Plan Review Details - Permit 20090565
Plan Review Stops For Permit 20090565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-17 Cont ID  
Sent By rmcdouga Date 2020-12-17 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2020-12-17 Time 14:32 Sent To  
Notes
2020-12-17 13:56:55PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) PARTIALLY ADDRESSED. (SPECIFY THE HEIGHT OF THE
 POLES. THE POLES ARE REQUIRED TO COMPLY WITH FBC
 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL
 BE BASED ON RATIONAL ANALYSIS, USING THE APPLICABLE
 WIND LOADS OF CHAPTER 16 AS SHOWN BELOW: 3105.4.2.1 THE
 WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE-COVERED
 STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY
 MEMBRANE OR FABRIC AT WIND VELOCITIES OF 75 MPH, SHALL
 BE BASED ON THE FOLLOWING CRITERIA: 1.MINIMUM WIND
 SPEED 105 MPH 2.EXPOSURE CATEGORY B, C OR D AS DEFINED
 IN CHAPTER 16.THE POLES WITH THE FABRIC REMOVED ARE
 REQUIRED TO BE CAPABLE OF WITHSTANDING 170 MPH
 WINDSPEED IN EXPOSURE C.) SUBMIT SIGNED AND SEALED
 DRAWINGS FROM A FLORIDA LICENSED DESIGN PROFESSIONAL
 THAT PROVIDE STRUCTURAL DETAILS FOR THE POLES AND THEIR
 FOUNDATIONS. SPECIFY THE HEIGHT AND DIMENSIONS OF THE
 POLES. PROVIDE THE DIMENSIONS OF THE FOUNDATIONS.
 SPECIFY THE WIND DESIGN DATA ON THE DRAWINGS AND
 PROVIDE CALCULATIONS. FS 471 OR 481, FBC 107, 1609 &
 3105.3
  
 3) NOT ADDRESSED. (BASED ON THE PLANS IT APPEARS THAT
 THE SAILS WILL HAVE TO BE REMOVED WHEN THE WIND SPEED
 IS FORCAST TO EXCEED 75 MPH.) IF THE SHADE SAILS ARE
 REQUIRED TO BE REMOVED DURING HIGH WIND EVENTS, SPECIFY
 WHEN THEY ARE TO BE REMOVE AND PROVIDE DETAILED REMOVAL
 INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW
 THIS IS DONE IN TERMS THAT A LAYMAN WILL UNDERSTAND.
 THESE INSTRUCTIONS ARE TO BE PROVIDED TO THE PROPERTY
 OWNER, OWNER'S REPRESENTATIVE OR LESSEE. FBC 107.2.1
  
 4) SUBMIT THE FLAME SPREAD EVALUATION FOR THE SHADE
 SAIL FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E84 OR UL 723.
  
 5) COMPLIED.
  
 6) THE VALUE OF $100.00 IS LOW FOR THIS PROJECT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 08:16 Sent To  
Notes
2020-10-02 08:51:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SURVEY AND A SITE PLAN SHOWING THE
 LOCATIONS OF THE METAL POLES THAT SUPPORT THE CABLES
 AND THE SHADE SAIL FABRIC. FBC 107.2.1
  
 2) SUBMIT SIGNED AND SEALED DRAWINGS FROM A FLORIDA
 LICENSED DESIGN PROFESSIONAL THAT PROVIDE STRUCTURAL
 DETAILS FOR THE POLES AND THEIR FOUNDATIONS. SPECIFY
 THE HEIGHT AND DIMENSIONS OF THE POLES. PROVIDE THE
 DIMENSIONS OF THE FOUNDATIONS. SPECIFY THE WIND DESIGN
 DATA ON THE DRAWINGS AND PROVIDE CALCULATIONS. FS 471
 OR 481, FBC 107, 1609 & 3105.3
  
 3) IF THE SHADE SAILS ARE REQUIRED TO BE REMOVED DURING
 HIGH WIND EVENTS, SPECIFY WHEN THEY ARE TO BE REMOVE
 AND PROVIDE DETAILED REMOVAL INSTRUCTIONS WITH
 PHOTOGRAPHS/DRAWINGS THAT SHOW HOW THIS IS DONE IN
 TERMS THAT A LAYMAN WILL UNDERSTAND. THESE INSTRUCTIONS
 ARE TO BE PROVIDED TO THE PROPERTY OWNER, OWNER'S
 REPRESENTATIVE OR LESSEE. FBC 107.2.1
  
 4) SUBMIT THE FLAME SPREAD EVALUATION FOR THE SHADE
 SAIL FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E84 OR UL 723.
  
 5) SPECIFY THE HEIGHT OF THE SAIL SHADES ABOVE GRADE.
 FBC 107.2.1
  
 6) THE VALUE OF $100.00 IS LOW FOR THIS PROJECT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-12-15 Cont ID  
Sent By pleduc Date 2020-12-15 Time   Rev Time 0.00
Received By pleduc Date 2020-12-15 Time 09:41 Sent To  
Notes
2020-12-15 09:46:31THERE ARE NO INDICATIONS OF RESPONSE TO FIRE'S PREVIOUS
 COMMENTS.
  
 THE PREVIOUS COMMENTS FROM FIRE ARE POSTED BELOW,
 PLEASE SPECIFICALLY ADDRESS.
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF FIRE RETARDENT OF THE
 PROPOSED MATERIAL.
  
 PER NFPA 1
  
 25.2.2 FLAME PROPAGATION PERFORMANCE.
 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME
 PROPAGATION
 PERFORMANCE CRITERIA CONTAINED IN TEST METHOD 2 OF NFPA
 701,
 STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF
 TEXTILES
 AND FILMS. [101: 11.11.2.1]
 25.2.2.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE TENT
 FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER
 EVIDENCE OF
 ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ.
 (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY
 OTHER
 INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO
 THE
 AHJ. [101: 11.11.2.2]
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By pleduc Date 2020-10-06 Time   Rev Time 0.00
Received By pleduc Date 2020-10-06 Time 14:16 Sent To  
Notes
2020-10-06 14:21:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF FIRE RETARDENT OF THE
 PROPOSED MATERIAL.
  
 PER NFPA 1
  
 25.2.2 FLAME PROPAGATION PERFORMANCE.
 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME
 PROPAGATION
 PERFORMANCE CRITERIA CONTAINED IN TEST METHOD 2 OF NFPA
 701,
 STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF
 TEXTILES
 AND FILMS. [101: 11.11.2.1]
 25.2.2.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE TENT
 FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER
 EVIDENCE OF
 ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ.
 (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY
 OTHER
 INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO
 THE
 AHJ. [101: 11.11.2.2]
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 14:58 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 14:58 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-17 Cont ID  
Sent By rmcdouga Date 2020-12-17 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2020-12-14 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By ccarvaja Date 2020-10-01 Time 14:00 Rev Time 0.00
Received By ccarvaja Date 2020-09-18 Time 14:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-17 Cont ID  
Sent By rmcdouga Date 2020-12-17 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2020-12-17 Time 14:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 08:16 Sent To  
Notes
2020-10-02 08:29:39SIGNED AND SEALED DRAWINGS FROM A DESIGN PROFESSIONAL
 ARE REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By elevesqu Date 2020-10-01 Time 14:30 Rev Time 0.00
Received By elevesqu Date 2020-10-01 Time 14:30 Sent To  
Notes
2020-10-01 14:31:20CANNOT BE ATTACHED TO ANY POLES OR ITEMS WITHIN CITY
 ROW
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By aaponte Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***