021-05-24 13:36:43 | ZONING WILL NEED TO RE-STAMP NEXT RE-SUBMITTAL. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-11-09 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-11-09 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-11-09 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-09-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-09-22 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-09-16 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-09-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-18 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-18 |
Time |
12:13 |
Sent To |
|
|
Notes |
2020-09-18 12:13:49 | CHANGE OF OCCUPANCY - | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2021-05-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-04 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-04 |
Time |
16:35 |
Sent To |
|
|
Notes |
2021-05-04 16:39:06 | THIS IS A CHANGE OF USE, PLEASE PROVIDE A COMPLETE | | MECHANICAL DRAWING SHOWING ALL DUCTWORK AND FIRE | | DAMPERS WHERE THE DUCTWORK PENETRATES THE RATED WALLS. | | FBC 107.2.1 AND FBC M 607 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-06 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-06 |
Time |
11:05 |
Sent To |
|
|
Notes |
2020-11-06 16:43:26 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT-20090644 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS A1 AND M.1 DO NOT MATCH, M.1 IS SHOWING ALL | | OFFICES BUT A1 IS SHOWING THE CORRECT PROPOSED USE OF | | SPACE AS E. THE MECHANICAL OUTDOOR AIR CALCULATIONS | | MUST BE CALCULATED ACCORDING TO USE OF EACH SPACE. FBC | | M TABLE 403.3.1.1. DESIGNER MUST PROVIDE AGE GROUPS OF | | EACH CLASS ROOM TO DETERMINE THE REQUIRED OUTDOOR AIR. | | | | 2) PLEASE SEE NOTE 3 OF THE ORIGINAL REVIEW BELOW: | | THE MECHANICAL PLAN DOES NOT SHOW ANY MECHANICAL SYSTEM | | FOR THE MULTIPURPOSE ROOM AREA. PLEASE SHOW HOW THIS | | SPACE WILL BE CONDITIONED. FBC 107.2.1 | | | | 3) PLEASE SEE NOTE 4 OF THE ORIGINAL REVIEW BELOW: | | PROVIDE AN UPDATED MECHANICAL DRAWING SHOWING THE | | PROPOSED USE OF SPACE. FBC 107.2 | | | | 4) PLEASE SEE NOTE 5 OF THE ORIGINAL REVIEW BELOW: | | PLEASE PROVIDE INFORMATION ON THE KITCHEN, WHAT IS | | GOING TO BE PREPARED IN THIS KITCHEN? IF COOKING IS | | BEING DONE THE A COMMERCIAL HOOD SHALL BE REQUIRED. A | | SEPARATE PERMIT AND REVIEW WILL BE REQUIRED FOR THE | | KITCHEN HOOD. FBC M 507.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-17 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-17 |
Time |
15:37 |
Sent To |
|
|
Notes |
2020-09-17 16:22:24 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20090644 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THERE WAS NOT ENOUGH INFORMATION SUBMITTED TO DO A | | COMPLETE REVIEW OF THIS PROJECT. | | | | 2) THIS IS A CHANGE OF USE FROM BUSINESS TO EDUCATION? | | PROVIDE VENTILATION CALCULATIONS OF EACH USE OF SPACE | | SHOWING AGE GROUPS FOR EACH CLASS ROOM FOR THIS CHILD | | CARE FACILITY. FBC M TABLE 403.3.1.1 | | | | 3) THE OLD PLAN DOES NOT SHOW ANY MECHANICAL SYSTEM FOR | | THE MULTIPURPOSE ROOM AREA PLEASE SHOW HOW THIS SPACE | | WILL BE CONDITIONED. FBC FS 107.2.1 | | | | 4) PROVIDE UPDATED MECHANICAL SHEET SHOWING THE | | PROPOSED USE OF SPACE. FBC FS 107.2.1 | | | | 5) PLEASE PROVIDE INFORMATION ON THE KITCHEN, WHAT IS | | GOING TO BE PREPARED IN THIS KITCHEN? IF COOKING IS | | BEING DONE THEN A COMMERCIAL HOOD SHALL BE REQUIRED. A | | SEPARATE PERMIT AND REVIEW WILL BE REQUIRED FOR THE | | KITCHEN HOOD. FBC M 507.2 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2021-05-06 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2021-05-04 |
Time |
15:07 |
Sent To |
|
|
Notes |
2021-05-06 16:09:06 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | MANUAL REVISED 2017 | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 20090644 2508 N AUSTRALIAN AVE | | | | | | 3RD REVIEW | | PLUMBING COMMENTS: DENIED | | | | | | 1.3RD REQUEST: PER WPB FBC 107.2.1, PROVIDE A FINANCIAL | | VALUATION OF THE PROJECT. SEE WPB FBC SECTION 109 FEES. | | RESPONSE IS THAT CONTRACTOR TO PROVIDE VALUATION. THAT | | VALUATION DOES NOT SEEM TO BE IN ANY OF THE SUBMITTED | | INFORMATION. PLEASE PROVIDE. | | | | 2.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL | | VENTS ON SANITARY RISER DIAGRAM. | | | | 3.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE | | PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND | | PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE | | THREAD CONNECTION? PROVIDE BACKFLOW PROTECTION AS | | REQUIRED IN FBC PL SECTION 608. | | | | 4.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF | | ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH | | CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC | | 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN. | | | | 5.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL | | ELEVATION MEASUREMENTS ON P-2 AND P-3. | | | | 6.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE | | TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC | | 609.4. | | | | 7.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE | | COMPARTMENT SINK AND HAND SINK AND FAUCET IN | | STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK | | SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE | | RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE | | FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY | | SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC | | 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC | | 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND | | SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO | | PROTECT AGAINST CONTACT. | | | | 8.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB FBC | | 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE SHALL | | CONFORM TO ASSE 1070." | | | | 9.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY | | OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON | | THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE | | E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY | | ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE | | DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS | | AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE | | VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER | | PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE | | SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED | | BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING | | ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB | | FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND. | | REVISIT AND SIZE THE HOT WATER DISTRIBUTION | | ACCORDINGLY. | | | | 10.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE | | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER | | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO | | COMPLY WITH FBC EC TABLE C403.2.10. | | | | 11.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER | | HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER | | SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS | | NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS. | | | | 12.IT IS NOTED THAT THE WATER HEATER IS EXISTING. | | PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO | | THE PIPING TO THE WATER HEATER IS MADE THEN THE | | REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET. | | PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING | | HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE | | CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING | | VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) , | | THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P | | DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN | | AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1; | | COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, | | 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. | | | | 13.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO | | COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP | | DISPENSER(S) STOCKED AT THE WATER COOLER. THE | | DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING | | FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER | | CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL | | DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD | | "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER" | | AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER | | 3. | | | | 14.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE | | FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC | | 107.2.1, CLARIFY. | | | | 15.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY | | REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER | | & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE | | COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER | | WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12 | | INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN | | TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED | | TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE | | M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH | | THROUGH 12 INCH." | | | | 16.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN | | THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE." | | | | 17.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR | | PLUMBING VALVES. | | | | 18.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND | | DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH | | FBC PL TABLE 308.5. | | | | 19.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE | | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER | | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO | | COMPLY WITH FBC EC TABLE C403.2.10. | | | | 20.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL | | VENTS ON SANITARY RISER DIAGRAM. | | | | 21.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE | | PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND | | PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE | | THREAD CONNECTION. PROVIDE BACKFLOW PROTECTION AS | | REQUIRED IN FBC PL SECTION 608. | | | | 22.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF | | ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH | | CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC | | 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN. | | | | 23.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL | | ELEVATION MEASUREMENTS ON P-2 AND P-3. | | | | 24.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE | | TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC | | 609.4. | | | | 25.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE | | COMPARTMENT SINK AND HAND SINK AND FAUCET IN | | STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK | | SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE | | RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE | | FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY | | SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC | | 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC | | 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND | | SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO | | PROTECT AGAINST CONTACT. | | | | 26.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB | | FBC 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE | | SHALL CONFORM TO ASSE 1070." | | | | 27.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY | | OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON | | THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE | | E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY | | ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE | | DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS | | AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE | | VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER | | PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE | | SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED | | BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING | | ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB | | FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND. | | REVISIT AND SIZE THE HOT WATER DISTRIBUTION | | ACCORDINGLY. | | | | 28.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE | | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER | | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO | | COMPLY WITH FBC EC TABLE C403.2.10. | | | | 29.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER | | HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER | | SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS | | NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS. | | | | 30.IT IS NOTED THAT THE WATER HEATER IS EXISTING. | | PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO | | THE PIPING TO THE WATER HEATER IS MADE THEN THE | | REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET. | | PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING | | HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE | | CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING | | VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) , | | THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P | | DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN | | AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1; | | COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, | | 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. | | | | 31.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO | | COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP | | DISPENSER(S) STOCKED AT THE WATER COOLER. THE | | DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING | | FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER | | CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL | | DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD | | "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER" | | AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER | | 3. | | | | 32.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE | | FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC | | 107.2.1, CLARIFY. | | | | 33.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY | | REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER | | & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE | | COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER | | WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12 | | INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN | | TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED | | TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE | | M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH | | THROUGH 12 INCH." | | | | 34.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN | | THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE." | | | | 35.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR | | PLUMBING VALVES. | | | | 36.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND | | DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH | | FBC PL TABLE 308.5. | | | | 37.PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION | | FOR BATHROOM FLOOR DRAINS COMPLYING WITH 1002.4.1.1, | | 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4. IF ONE OF THE | | FIRST THREE METHODS ARE SELECTED SHOW FEED INTO FLOOR | | DRAIN AND SOURCE ON THE PLAN; PROVIDE A MANUFACTURER | | SPECIFICATION AND AND DETAIL. IF THE FOURTH METHOD IS | | CHOSEN, PROVIDE A MANUFACTURER SPECIFICATION. | | | | | | | | | | END OF COMMENTS. | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED | | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-246-0882 MOBILE | | 20090644 2508 N AUSTRALIAN AVE |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2020-11-09 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-11-09 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-11-09 |
Time |
12:14 |
Sent To |
|
|
Notes |
2020-11-09 15:14:24 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | MANUAL REVISED 2017 | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 20090644 2508 N AUSTRALIAN AVE | | | | | | PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN | | PROVIDED. | | | | | | 2ND REVIEW | | PLUMBING COMMENTS: DENIED | | | | 1. SECOND REQUEST: PER WPB FBC 107.2.1, CLARIFY AS TO | | WHETHER OR NOT THERE WILL BE FOOD PREP AND FOOD SERVED | | IN THE FACILITY. A SEPARATE HAND SINK MAY BE REQUIRED | | BY THE BOARD OF HEALTH. A GREASY WASTE SYSTEM WITH | | INTERCEPTOR MAY ALSO BE REQUIRED. PLEASE NOTE THAT A | | RESPONSE LETTER HAS NOT BEEN PROVIDED. | | | | IDENTIFY ALL PLUMBING FIXTURES ON THE PLAN. CLARIFY | | WHICH IS NEW AND WHICH IS EXISTING. IF FOOD PREP IS | | CONDUCTED IN THE KITCHEN, A GREASE INTERCEPTOR IS | | REQUIRED PER FBC PL 1003.3.1 | | | | PERMIT 17011234 RECORD DRAWINGS DATED 1/18/2017 | | INDICATE THAT ROOMS IN THE KITCHEN AREA HAVE BEEN | | RECONFIGURED AND DO NOT REFLECT ANY PLUMBING FIXTURES. | | PLUMBING DRAWINGS AND INFORMATION ARE REQUIRED AS NOTED | | IN COMMENT 7. | | | | 2. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A | | FINANCIAL VALUATION OF THE PROJECT. SEE WPB FBC SECTION | | 109 FEES. PLEASE NOTE THAT A RESPONSE LETTER HAS NOT | | BEEN PROVIDED. | | | | 3. SECOND REQUEST: PER WPB FBC 107.1, PLANS SHALL BE | | DIGITALLY SIGNED BY A STATE REGISTERED DESIGN | | PROFESSIONAL IN ACCORDANCE WITH FS 471 AND FAC 61G15 OR | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. CONTRACTOR SHALL PRINT THEIR NAME, SIGN | | THEIR NAME AND PROVIDE LICENSE NUMBER FOR THE TRADE HE | | OR SHE IS LICENSED IN AND PLANS DRAWN. EACH TRADE SHALL | | PROVIDE PLANS FOR THEIR DESIGNATED WORK. SEE WPB FBC | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THAT | | A RESPONSE LETTER HAS NOT BEEN PROVIDED. | | | | 4. OK. OCCUPANCY TYPE AND CALCULATIONS FOR OCCUPANT | | LOAD PER WPB FBC 107.2.1 HAVE BEEN PROVIDED. | | | | 5. SCHEDULE PROVIDED. PER WPB FBC 107.2.1, PROVIDE | | FIXTURE SCHEDULE COMPLYING WITH FBC PL SECTION 403 FOR | | MINIMUM FIXTURE REQUIREMENTS. NOTE: WATER COOLERS DO | | NOT COMPLY WITH FBC ACC 212, FBC PL 410.3 AND FBC PL | | TABLE 401.3 EDUCATIONAL-E. SEE COMMENT 6. | | | | 6. DEPENDING UPON THE OCCUPANCY AND LOAD, A DRINKING | | FOUNTAIN MAY BE REQUIRED. WHERE A DRINKING FOUNTAIN IS | | REQUIRED, A MINIMUM OF TWO COMPLYING WITH FBC ACC 212 | | AND FBC PL 410.3 ARE REQUIRED. AN ADA COMPLIANT | | BI-LEVEL IS ACCEPTABLE IN LIEU OF TWO SEPARATE UNITS. | | PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN | | PROVIDED. NEW COMMENT: A DRINKING FOUNTAIN COMPLYING | | WITH FBC ACC 212 AND FBC PL 410.3. REGARDING ZOOM | | MEETING 10/1/2020 PLEASE SEE MY EMAIL SENT ON 10/1/2020 | | TO MS. RENATTA ESPINOZA AND ALL INDIVIDUALS INVITED TO | | SAID MEETING WITH COMMENTS REGARDING THE DRINKING | | FOUNTAIN. FULL TEXT OF COMMENTS ARE AT THE END OF THIS | | REVIEW. | | | | 7. SECOND REQUEST: PLEASE NOTE THAT A RESPONSE LETTER | | HAS NOT BEEN PROVIDED. PER WPB FBC 107.2.1 AND | | 107.3.5.1.3, PROVIDE THE FOLLOWING: | | A.PLUMBING FIXTURE SCHEDULE | | B.PLUMBING EQUIPMENT SCHEDULE (WATER HEATER, HOT WATER | | RECIRCULATING PUMP, DISHWASHER) | | C.SANITARY DRAINAGE, WASTE AND VENT RISER DIAGRAM SIZED | | AND FIXTURES IDENTIFIED | | E.WATER RISER DIAGRAM SIZED AND FIXTURES AND EQUIPMENT | | (WATER HEATER) IDENTIFIED. SHOW ALL VALVES AND BACKFLOW | | PREVENTER(S) | | F.PLUMBING WATER AND SANITARY FLOOR PLAN WITH FIXTURES | | IDENTIFIED. SHOW ALL TRAPS REQUIRED AT ROUGH IN STAGE. | | | | 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE UP TO | | DATE CERTIFICATION AND LOCATION OF EXISTING LEAD FREE | | BACKFLOW PREVENTER OR PROVIDE NEW WITH SPECIFICATION | | AND DETAIL FOR THE SAME. LOCATE EXISTING OR NEW ON THE | | PLANS. PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN | | PROVIDED. | | | | 9.SECOND REQUEST: PLEASE NOTE THAT A RESPONSE LETTER | | HAS NOT BEEN PROVIDED. PER WPB FBC 107.2.1, IDENTIFY | | ALL ACCESSIBLE PLUMBING FIXTURES ON THE FLOOR PLAN AND | | SHOW COMPLIANCE WITH FBC ACC CHAPTERS 3 AND 6 BY | | PROVIDING DETAILS INDICATING THE FOLLOWING: NOTE; | | PLEASE SEE FBC ACC 604.9 CHILDREN'S ACCESSIBILITY | | GUIDELINES FOR WATER CLOSETS AND TOILET ROOMS. | | | | NEW COMMENT: REGARDING FBC ACC 604.9. PER FBC ACC | | 604.1: WATER CLOSETS AND TOILET COMPARTMENTS SHALL | | COMPLY WITH 604.2 THROUGH 604.8. EXCEPTION: WATER | | CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE | | SHALL BE PERMITTED TO COMPLY WITH 604.9. AS SUCH 604.9 | | IS NOT A MANDATORY REQUIREMENT | | | | A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | ACC 604.2 | | B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | WALL PER FBC ACC 604.3.1 | | C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | WALL PER FBC ACC 604.5.1 | | D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | WATER CLOSET PER FBC ACC 604.6 | | F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC | | ACC 604.8. | | G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER | | FBC ACC 604.4. | | H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT | | THE CENTER) OF THE GRIPPING SURFACE | | I.ACCESSIBLE LAVATORIES AND SINKS (PER FBC ACC 212.3, | | THE KITCHEN SINK SHALL MEET THIS REQUIREMENT) SHALL BE | | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR | | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. PER FBC ACC 606.3, ADDITIONALLY SHOW | | TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND | | 306.3 | | J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 | | K.SHOW TURNING SPACE FOR WATER CLOSET COMPLYING WITH | | FBC ACC 304.3.1 OR 304.3.2. | | L.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES | | PER FBC ACC 304.4. | | M.SHOW CLEAR FLOOR SPACES FOR ACCESSIBLE LAVATORIES AND | | ACCESSIBLE SINKS (PER FBC ACC 212.3, THE KITCHEN SINK | | SHALL MEET THIS REQUIREMENT). THE CLEAR FLOOR OR GROUND | | SPACE SHALL BE 30 INCHES (760 MM) MINIMUM BY 48 INCHES | | (1220 MM) MINIMUM AND COMPLY WITH FBC ACC SECTION 305. | | N. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE | | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | ACC 603.3. | | O.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER | | FBC ACC 602.1. | | P.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. | | Q.EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 | | SHALL BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE | | THE SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE | | FINISH FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM) | | MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING | | BUMPERS. | | R.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC | | 602.3. | | S.SPOUT OUTLETS FOR WHEELCHAIR SHALL BE 36 INCHES (915 | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | ACC 602.4. | | T.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | GROUND PER FBC ACC 602.7 | | U.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM | | FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM | | FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER | | FBC ACC 602.5. | | | | NEW COMMENT: THE SPACE FOR THE WATER COOLER SHOWN IN | | THE HALL WAY BY THE JANITOR?S CLOSET AND GIRL?S TOILET | | ROOM VESTIBULE SHALL BE BUILT TO A DIMENSION TO PROVIDE | | FOR A DRINKING FOUNTAIN(S) WHICH COMPLIES WITH FBC ACC | | 302, 307, 602 AND FBC PL 410.3. | | | | NEW COMMENT: SEE EMAIL NOTES OF ZOOM MEETING. REGARDING | | THE DRINKING FOUNTAIN, I ADVISE YOU TO MAKE CLEAR ON | | THE PLANS THAT THE WATER AND DRAIN CONNECTIONS ARE IN | | PLACE FOR THE DRINKING FOUNTAIN AND CAPPED FOR FUTURE. | | PROVIDE A MANUFACTURER?S SPECIFICATION/INSTALLATION | | MANUAL FOR THE SAME. NOT PREVIOUSLY DISCUSSED IS THE | | FACT THAT THE UNIT HAS TO COMPLY WITH FLORIDA | | ACCESSIBILITY CODE. SHOW THE WATER COOLER AT THAT | | LOCATION AND NOTE THAT THE BOARD OF HEALTH REQUIRED YOU | | TO REMOVE THE DRINKING FOUNTAIN DUE TO THE COVID | | PANDEMIC. PROVIDE AS A SUPPORTING DOCUMENT, THE | | REQUIREMENT FROM THE BOARD OF HEALTH. ALSO PLEASE BRING | | THIS MATTER UP WITH DYLAN BATTLES. HOPEFULLY IT CAN BE | | SATISFACTORILY RESOLVED PRIOR TO THE NEXT REVIEW. THIS | | WAS NOT ADDRESSED ON THE PLANS, NOR HAVE I HAD ANY | | DIRECTION FROM MR. DYLAN BATTLES REGARDING THIS MATTER. | | | | NEW COMMENT: PLEASE NOTE THAT MOST OF THE ORIGINAL | | COMMENTS AS WELL AS THE EMAILED COMMENTS FOR THE ZOOM | | MEETING HAVE NOT BEEN RESPONDED TO. | | | | | | EMAILED COMMENTS REGARDING ZOOM MEETING OF 10/1/2020: | | HELLO RENATTA. BASED UPON THE ZOOM MEETING PLEASE SEE | | BELOW CONCERNING PLUMBING. | | *PROVIDE PLUMBING FIXTURE SCHEDULE FOR THE NEW ADA | | BATHROOM | | *PROVIDE EQUIPMENT SCHEDULE AND SPECIFICATION FOR ANY | | NEW PLUMBING EQUIPMENT SUCH AS TANKLESS WATER HEATERS | | AND/OR HOT WATER RECIRCULATION PUMP. | | *PROVIDE WATER RISER DIAGRAM FOR HOT AND COLD WATER. | | *DUE TO CHANGE OF OCCUPANCY, THE HOT WATER SYSTEM HAS | | TO BE BROUGHT UP TO CURRENT CODE. IF THE PIPING EXCEEDS | | 50 FEET FROM SOURCE THEN AN INSULATED (SPECIFY THE | | TYPE/THICKNESS INSULATION) RECIRCULATING SYSTEM OR HEAT | | TRACE SYSTEM IS REQUIRED, OR A MODIFICATION OF THE | | SYSTEM WHICH WOULD INCORPORATE POINT OF USE HEATERS; | | THE WATER RISER DIAGRAM NEEDS TO REFLECT WHATEVER | | OPTION IS TO BE USED. | | *REGARDING THE DRINKING FOUNTAIN, I ADVISE YOU TO MAKE | | CLEAR ON THE PLANS THAT THE WATER AND DRAIN CONNECTIONS | | ARE IN PLACE FOR THE DRINKING FOUNTAIN AND CAPPED FOR | | FUTURE. PROVIDE A MANUFACTURER?S | | SPECIFICATION/INSTALLATION MANUAL FOR THE SAME. NOT | | PREVIOUSLY DISCUSSED IS THE FACT THAT THE UNIT HAS TO | | COMPLY WITH FLORIDA ACCESSIBILITY CODE. SHOW THE WATER | | COOLER AT THAT LOCATION AND NOTE THAT THE BOARD OF | | HEALTH REQUIRED YOU TO REMOVE THE DRINKING FOUNTAIN DUE | | TO THE COVID PANDEMIC. PROVIDE AS A SUPPORTING | | DOCUMENT, THE REQUIREMENT FROM THE BOARD OF HEALTH. | | ALSO PLEASE BRING THIS MATTER UP WITH DYLAN BATTLES. | | HOPEFULLY IT CAN BE SATISFACTORILY RESOLVED PRIOR TO | | THE NEXT REVIEW. | | *PLEASE RESPOND TO MY COMMENT CONCERNING THE DISPUTED | | LOCATION OF THE EXISTING DRINKING FOUNTAIN IN THE | | MANNER THAT WAS DISCUSSED NOTING THAT THE EXISTING | | DRINKING FOUNTAIN IS IN FACT LOCATED AS NOTED ON THE | | SUBMITTED PLANS. | | *ALL BATHROOM WALLS REQUIRE HARD SURFACES SUCH AS TILE | | OR FRP PANELS 4 FEET UP FROM THE FLOOR PER FBC | | 1210.2.2. PLEASE PROVIDE NOTE SHOWING COMPLIANCE FOR | | ALL BATHROOMS AND SERVICE SINK. | | *STAFF LOUNGE SINK AND CABINET NEED TO COMPLY WITH THE | | FLORIDA ACCESSIBILITY CODE. NOT PREVIOUSLY DISCUSSED. | | BE SURE TO PROVIDE ALL CLEAR FLOOR SPACES. | | *IDENTIFY SERVICE SINK ON PLAN OR FURNISH ONE TO COMPLY | | WITH MINIMUM PLUMBING FIXTURE REQUIREMENTS. NOT | | PREVIOUSLY DISCUSSED. NOTED IT IS FURNISHED; PLEASE ID | | ON THE PLANS | | | | NEW NOTE APPLICABLE TO THE DRINKING FOUNTAIN. PER | | FLORIDA ACCESSIBILITY CODE 307.2, OBJECTS WITH LEADING | | EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES | | ABOVE THE FINISH FLOOR OR GROUND SHALL PROTRUDE 4 | | INCHES MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. | | THIS MEANS SIDE WALLS ARE REQUIRED ON EITHER SIDE OF | | THE DRINKING FOUNTAIN. | | | | | | END OF COMMENTS. | | | | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT | | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A | | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS | | FROM THE FIRST REVIEW. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED | | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-246-0882 MOBILE | | 20090644 2508 N AUSTRALIAN AVE | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2020-09-17 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2020-09-17 |
Time |
14:58 |
Sent To |
|
|
Notes |
2020-09-17 16:40:43 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | MANUAL REVISED 2017 | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 20090644 2508 N AUSTRALIAN AVE | | | | 1ST REVIEW | | PLUMBING COMMENTS: DENIED | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL | | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST | | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW | | APPROVAL. | | | | 1. PER WPB FBC 107.2.1, CLARIFY AS TO WHETHER OR NOT | | THERE WILL BE FOOD PREP AND FOOD SERVED IN THE | | FACILITY. A SEPARATE HAND SINK MAY BE REQUIRED BY THE | | BOARD OF HEALTH. A GREASY WASTE SYSTEM WITH INTERCEPTOR | | MAY ALSO BE REQUIRED. | | | | 2. PER WPB FBC 107.2.1, PROVIDE A FINANCIAL VALUATION | | OF THE PROJECT. SEE WPB FBC SECTION 109 FEES. | | | | 3. PER WPB FBC 107.1, PLANS SHALL BE DIGITALLY SIGNED | | BY A STATE REGISTERED DESIGN PROFESSIONAL IN ACCORDANCE | | WITH FS 471 AND FAC 61G15 OR THE CONTRACTOR (QUALIFIER) | | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO | | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. | | CONTRACTOR SHALL PRINT THEIR NAME, SIGN THEIR NAME AND | | PROVIDE LICENSE NUMBER FOR THE TRADE HE OR SHE IS | | LICENSED IN AND PLANS DRAWN. EACH TRADE SHALL PROVIDE | | PLANS FOR THEIR DESIGNATED WORK. SEE WPB FBC 107.3.4.3 | | CERTIFICATION BY CONTRACTOR. | | | | 4. PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND | | CALCULATIONS FOR OCCUPANT LOAD. SEE FBC 1004. | | | | 5. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE | | COMPLYING WITH FBC PL SECTION 403 FOR MINIMUM FIXTURE | | REQUIREMENTS. | | | | 6. DEPENDING UPON THE OCCUPANCY AND LOAD, A DRINKING | | FOUNTAIN MAY BE REQUIRED. WHERE A DRINKING FOUNTAIN IS | | REQUIRED, A MINIMUM OF TWO COMPLYING WITH FBC ACC 212 | | AND FBC PL 410.3 ARE REQUIRED. AN ADA COMPLIANT | | BI-LEVEL IS ACCEPTABLE IN LIEU OF TWO SEPARATE UNITS. | | | | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE | | FOLLOWING: | | A.PLUMBING FIXTURE SCHEDULE | | B.PLUMBING EQUIPMENT SCHEDULE (WATER HEATER, HOT WATER | | RECIRCULATING PUMP, DISHWASHER) | | C.SANITARY DRAINAGE, WASTE AND VENT RISER DIAGRAM SIZED | | AND FIXTURES IDENTIFIED | | E.WATER RISER DIAGRAM SIZED AND FIXTURES AND EQUIPMENT | | (WATER HEATER) IDENTIFIED. SHOW ALL VALVES AND BACKFLOW | | PREVENTER(S) | | F.PLUMBING WATER AND SANITARY FLOOR PLAN WITH FIXTURES | | IDENTIFIED. SHOW ALL TRAPS REQUIRED AT ROUGH IN STAGE. | | | | 8. PER WPB FBC 107.2.1, PROVIDE UP TO DATE | | CERTIFICATION AND LOCATION OF EXISTING LEAD FREE | | BACKFLOW PREVENTER OR PROVIDE NEW WITH SPECIFICATION | | AND DETAIL FOR THE SAME. LOCATE EXISTING OR NEW ON THE | | PLANS. | | | | 9.PER WPB FBC 107.2.1, IDENTIFY ALL ACCESSIBLE PLUMBING | | FIXTURES ON THE FLOOR PLAN AND SHOW COMPLIANCE WITH FBC | | ACC CHAPTERS 3 AND 6 BY PROVIDING DETAILS INDICATING | | THE FOLLOWING: NOTE; PLEASE SEE FBC ACC 604.9 | | CHILDREN'S ACCESSIBILITY GUIDELINES FOR WATER CLOSETS | | AND TOILET ROOMS. | | A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | ACC 604.2 | | B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | WALL PER FBC ACC 604.3.1 | | C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | WALL PER FBC ACC 604.5.1 | | D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | WATER CLOSET PER FBC ACC 604.6 | | F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC | | ACC 604.8. | | G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER | | FBC ACC 604.4. | | H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT | | THE CENTER) OF THE GRIPPING SURFACE | | I.ACCESSIBLE LAVATORIES AND SINKS (PER FBC ACC 212.3, | | THE KITCHEN SINK SHALL MEET THIS REQUIREMENT) SHALL BE | | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR | | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. PER FBC ACC 606.3, ADDITIONALLY SHOW | | TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND | | 306.3 | | JUNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 | | K.SHOW TURNING SPACE FOR WATER CLOSET COMPLYING WITH | | FBC ACC 304.3.1 OR 304.3.2. | | L.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES | | PER FBC ACC 304.4. | | M.SHOW CLEAR FLOOR SPACES FOR ACCESSIBLE LAVATORIES AND | | ACCESSIBLE SINKS (PER FBC ACC 212.3, THE KITCHEN SINK | | SHALL MEET THIS REQUIREMENT). THE CLEAR FLOOR OR GROUND | | SPACE SHALL BE 30 INCHES (760 MM) MINIMUM BY 48 INCHES | | (1220 MM) MINIMUM AND COMPLY WITH FBC ACC SECTION 305. | | N.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3. | | O.NOT USED | | P.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER | | FBC ACC 602.1. | | Q.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. | | R.EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 | | SHALL BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE | | THE SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE | | FINISH FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM) | | MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING | | BUMPERS. | | S.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC | | 602.3. | | T.SPOUT OUTLETS FOR WHEELCHAIR SHALL BE 36 INCHES (915 | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | ACC 602.4. | | U.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | GROUND PER FBC ACC 602.7 | | V.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM | | FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM | | FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER | | FBC ACC 602.5. | | | | END OF COMMENTS. | | | | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT | | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A | | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS | | FROM THE FIRST REVIEW. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | ALL PAPER PLANS TO BE SIGNED AND SEALED BY THE DESIGNER | | AS REQUIRED BY FAC AND FS. | | ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED | | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-246-0882 MOBILE | | | | 20090644 2508 N AUSTRALIAN AVE |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-07 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-06 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-06 |
Time |
15:06 |
Sent To |
|
|
Notes |
2020-11-06 15:07:34 | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | [email protected] AND ASKING FOR THE FORM. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-09-17 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-09-17 |
Time |
15:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-09-17 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2020-09-17 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2020-09-17 |
Time |
11:44 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |