Plan Review Details - Permit 20090644
Plan Review Stops For Permit 20090644
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-05-07 Cont ID  
Sent By rmcphers Date 2021-05-07 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 15:04 Sent To  
Notes
2021-05-07 15:15:27CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY
 CLASSIFICATION
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE TOILET REAR GRAB BAR CENTERLINE
 DIMENSIONS PER FBC ACCESSIBILITY FIGURE 604.5.2 TO
 AVOID INCORRECT INSTALLATION.
 2) PLEASE SHOW THE GRAB BAR MAXIMUM HEIGHT TO THE TOP
 OF THE GRIPPING SURFACE NOT THE CENTER OF THE BAR PER
 FBC ACCESSIBILITY 609.4
 3) THERE IS A NOTE ON DRAWING A 3.0 FROM THE FIRE PLAN
 REVIEWER STATING THAT THE ADDED SLIDING GLASS DOORS
 NEED TO BE ABLE TO SWING OUT - THE PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR DOES NOT SHOW THE OPTION TO
 SWING OUT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-06 Cont ID  
Sent By rmcphers Date 2020-11-06 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2020-11-06 Time 13:05 Sent To  
Notes
2020-11-06 13:48:02CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY
 CLASSIFICATION
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) OCCUPANT LOAD SHOULD BE DETERMINED BY ROOM USE PER
 FBC 1004 - SHOW THE USE AND THE OCCUPANT LOAD FOR EACH
 ROOM.
 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1
 3) PLEASE SHOW THAT DOORS THAT SWING INTO THE CORRIDOR
 COMPLY WITH - 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 4) PLEASE SHOW THE GLAZING IN THE FIRE RATED CORRIDOR
 WALLS COMPLIES WITH FBC 716.2
 5) PLEASE SHOW THE FIRE RATING, SELF LATCHING AND SELF
 CLOSING OF THE CORRIDOR DOORS TO COMPLY WITH FBC 716
 6) EGRESS DOOR IN THE "MULTIPURPOSE ROOM" LEADING TO
 THE EGRESS CORRIDOR NEEDS TO COMPLY WITH FBC 1010.1.2.1
 DIRECTION OF SWING.
 PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 (ASSEMBLY AT 7SQ.FT. PER PERSON = 244 OCCUPANTS) -
 PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION ALSO.
 7) PLEASE SHOW THE CORRIDOR WALL FIRE RATING TO COMPLY
 WITH FBC 466.8 (FBC 708.4 CONTINUITY. FIRE PARTITIONS
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED
 THERETO.)
 8) PLEASE SHOW FIRE ALARMS TO COMPLY WITH - FBC 466.7
 -- SHOW LOCATION OF SMOKE DETECTORS TO COMPLY WITH
 466.7.2DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
 9) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT
 AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT.
 10) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON
 RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1
 11) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE
 SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED
 AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT
 WITHOUT THE CITY STAMP ON THEM.
 12) SHOW NEW RESTROOM TO MEET ACCESSIBILITY
 REQUIREMENTS FBC ACCESSIBILITY 213.2
 13) SHOW ALL REQUIRED EXIT SIGNS TO COMPLY WITH FBC
 1013.1
 14) SHOW EXIT EMERGENCY LIGHTING TO COMPLY WITH FBC
 1008.3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-18 Cont ID  
Sent By rmcphers Date 2020-09-18 Time 12:17 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 10:04 Sent To  
Notes
2020-09-18 11:31:51CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(I-4 ?)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY
 CLASSIFICATION
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW ON THE DRAWING IF THIS IS AN OCCUPANCY
 CLASSIFICATION (I-4) - - FBC CHAPTER 3 - INSTITUTIONAL
 GROUP I-4 OCCUPANCY SHALL INCLUDE BUILDINGS AND
 STRUCTURES OCCUPIED BY MORE THAN FIVE PERSONS OF ANY
 AGE WHO RECEIVE CUSTODIAL CARE FOR FEWER THAN 24 HOURS
 PER DAY BY PERSONS OTHER THAN PARENTS OR GUARDIANS,
 RELATIVES BY BLOOD, MARRIAGE OR ADOPTION, AND IN A
 PLACE OTHER THAN THE HOME OF THE PERSON CARED FOR. THIS
 GROUP SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING: ADULT DAY CARE - CHILD DAY CARE
 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1
 3) PLEASE SHOW FIRE SPRINKLERS TO COMPLY WITH FBC
 903.2.6
 4) PLEASE SHOW THE CORRIDOR FIRE RATING TO COMPLY WITH
 FBC 466.8
 5) PLEASE SHOW FIRE ALARMS TO COMPLY WITH FBC 907.2.6
 6) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT
 AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT.
 7) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON
 RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1
 8) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE
 SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED
 AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT
 WITHOUT THE CITY STAMP ON THEM.
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-05-21 Cont ID  
Sent By equinone Date 2021-05-21 Time 13:30 Rev Time 0.00
Received By equinone Date 2021-05-21 Time 11:57 Sent To  
Notes
2021-05-21 13:36:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 1) SHEET E-1.0: RECEPTACLES ON NEW WALLS ARE SHOWN AS
 EXISTING. PLEASE CORRECT TO PROPERLY DESIGNATE NEW
 RECEPTACLES AND EXISTING ONES.
 2) SHEET E-2.0: ALL LIGHTING FIXTURES ARE SHOWN AS
 EXISTING WITH NONE TO BE RELOCATED OR NEW. PLEASE
 CONFIRM THIS IS THE CASE.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-11-06 Cont ID  
Sent By equinone Date 2020-11-06 Time 10:44 Rev Time 0.00
Received By equinone Date 2020-11-06 Time 10:44 Sent To  
Notes
2020-11-06 10:49:13CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 SAME COMMENTS AS PRIOR REVIEW. SEE BELOW:
  
 1) NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE
 A GOOD REVIEW OF THE FACILITY.
  
 2) OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER
 RESISTANT TYPE PER 406.12(C)
  
 3) 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT
 RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN
 406.12(A) THROUGH (C).
 4) (C) CHILD CARE FACILITIES. IN ALL CHILD CARE
 FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND
 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES.
  
 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR
 STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL,
 SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN
 FOUR CHILDREN 7 YEARS OLD OR LESS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-09-17 Cont ID  
Sent By jleahy Date 2020-09-17 Time 16:21 Rev Time 0.00
Received By jleahy Date 2020-09-17 Time 16:21 Sent To  
Notes
2020-09-17 16:27:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE A
 GOOD REVIEW OF THE FACILITY.
  
 OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER
 RESISTANT TYPE PER 406.12(C)
  
 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT
 RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN
 406.12(A) TH ROUGH (C).
 (C) CHILD CARE FACILITIES. IN ALL CHILD CARE
 FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND
 20-AMPERE RECEPTAC LES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES.
  
 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR
 STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL,
 SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN
 FOUR CHILDREN 7 YEARS OLD OR LESS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By jleahy Date 2020-10-21 Time 09:35 Rev Time 0.00
Received By jleahy Date 2020-09-17 Time 15:29 Sent To  
Notes
2020-10-21 09:37:38SEE COMMENT FROM FIRST REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-03 Cont ID  
Sent By pleduc Date 2021-05-03 Time   Rev Time 0.00
Received By pleduc Date 2021-04-29 Time 11:40 Sent To  
Notes
2021-05-03 14:13:51FIRE PROVISO
  
 THERE ARE INDICATION OF SLIDING DOOR ASSEMBLIES IN TWO
 CLASSROOMS.
  
 THEY SHALL MEETING THE FOLLOWING EGRESS REQQUIRMENTS
 WHERE APPLICABLE.
  
 (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE
 PERMITTED UNDER ANY
 OF THE FOLLOWING CONDITIONS:
 (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND
 CORRECTIONAL
 OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 AND 23, SHALL
 BE PERMITTED.
 (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR
 FOLDING DOOR
 ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL BE PERMITTED.
 (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 DOOR ASSEMBLIES SERVING A ROOM OR AREA WITH AN OCCUPANT
 LOAD OF FEWER THAN 10 SHALL BE PERMITTED, PROVIDED THAT
 ALL OF THE FOLLOWING CRITERIA ARE MET:
 I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH
 HAZARD
 CONTENTS.
 II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER
 SIDE
 WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN
 THE
 DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 LBF
 (133 N)
 TO SET THE DOOR LEAF IN MOTION AND IS NOT MORE THAN 15
 LBF
 (67 N) TO CLOSE THE DOOR ASSEMBLY OR OPEN IT TO THE
 MINIMUM
 REQUIRED WIDTH.
 IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE
 PROTECTION
 RATING, AND, WHERE RATED, IS SELF-CLOSING OR
 AUTOMATICCLOSING
 BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH
 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80.
 V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE
 SELF-LATCHING HAVE
 A LATCH OR OTHER MECHANISM THAT ENSURES THAT THE DOOR
 LEAF
 WILL NOT REBOUND INTO A PARTIALLY OPEN POSITION IF
 FORCEFULLY
 CLOSED.
 (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL
 AREAS, AND
 STORAGE AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10
 CONTAIN
 ONLY LOW OR ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO
 SUCH
 AREAS AND PRIVATE GARAGES SHALL BE PERMITTED TO BE
 HORIZONTALSLIDING
 DOOR ASSEMBLIES.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 THE FIRE INSPECTOR WILL CONFIRM COMPLIANCE ON
 INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-11-06 Cont ID  
Sent By pleduc Date 2020-11-06 Time   Rev Time 0.00
Received By pleduc Date 2020-11-06 Time 11:37 Sent To  
Notes
2020-11-06 11:41:49PREVIOUS COMMENTS WERE NOT SPECIFICALLY ADDRESS AND ARE
 BEING RESUBMITTED:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO
 CONDUCT A DETAILED LIFE SAFETY REVIEW.
  
 A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE
 PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED.
  
 16.1 GENERAL REQUIREMENTS.
 16.1.1* APPLICATION.
 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE
 OCCUPANCIES. (SEE
 1.3.1.)
  
 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5
 AND
 SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN
 WHICH MORE
 THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY
 OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR
 LESS THAN 24
 HOURS PER DAY.
  
 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE
 GROUP OR SELFPRESERVATION
 CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO
 ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE
 OCCUPANCY
 OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE
 AREA HOUSING
 SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA.
  
 PLEASE PROVIDE DETAILS
  
  
  
  
 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM
 BUSINESS TO CHILDCARE
  
 THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE
 LESSON ROOMS AND A PRE-SCHOOLD ROOM.
  
  
 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4.
 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS
 PRIMARILY
 EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER,
 EVEN THOUGH
 THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL
 AGE, SHALL
 COMPLY WITH THE PROVISIONS OF CHAPTER 14.
  
  
 PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF
 THE CARE, PROPOSED AGES,
  
  
  
  
 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR
 FIRE ALARM SYSTEMS.
  
 PER NFPA 101
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES, OTHER
 THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING
 DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR EXIT ACCESS
 BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL
 COMPLY
 WITH BOTH OF THE FOLLOWING:
 (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT
 OF THE DOORS
 TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS
 OCCUPIED BY
 THE DAY-CARE OCCUPANCY.
 (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION
 AREAS, AND
 SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY.
  
 16.3.5 EXTINGUISHMENT REQUIREMENTS.
 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN
 ACCORDANCE WITH
 SECTION 9.7.
 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH 9.7.1.1(1).
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS.
  
 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE
 CONSTRUCTED OF
 WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE
 RATING IN
 ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED
 BY ANY OF
 THE FOLLOWING:
 (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL
 SPACES
 NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN
 ONE
 DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR
 EXIT
 ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3.
 (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7,
 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION
 8.4.
 (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE
 RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR
 WALLS
 SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR
 CEILING.
 (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES
 BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3.
 (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7.
 (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS
 FORM
 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4.
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
  
 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD
 CALCULATION.
  
 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY
 DOOR IN A
 REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN
 OCCUPANT LOAD OF
 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED
 WITH A LATCH
 OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT
 HARDWARE COMPLYING WITH 7.2.1.7.
  
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE
 AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS
 SHALL BE SUCH
 THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR
 AREA.
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE
 BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE
 TO THE STAFF.
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
  
 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES.
  
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT
 OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS
 THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 ALL OF THE
 FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE
 USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN
 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT,
 AND 5.7
 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120
 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH
 AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7
 FT2 (0.5
 M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510
 MM), TO
 PASS FULLY THROUGH THE OPENING.
 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT
 APPLY TO
 EITHER OF THE FOLLOWING:
 (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7
 (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO AN EXIT
 OR DIRECTLY TO THE OUTSIDE OF THE BUILDING
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE
 REQUIRED EGRESS PATH.
  
 ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE
 STAFF RESTROOM.
  
 THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE
 LOBBY.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REIVEW AND CORRECT
  
  
  
 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE
 TOP.
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR
 16.3.2.5.
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN
 FOOD PREPARATION AREAS AND DINING AREAS.
  
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD
 WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE
 PROTECTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3
  
  
  
 9) THERE IS NO LIFE SAFETY PLAN
  
 4.6.9 CONDITIONS FOR OCCUPANCY.
 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL
 BE
 OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE
 PROVISIONS OF THIS
 CODE, UNLESS THE FOLLOWING CONDITIONS EXIST:
 (1) A PLAN OF CORRECTION HAS BEEN APPROVED.
 (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME.
 (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY
 THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By pleduc Date 2020-09-17 Time   Rev Time 0.00
Received By pleduc Date 2020-09-17 Time 14:53 Sent To  
Notes
2020-09-17 16:18:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO
 CONDUCT A DETAILED LIFE SAFETY REVIEW.
  
 A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE
 PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED.
  
 16.1 GENERAL REQUIREMENTS.
 16.1.1* APPLICATION.
 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE
 OCCUPANCIES. (SEE
 1.3.1.)
  
 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5
 AND
 SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN
 WHICH MORE
 THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY
 OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR
 LESS THAN 24
 HOURS PER DAY.
  
 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE
 GROUP OR SELFPRESERVATION
 CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO
 ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE
 OCCUPANCY
 OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE
 AREA HOUSING
 SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA.
  
 PLEASE PROVIDE DETAILS
  
  
  
  
 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM
 BUSINESS TO CHILDCARE
  
 THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE
 LESSON ROOMS AND A PRE-SCHOOLD ROOM.
  
  
 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4.
 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS
 PRIMARILY
 EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER,
 EVEN THOUGH
 THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL
 AGE, SHALL
 COMPLY WITH THE PROVISIONS OF CHAPTER 14.
  
  
 PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF
 THE CARE, PROPOSED AGES,
  
  
  
  
 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR
 FIRE ALARM SYSTEMS.
  
 PER NFPA 101
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE
 OCCUPANCIES, OTHER
 THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING
 DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR EXIT ACCESS
 BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL
 COMPLY
 WITH BOTH OF THE FOLLOWING:
 (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT
 OF THE DOORS
 TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS
 OCCUPIED BY
 THE DAY-CARE OCCUPANCY.
 (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION
 AREAS, AND
 SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY.
  
 16.3.5 EXTINGUISHMENT REQUIREMENTS.
 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN
 ACCORDANCE WITH
 SECTION 9.7.
 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH 9.7.1.1(1).
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS.
  
 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE
 CONSTRUCTED OF
 WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE
 RATING IN
 ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED
 BY ANY OF
 THE FOLLOWING:
 (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL
 SPACES
 NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN
 ONE
 DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR
 EXIT
 ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3.
 (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7,
 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION
 8.4.
 (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE
 RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR
 WALLS
 SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR
 CEILING.
 (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES
 BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3.
 (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7.
 (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS
 FORM
 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4.
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
  
 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD
 CALCULATION.
  
 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY
 DOOR IN A
 REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN
 OCCUPANT LOAD OF
 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED
 WITH A LATCH
 OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT
 HARDWARE COMPLYING WITH 7.2.1.7.
  
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE
 AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS
 SHALL BE SUCH
 THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR
 AREA.
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE
 BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE
 TO THE STAFF.
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
  
 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES.
  
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT
 OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS
 THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 ALL OF THE
 FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE
 USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN
 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT,
 AND 5.7
 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120
 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH
 AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7
 FT2 (0.5
 M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510
 MM), TO
 PASS FULLY THROUGH THE OPENING.
 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT
 APPLY TO
 EITHER OF THE FOLLOWING:
 (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7
 (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO AN EXIT
 OR DIRECTLY TO THE OUTSIDE OF THE BUILDING
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE
 REQUIRED EGRESS PATH.
  
 ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE
 STAFF RESTROOM.
  
 THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE
 LOBBY.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REIVEW AND CORRECT
  
  
  
 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE
 TOP.
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR
 16.3.2.5.
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN
 FOOD PREPARATION AREAS AND DINING AREAS.
  
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD
 WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE
 PROTECTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3
  
  
  
 9) THERE IS NO LIFE SAFETY PLAN
  
 4.6.9 CONDITIONS FOR OCCUPANCY.
 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL
 BE
 OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE
 PROVISIONS OF THIS
 CODE, UNLESS THE FOLLOWING CONDITIONS EXIST:
 (1) A PLAN OF CORRECTION HAS BEEN APPROVED.
 (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME.
 (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY
 THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-24 Cont ID  
Sent By dbattles Date 2021-05-24 Time 13:35 Rev Time 0.00
Received By dbattles Date 2021-04-28 Time 13:00 Sent To  
Notes
2021-05-24 13:36:43ZONING WILL NEED TO RE-STAMP NEXT RE-SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-09 Cont ID  
Sent By jesmith Date 2020-11-09 Time 15:31 Rev Time 0.00
Received By jesmith Date 2020-11-09 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-22 Cont ID  
Sent By lmarchan Date 2020-09-22 Time 13:25 Rev Time 0.00
Received By lmarchan Date 2020-09-16 Time 16:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-18 Cont ID  
Sent By rmcphers Date 2020-09-18 Time 12:13 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 12:13 Sent To  
Notes
2020-09-18 12:13:49CHANGE OF OCCUPANCY -
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 16:36 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 16:35 Sent To  
Notes
2021-05-04 16:39:06THIS IS A CHANGE OF USE, PLEASE PROVIDE A COMPLETE
 MECHANICAL DRAWING SHOWING ALL DUCTWORK AND FIRE
 DAMPERS WHERE THE DUCTWORK PENETRATES THE RATED WALLS.
 FBC 107.2.1 AND FBC M 607
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-11-06 Cont ID  
Sent By medwards Date 2020-11-06 Time 11:24 Rev Time 0.00
Received By medwards Date 2020-11-06 Time 11:05 Sent To  
Notes
2020-11-06 16:43:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20090644
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1 AND M.1 DO NOT MATCH, M.1 IS SHOWING ALL
 OFFICES BUT A1 IS SHOWING THE CORRECT PROPOSED USE OF
 SPACE AS E. THE MECHANICAL OUTDOOR AIR CALCULATIONS
 MUST BE CALCULATED ACCORDING TO USE OF EACH SPACE. FBC
 M TABLE 403.3.1.1. DESIGNER MUST PROVIDE AGE GROUPS OF
 EACH CLASS ROOM TO DETERMINE THE REQUIRED OUTDOOR AIR.
  
 2) PLEASE SEE NOTE 3 OF THE ORIGINAL REVIEW BELOW:
 THE MECHANICAL PLAN DOES NOT SHOW ANY MECHANICAL SYSTEM
 FOR THE MULTIPURPOSE ROOM AREA. PLEASE SHOW HOW THIS
 SPACE WILL BE CONDITIONED. FBC 107.2.1
  
 3) PLEASE SEE NOTE 4 OF THE ORIGINAL REVIEW BELOW:
 PROVIDE AN UPDATED MECHANICAL DRAWING SHOWING THE
 PROPOSED USE OF SPACE. FBC 107.2
  
 4) PLEASE SEE NOTE 5 OF THE ORIGINAL REVIEW BELOW:
 PLEASE PROVIDE INFORMATION ON THE KITCHEN, WHAT IS
 GOING TO BE PREPARED IN THIS KITCHEN? IF COOKING IS
 BEING DONE THE A COMMERCIAL HOOD SHALL BE REQUIRED. A
 SEPARATE PERMIT AND REVIEW WILL BE REQUIRED FOR THE
 KITCHEN HOOD. FBC M 507.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By medwards Date 2020-09-17 Time 16:21 Rev Time 0.00
Received By medwards Date 2020-09-17 Time 15:37 Sent To  
Notes
2020-09-17 16:22:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090644
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE WAS NOT ENOUGH INFORMATION SUBMITTED TO DO A
 COMPLETE REVIEW OF THIS PROJECT.
  
 2) THIS IS A CHANGE OF USE FROM BUSINESS TO EDUCATION?
 PROVIDE VENTILATION CALCULATIONS OF EACH USE OF SPACE
 SHOWING AGE GROUPS FOR EACH CLASS ROOM FOR THIS CHILD
 CARE FACILITY. FBC M TABLE 403.3.1.1
  
 3) THE OLD PLAN DOES NOT SHOW ANY MECHANICAL SYSTEM FOR
 THE MULTIPURPOSE ROOM AREA PLEASE SHOW HOW THIS SPACE
 WILL BE CONDITIONED. FBC FS 107.2.1
  
 4) PROVIDE UPDATED MECHANICAL SHEET SHOWING THE
 PROPOSED USE OF SPACE. FBC FS 107.2.1
  
 5) PLEASE PROVIDE INFORMATION ON THE KITCHEN, WHAT IS
 GOING TO BE PREPARED IN THIS KITCHEN? IF COOKING IS
 BEING DONE THEN A COMMERCIAL HOOD SHALL BE REQUIRED. A
 SEPARATE PERMIT AND REVIEW WILL BE REQUIRED FOR THE
 KITCHEN HOOD. FBC M 507.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-05-06 Cont ID  
Sent By jesmith Date 2021-05-06 Time 16:13 Rev Time 0.00
Received By jesmith Date 2021-05-04 Time 15:07 Sent To  
Notes
2021-05-06 16:09:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090644 2508 N AUSTRALIAN AVE
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 1.3RD REQUEST: PER WPB FBC 107.2.1, PROVIDE A FINANCIAL
 VALUATION OF THE PROJECT. SEE WPB FBC SECTION 109 FEES.
 RESPONSE IS THAT CONTRACTOR TO PROVIDE VALUATION. THAT
 VALUATION DOES NOT SEEM TO BE IN ANY OF THE SUBMITTED
 INFORMATION. PLEASE PROVIDE.
  
 2.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL
 VENTS ON SANITARY RISER DIAGRAM.
  
 3.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE
 PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND
 PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE
 THREAD CONNECTION? PROVIDE BACKFLOW PROTECTION AS
 REQUIRED IN FBC PL SECTION 608.
  
 4.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF
 ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH
 CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC
 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN.
  
 5.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL
 ELEVATION MEASUREMENTS ON P-2 AND P-3.
  
 6.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE
 TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC
 609.4.
  
 7.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE
 COMPARTMENT SINK AND HAND SINK AND FAUCET IN
 STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY
 SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC
 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC
 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND
 SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.
  
 8.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB FBC
 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE SHALL
 CONFORM TO ASSE 1070."
  
 9.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY
 OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON
 THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE
 E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY
 ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE
 DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS
 AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE
 VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER
 PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE
 SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED
 BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING
 ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB
 FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND.
 REVISIT AND SIZE THE HOT WATER DISTRIBUTION
 ACCORDINGLY.
  
 10.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE
 FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER
 HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO
 COMPLY WITH FBC EC TABLE C403.2.10.
  
 11.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER
 HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER
 SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS
 NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS.
  
 12.IT IS NOTED THAT THE WATER HEATER IS EXISTING.
 PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO
 THE PIPING TO THE WATER HEATER IS MADE THEN THE
 REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET.
 PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING
 HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE
 CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING
 VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) ,
 THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P
 DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN
 AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1;
 COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 13.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO
 COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP
 DISPENSER(S) STOCKED AT THE WATER COOLER. THE
 DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING
 FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER
 CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL
 DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD
 "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER"
 AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER
 3.
  
 14.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE
 FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC
 107.2.1, CLARIFY.
  
 15.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY
 REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER
 & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE
 COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER
 WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12
 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN
 TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED
 TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE
 M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH
 THROUGH 12 INCH."
  
 16.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN
 THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE."
  
 17.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 PLUMBING VALVES.
  
 18.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND
 DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH
 FBC PL TABLE 308.5.
  
 19.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE
 FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER
 HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO
 COMPLY WITH FBC EC TABLE C403.2.10.
  
 20.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL
 VENTS ON SANITARY RISER DIAGRAM.
  
 21.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE
 PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND
 PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE
 THREAD CONNECTION. PROVIDE BACKFLOW PROTECTION AS
 REQUIRED IN FBC PL SECTION 608.
  
 22.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF
 ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH
 CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC
 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN.
  
 23.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL
 ELEVATION MEASUREMENTS ON P-2 AND P-3.
  
 24.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE
 TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC
 609.4.
  
 25.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE
 COMPARTMENT SINK AND HAND SINK AND FAUCET IN
 STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY
 SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC
 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC
 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND
 SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.
  
 26.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB
 FBC 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE
 SHALL CONFORM TO ASSE 1070."
  
 27.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY
 OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON
 THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE
 E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY
 ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE
 DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS
 AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE
 VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER
 PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE
 SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED
 BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING
 ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB
 FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND.
 REVISIT AND SIZE THE HOT WATER DISTRIBUTION
 ACCORDINGLY.
  
 28.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE
 FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER
 HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO
 COMPLY WITH FBC EC TABLE C403.2.10.
  
 29.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER
 HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER
 SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS
 NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS.
  
 30.IT IS NOTED THAT THE WATER HEATER IS EXISTING.
 PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO
 THE PIPING TO THE WATER HEATER IS MADE THEN THE
 REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET.
 PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING
 HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE
 CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING
 VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) ,
 THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P
 DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN
 AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1;
 COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 31.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO
 COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP
 DISPENSER(S) STOCKED AT THE WATER COOLER. THE
 DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING
 FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER
 CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL
 DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD
 "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER"
 AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER
 3.
  
 32.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE
 FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC
 107.2.1, CLARIFY.
  
 33.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY
 REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER
 & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE
 COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER
 WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12
 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN
 TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED
 TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE
 M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH
 THROUGH 12 INCH."
  
 34.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN
 THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE."
  
 35.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 PLUMBING VALVES.
  
 36.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND
 DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH
 FBC PL TABLE 308.5.
  
 37.PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION
 FOR BATHROOM FLOOR DRAINS COMPLYING WITH 1002.4.1.1,
 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4. IF ONE OF THE
 FIRST THREE METHODS ARE SELECTED SHOW FEED INTO FLOOR
 DRAIN AND SOURCE ON THE PLAN; PROVIDE A MANUFACTURER
 SPECIFICATION AND AND DETAIL. IF THE FOURTH METHOD IS
 CHOSEN, PROVIDE A MANUFACTURER SPECIFICATION.
  
  
  
  
 END OF COMMENTS.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
 20090644 2508 N AUSTRALIAN AVE

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-11-09 Cont ID  
Sent By jesmith Date 2020-11-09 Time 15:30 Rev Time 0.00
Received By jesmith Date 2020-11-09 Time 12:14 Sent To  
Notes
2020-11-09 15:14:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090644 2508 N AUSTRALIAN AVE
  
  
 PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN
 PROVIDED.
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. SECOND REQUEST: PER WPB FBC 107.2.1, CLARIFY AS TO
 WHETHER OR NOT THERE WILL BE FOOD PREP AND FOOD SERVED
 IN THE FACILITY. A SEPARATE HAND SINK MAY BE REQUIRED
 BY THE BOARD OF HEALTH. A GREASY WASTE SYSTEM WITH
 INTERCEPTOR MAY ALSO BE REQUIRED. PLEASE NOTE THAT A
 RESPONSE LETTER HAS NOT BEEN PROVIDED.
  
 IDENTIFY ALL PLUMBING FIXTURES ON THE PLAN. CLARIFY
 WHICH IS NEW AND WHICH IS EXISTING. IF FOOD PREP IS
 CONDUCTED IN THE KITCHEN, A GREASE INTERCEPTOR IS
 REQUIRED PER FBC PL 1003.3.1
  
 PERMIT 17011234 RECORD DRAWINGS DATED 1/18/2017
 INDICATE THAT ROOMS IN THE KITCHEN AREA HAVE BEEN
 RECONFIGURED AND DO NOT REFLECT ANY PLUMBING FIXTURES.
 PLUMBING DRAWINGS AND INFORMATION ARE REQUIRED AS NOTED
 IN COMMENT 7.
  
 2. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A
 FINANCIAL VALUATION OF THE PROJECT. SEE WPB FBC SECTION
 109 FEES. PLEASE NOTE THAT A RESPONSE LETTER HAS NOT
 BEEN PROVIDED.
  
 3. SECOND REQUEST: PER WPB FBC 107.1, PLANS SHALL BE
 DIGITALLY SIGNED BY A STATE REGISTERED DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FS 471 AND FAC 61G15 OR
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. CONTRACTOR SHALL PRINT THEIR NAME, SIGN
 THEIR NAME AND PROVIDE LICENSE NUMBER FOR THE TRADE HE
 OR SHE IS LICENSED IN AND PLANS DRAWN. EACH TRADE SHALL
 PROVIDE PLANS FOR THEIR DESIGNATED WORK. SEE WPB FBC
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THAT
 A RESPONSE LETTER HAS NOT BEEN PROVIDED.
  
 4. OK. OCCUPANCY TYPE AND CALCULATIONS FOR OCCUPANT
 LOAD PER WPB FBC 107.2.1 HAVE BEEN PROVIDED.
  
 5. SCHEDULE PROVIDED. PER WPB FBC 107.2.1, PROVIDE
 FIXTURE SCHEDULE COMPLYING WITH FBC PL SECTION 403 FOR
 MINIMUM FIXTURE REQUIREMENTS. NOTE: WATER COOLERS DO
 NOT COMPLY WITH FBC ACC 212, FBC PL 410.3 AND FBC PL
 TABLE 401.3 EDUCATIONAL-E. SEE COMMENT 6.
  
 6. DEPENDING UPON THE OCCUPANCY AND LOAD, A DRINKING
 FOUNTAIN MAY BE REQUIRED. WHERE A DRINKING FOUNTAIN IS
 REQUIRED, A MINIMUM OF TWO COMPLYING WITH FBC ACC 212
 AND FBC PL 410.3 ARE REQUIRED. AN ADA COMPLIANT
 BI-LEVEL IS ACCEPTABLE IN LIEU OF TWO SEPARATE UNITS.
 PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN
 PROVIDED. NEW COMMENT: A DRINKING FOUNTAIN COMPLYING
 WITH FBC ACC 212 AND FBC PL 410.3. REGARDING ZOOM
 MEETING 10/1/2020 PLEASE SEE MY EMAIL SENT ON 10/1/2020
 TO MS. RENATTA ESPINOZA AND ALL INDIVIDUALS INVITED TO
 SAID MEETING WITH COMMENTS REGARDING THE DRINKING
 FOUNTAIN. FULL TEXT OF COMMENTS ARE AT THE END OF THIS
 REVIEW.
  
 7. SECOND REQUEST: PLEASE NOTE THAT A RESPONSE LETTER
 HAS NOT BEEN PROVIDED. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE THE FOLLOWING:
 A.PLUMBING FIXTURE SCHEDULE
 B.PLUMBING EQUIPMENT SCHEDULE (WATER HEATER, HOT WATER
 RECIRCULATING PUMP, DISHWASHER)
 C.SANITARY DRAINAGE, WASTE AND VENT RISER DIAGRAM SIZED
 AND FIXTURES IDENTIFIED
 E.WATER RISER DIAGRAM SIZED AND FIXTURES AND EQUIPMENT
 (WATER HEATER) IDENTIFIED. SHOW ALL VALVES AND BACKFLOW
 PREVENTER(S)
 F.PLUMBING WATER AND SANITARY FLOOR PLAN WITH FIXTURES
 IDENTIFIED. SHOW ALL TRAPS REQUIRED AT ROUGH IN STAGE.
  
 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE UP TO
 DATE CERTIFICATION AND LOCATION OF EXISTING LEAD FREE
 BACKFLOW PREVENTER OR PROVIDE NEW WITH SPECIFICATION
 AND DETAIL FOR THE SAME. LOCATE EXISTING OR NEW ON THE
 PLANS. PLEASE NOTE THAT A RESPONSE LETTER HAS NOT BEEN
 PROVIDED.
  
 9.SECOND REQUEST: PLEASE NOTE THAT A RESPONSE LETTER
 HAS NOT BEEN PROVIDED. PER WPB FBC 107.2.1, IDENTIFY
 ALL ACCESSIBLE PLUMBING FIXTURES ON THE FLOOR PLAN AND
 SHOW COMPLIANCE WITH FBC ACC CHAPTERS 3 AND 6 BY
 PROVIDING DETAILS INDICATING THE FOLLOWING: NOTE;
 PLEASE SEE FBC ACC 604.9 CHILDREN'S ACCESSIBILITY
 GUIDELINES FOR WATER CLOSETS AND TOILET ROOMS.
  
 NEW COMMENT: REGARDING FBC ACC 604.9. PER FBC ACC
 604.1: WATER CLOSETS AND TOILET COMPARTMENTS SHALL
 COMPLY WITH 604.2 THROUGH 604.8. EXCEPTION: WATER
 CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE
 SHALL BE PERMITTED TO COMPLY WITH 604.9. AS SUCH 604.9
 IS NOT A MANDATORY REQUIREMENT
  
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
 I.ACCESSIBLE LAVATORIES AND SINKS (PER FBC ACC 212.3,
 THE KITCHEN SINK SHALL MEET THIS REQUIREMENT) SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 606.3, ADDITIONALLY SHOW
 TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND
 306.3
 J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.SHOW TURNING SPACE FOR WATER CLOSET COMPLYING WITH
 FBC ACC 304.3.1 OR 304.3.2.
 L.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES
 PER FBC ACC 304.4.
 M.SHOW CLEAR FLOOR SPACES FOR ACCESSIBLE LAVATORIES AND
 ACCESSIBLE SINKS (PER FBC ACC 212.3, THE KITCHEN SINK
 SHALL MEET THIS REQUIREMENT). THE CLEAR FLOOR OR GROUND
 SPACE SHALL BE 30 INCHES (760 MM) MINIMUM BY 48 INCHES
 (1220 MM) MINIMUM AND COMPLY WITH FBC ACC SECTION 305.
 N. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 O.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER
 FBC ACC 602.1.
 P.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 Q.EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE
 THE SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM)
 MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING
 BUMPERS.
 R.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC
 602.3.
 S.SPOUT OUTLETS FOR WHEELCHAIR SHALL BE 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 602.4.
 T.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7
 U.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER
 FBC ACC 602.5.
  
 NEW COMMENT: THE SPACE FOR THE WATER COOLER SHOWN IN
 THE HALL WAY BY THE JANITOR?S CLOSET AND GIRL?S TOILET
 ROOM VESTIBULE SHALL BE BUILT TO A DIMENSION TO PROVIDE
 FOR A DRINKING FOUNTAIN(S) WHICH COMPLIES WITH FBC ACC
 302, 307, 602 AND FBC PL 410.3.
  
 NEW COMMENT: SEE EMAIL NOTES OF ZOOM MEETING. REGARDING
 THE DRINKING FOUNTAIN, I ADVISE YOU TO MAKE CLEAR ON
 THE PLANS THAT THE WATER AND DRAIN CONNECTIONS ARE IN
 PLACE FOR THE DRINKING FOUNTAIN AND CAPPED FOR FUTURE.
 PROVIDE A MANUFACTURER?S SPECIFICATION/INSTALLATION
 MANUAL FOR THE SAME. NOT PREVIOUSLY DISCUSSED IS THE
 FACT THAT THE UNIT HAS TO COMPLY WITH FLORIDA
 ACCESSIBILITY CODE. SHOW THE WATER COOLER AT THAT
 LOCATION AND NOTE THAT THE BOARD OF HEALTH REQUIRED YOU
 TO REMOVE THE DRINKING FOUNTAIN DUE TO THE COVID
 PANDEMIC. PROVIDE AS A SUPPORTING DOCUMENT, THE
 REQUIREMENT FROM THE BOARD OF HEALTH. ALSO PLEASE BRING
 THIS MATTER UP WITH DYLAN BATTLES. HOPEFULLY IT CAN BE
 SATISFACTORILY RESOLVED PRIOR TO THE NEXT REVIEW. THIS
 WAS NOT ADDRESSED ON THE PLANS, NOR HAVE I HAD ANY
 DIRECTION FROM MR. DYLAN BATTLES REGARDING THIS MATTER.
  
 NEW COMMENT: PLEASE NOTE THAT MOST OF THE ORIGINAL
 COMMENTS AS WELL AS THE EMAILED COMMENTS FOR THE ZOOM
 MEETING HAVE NOT BEEN RESPONDED TO.
  
  
 EMAILED COMMENTS REGARDING ZOOM MEETING OF 10/1/2020:
 HELLO RENATTA. BASED UPON THE ZOOM MEETING PLEASE SEE
 BELOW CONCERNING PLUMBING.
 *PROVIDE PLUMBING FIXTURE SCHEDULE FOR THE NEW ADA
 BATHROOM
 *PROVIDE EQUIPMENT SCHEDULE AND SPECIFICATION FOR ANY
 NEW PLUMBING EQUIPMENT SUCH AS TANKLESS WATER HEATERS
 AND/OR HOT WATER RECIRCULATION PUMP.
 *PROVIDE WATER RISER DIAGRAM FOR HOT AND COLD WATER.
 *DUE TO CHANGE OF OCCUPANCY, THE HOT WATER SYSTEM HAS
 TO BE BROUGHT UP TO CURRENT CODE. IF THE PIPING EXCEEDS
 50 FEET FROM SOURCE THEN AN INSULATED (SPECIFY THE
 TYPE/THICKNESS INSULATION) RECIRCULATING SYSTEM OR HEAT
 TRACE SYSTEM IS REQUIRED, OR A MODIFICATION OF THE
 SYSTEM WHICH WOULD INCORPORATE POINT OF USE HEATERS;
 THE WATER RISER DIAGRAM NEEDS TO REFLECT WHATEVER
 OPTION IS TO BE USED.
 *REGARDING THE DRINKING FOUNTAIN, I ADVISE YOU TO MAKE
 CLEAR ON THE PLANS THAT THE WATER AND DRAIN CONNECTIONS
 ARE IN PLACE FOR THE DRINKING FOUNTAIN AND CAPPED FOR
 FUTURE. PROVIDE A MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SAME. NOT
 PREVIOUSLY DISCUSSED IS THE FACT THAT THE UNIT HAS TO
 COMPLY WITH FLORIDA ACCESSIBILITY CODE. SHOW THE WATER
 COOLER AT THAT LOCATION AND NOTE THAT THE BOARD OF
 HEALTH REQUIRED YOU TO REMOVE THE DRINKING FOUNTAIN DUE
 TO THE COVID PANDEMIC. PROVIDE AS A SUPPORTING
 DOCUMENT, THE REQUIREMENT FROM THE BOARD OF HEALTH.
 ALSO PLEASE BRING THIS MATTER UP WITH DYLAN BATTLES.
 HOPEFULLY IT CAN BE SATISFACTORILY RESOLVED PRIOR TO
 THE NEXT REVIEW.
 *PLEASE RESPOND TO MY COMMENT CONCERNING THE DISPUTED
 LOCATION OF THE EXISTING DRINKING FOUNTAIN IN THE
 MANNER THAT WAS DISCUSSED NOTING THAT THE EXISTING
 DRINKING FOUNTAIN IS IN FACT LOCATED AS NOTED ON THE
 SUBMITTED PLANS.
 *ALL BATHROOM WALLS REQUIRE HARD SURFACES SUCH AS TILE
 OR FRP PANELS 4 FEET UP FROM THE FLOOR PER FBC
 1210.2.2. PLEASE PROVIDE NOTE SHOWING COMPLIANCE FOR
 ALL BATHROOMS AND SERVICE SINK.
 *STAFF LOUNGE SINK AND CABINET NEED TO COMPLY WITH THE
 FLORIDA ACCESSIBILITY CODE. NOT PREVIOUSLY DISCUSSED.
 BE SURE TO PROVIDE ALL CLEAR FLOOR SPACES.
 *IDENTIFY SERVICE SINK ON PLAN OR FURNISH ONE TO COMPLY
 WITH MINIMUM PLUMBING FIXTURE REQUIREMENTS. NOT
 PREVIOUSLY DISCUSSED. NOTED IT IS FURNISHED; PLEASE ID
 ON THE PLANS
  
 NEW NOTE APPLICABLE TO THE DRINKING FOUNTAIN. PER
 FLORIDA ACCESSIBILITY CODE 307.2, OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FINISH FLOOR OR GROUND SHALL PROTRUDE 4
 INCHES MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
 THIS MEANS SIDE WALLS ARE REQUIRED ON EITHER SIDE OF
 THE DRINKING FOUNTAIN.
  
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
 20090644 2508 N AUSTRALIAN AVE
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By jesmith Date 2020-09-17 Time 16:40 Rev Time 0.00
Received By jesmith Date 2020-09-17 Time 14:58 Sent To  
Notes
2020-09-17 16:40:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090644 2508 N AUSTRALIAN AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, CLARIFY AS TO WHETHER OR NOT
 THERE WILL BE FOOD PREP AND FOOD SERVED IN THE
 FACILITY. A SEPARATE HAND SINK MAY BE REQUIRED BY THE
 BOARD OF HEALTH. A GREASY WASTE SYSTEM WITH INTERCEPTOR
 MAY ALSO BE REQUIRED.
  
 2. PER WPB FBC 107.2.1, PROVIDE A FINANCIAL VALUATION
 OF THE PROJECT. SEE WPB FBC SECTION 109 FEES.
  
 3. PER WPB FBC 107.1, PLANS SHALL BE DIGITALLY SIGNED
 BY A STATE REGISTERED DESIGN PROFESSIONAL IN ACCORDANCE
 WITH FS 471 AND FAC 61G15 OR THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 CONTRACTOR SHALL PRINT THEIR NAME, SIGN THEIR NAME AND
 PROVIDE LICENSE NUMBER FOR THE TRADE HE OR SHE IS
 LICENSED IN AND PLANS DRAWN. EACH TRADE SHALL PROVIDE
 PLANS FOR THEIR DESIGNATED WORK. SEE WPB FBC 107.3.4.3
 CERTIFICATION BY CONTRACTOR.
  
 4. PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND
 CALCULATIONS FOR OCCUPANT LOAD. SEE FBC 1004.
  
 5. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE
 COMPLYING WITH FBC PL SECTION 403 FOR MINIMUM FIXTURE
 REQUIREMENTS.
  
 6. DEPENDING UPON THE OCCUPANCY AND LOAD, A DRINKING
 FOUNTAIN MAY BE REQUIRED. WHERE A DRINKING FOUNTAIN IS
 REQUIRED, A MINIMUM OF TWO COMPLYING WITH FBC ACC 212
 AND FBC PL 410.3 ARE REQUIRED. AN ADA COMPLIANT
 BI-LEVEL IS ACCEPTABLE IN LIEU OF TWO SEPARATE UNITS.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE
 FOLLOWING:
 A.PLUMBING FIXTURE SCHEDULE
 B.PLUMBING EQUIPMENT SCHEDULE (WATER HEATER, HOT WATER
 RECIRCULATING PUMP, DISHWASHER)
 C.SANITARY DRAINAGE, WASTE AND VENT RISER DIAGRAM SIZED
 AND FIXTURES IDENTIFIED
 E.WATER RISER DIAGRAM SIZED AND FIXTURES AND EQUIPMENT
 (WATER HEATER) IDENTIFIED. SHOW ALL VALVES AND BACKFLOW
 PREVENTER(S)
 F.PLUMBING WATER AND SANITARY FLOOR PLAN WITH FIXTURES
 IDENTIFIED. SHOW ALL TRAPS REQUIRED AT ROUGH IN STAGE.
  
 8. PER WPB FBC 107.2.1, PROVIDE UP TO DATE
 CERTIFICATION AND LOCATION OF EXISTING LEAD FREE
 BACKFLOW PREVENTER OR PROVIDE NEW WITH SPECIFICATION
 AND DETAIL FOR THE SAME. LOCATE EXISTING OR NEW ON THE
 PLANS.
  
 9.PER WPB FBC 107.2.1, IDENTIFY ALL ACCESSIBLE PLUMBING
 FIXTURES ON THE FLOOR PLAN AND SHOW COMPLIANCE WITH FBC
 ACC CHAPTERS 3 AND 6 BY PROVIDING DETAILS INDICATING
 THE FOLLOWING: NOTE; PLEASE SEE FBC ACC 604.9
 CHILDREN'S ACCESSIBILITY GUIDELINES FOR WATER CLOSETS
 AND TOILET ROOMS.
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
 I.ACCESSIBLE LAVATORIES AND SINKS (PER FBC ACC 212.3,
 THE KITCHEN SINK SHALL MEET THIS REQUIREMENT) SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 606.3, ADDITIONALLY SHOW
 TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND
 306.3
 JUNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.SHOW TURNING SPACE FOR WATER CLOSET COMPLYING WITH
 FBC ACC 304.3.1 OR 304.3.2.
 L.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES
 PER FBC ACC 304.4.
 M.SHOW CLEAR FLOOR SPACES FOR ACCESSIBLE LAVATORIES AND
 ACCESSIBLE SINKS (PER FBC ACC 212.3, THE KITCHEN SINK
 SHALL MEET THIS REQUIREMENT). THE CLEAR FLOOR OR GROUND
 SPACE SHALL BE 30 INCHES (760 MM) MINIMUM BY 48 INCHES
 (1220 MM) MINIMUM AND COMPLY WITH FBC ACC SECTION 305.
 N.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 O.NOT USED
 P.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER
 FBC ACC 602.1.
 Q.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 R.EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED AT UNITS FOR CHILDREN?S USE WHERE
 THE SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM)
 MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING
 BUMPERS.
 S.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC
 602.3.
 T.SPOUT OUTLETS FOR WHEELCHAIR SHALL BE 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 602.4.
 U.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7
 V.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER
 FBC ACC 602.5.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PAPER PLANS TO BE SIGNED AND SEALED BY THE DESIGNER
 AS REQUIRED BY FAC AND FS.
 ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090644 2508 N AUSTRALIAN AVE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-07 Cont ID  
Sent By rmcphers Date 2021-05-07 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 15:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-06 Cont ID  
Sent By rmcphers Date 2020-11-06 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2020-11-06 Time 15:06 Sent To  
Notes
2020-11-06 15:07:34SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-09-17 Cont ID  
Sent By shill Date 2020-09-17 Time 15:24 Rev Time 0.00
Received By shill Date 2020-09-17 Time 15:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-17 Cont ID  
Sent By ajones Date 2020-09-17 Time 11:44 Rev Time 0.00
Received By ajones Date 2020-09-17 Time 11:44 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved