Plan Review Details - Permit 20090481
Plan Review Stops For Permit 20090481
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-10-07 Cont ID  
Sent By jleahy Date 2020-10-07 Time 13:33 Rev Time 0.00
Received By jleahy Date 2020-10-07 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 14:46 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-09-30 Cont ID  
Sent By jleahy Date 2020-09-30 Time 17:39 Rev Time 0.00
Received By jleahy Date 2020-09-30 Time 17:34 Sent To  
Notes
2020-09-30 17:41:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THE VALUE OF THE WORK SHOWN IS LOW ON PERMIT, SUBMIT A
 SIGNED CONTRACT WITH THE OWNER FOR THE WORK INVOLVED.
 PLEASE MEET MINIMUM INDUSTRY STANDARDS WHEN SUBMITTING
 CONTRACT VALUE.
  
 PLEASE SUBMIT THE CUT THEYS FOR THE CAMERAS 110.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By jleahy Date 2020-09-22 Time 13:19 Rev Time 0.00
Received By jleahy Date 2020-09-22 Time 13:17 Sent To  
Notes
2020-09-22 13:22:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT STATES PHONE, TV ECT, ECT. PLEASE INDICATE THEM
 ON PLAN
  
 SUBMIT A SIGNED CONTRACT FOR THE WORK.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 PLAN IS NOT SIGNED.
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 14:46 Rev Time 0.00
Received By jleahy Date 2020-10-01 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-30 Cont ID  
Sent By jleahy Date 2020-09-30 Time 17:42 Rev Time 0.00
Received By jleahy Date 2020-09-24 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-22 Cont ID  
Sent By jleahy Date 2020-09-22 Time 13:24 Rev Time 0.00
Received By jleahy Date 2020-09-16 Time 16:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 14:46 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 14:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-30 Cont ID  
Sent By jleahy Date 2020-09-30 Time 17:42 Rev Time 0.00
Received By jleahy Date 2020-09-30 Time 17:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By jleahy Date 2020-09-22 Time 13:23 Rev Time 0.00
Received By jleahy Date 2020-09-22 Time 13:23 Sent To  
Notes
2020-09-22 13:24:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  