Plan Review Details - Permit 20090530
Plan Review Stops For Permit 20090530
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 15:28 Sent To  
Notes
2020-09-24 15:30:45CONTRACTOR EMAILED CLARIFICATION OF OPENING WIDTH. IT
 APPEARED TO BE 164" BUT WAS ACTUALLY 104".

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 12:13 Sent To  
Notes
2020-09-24 13:26:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DRAWING THAT WAS SUBMITTED SHOWS THE DOOR
 OPENING AS 164" X 96". THE MAXIMUM WIDTH OF THE DOOR IN
 THE PRODUCT APPROVAL IS 151.5" WHICH IS TOO SMALL FOR
 THE OPENING. PLEASE CLARIFY. CITY AMENDMENTS FBC 107.1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2020-09-14 Time 08:58 Sent To  
Notes
***NONE***