Plan Review Details - Permit 20090465
Plan Review Stops For Permit 20090465
Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 16:21 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 16:13 Sent To  
Notes
2021-03-25 16:22:512ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090465
 3/25/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 PREVIOUS REVIEW COMMENT NOT ADDRESSED.
 AFTER REVIEWING THE COMMENT BELOW PLEASE CONTACT ME .
  
 1) PLEASE SHOW THE PE LINE TO THE NEW GENERATOR THAT IS
 CURRENTLY BEING INSPECTED UNDER PERMIT 20041075. SHOW
 THE PE PIPING POINT OF CONNECTION TO THE SCHEDULE 40
 AND ADD THE 575,000 BTU LOAD OF THE GENERATOR TO THE
 TOTAL LOAD OF THE SYSTEM- SECTIONS G2413.3 & G2413.4
 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-22 Cont ID  
Sent By ccole Date 2021-03-22 Time 13:51 Rev Time 0.00
Received By ccole Date 2021-03-22 Time 13:51 Sent To  
Notes
2021-03-22 13:52:082ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090465
 3/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE PE LINE TO THE NEW GENERATOR THAT IS
 CURRENTLY BEING INSPECTED UNDER PERMITS 20041074 &
 20041075. SHOW THE PE PIPING POINT OF CONNECTION TO THE
 SCHEDULE 40 AND ADD THE 575,000 BTU LOAD OF THE
 GENERATOR TO THE TOTAL LOAD OF THE SYSTEM- SECTIONS
 G2413.3 & G2413.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 11:18 Rev Time 0.00
Received By ccole Date 2020-10-29 Time 10:12 Sent To  
Notes
2020-10-29 11:19:411ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090465
 10/29/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A PERMIT APPLICATION FOR THE PROPOSED GAS
 PIPING INSTALLATION- SECTION 105.1 WPB.
  
 2) GAS RISER DRAWING:
 A) SHOW ALL PIPE SIZES INCLUDING THE MAIN PIPE FROM THE
 METER TO THE TEE, THE MAIN RUN, AND THE BRANCHES TO THE
 APPLIANCES- SECTION G2413.1 FBC RES.
 B) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS
 AND THE OUTPUT PRESSURES AT EACH APPLIANCE- SECTION
 G2421.1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, INPUT AND OUTPUT PRESSURES AND PIPE
 SIZES, AND ORIFICE SIZES.
 C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATORS- SECTION
 G2421.2(7).
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED APPLIANCES OR PLACE A NOTE THAT THE SPECS
 WILL BE ONSITE AT TIME OF INSPECTION- SECTION 107.2.1
 WPB. THE SPECS SHALL BE MARKED UP OR HIGHLIGHTED TO
 INDICATE THE BTUH LOADS AND INPUT PRESSURES.
  
 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE
 DRAWINGS SHALL PROVIDE HIS COMPLETE SIGNATURE- FIRST
 AND LAST NAME- ON BOTH PLANS- SECTION 107.2.1 WPB, AND
 FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-03-25 Time   Rev Time 0.00
Received By aoliver Date 2021-03-24 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-22 Time   Rev Time 0.00
Received By ccarvaja Date 2021-03-15 Time 18:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 11:19 Rev Time 0.00
Received By ccole Date 2020-10-23 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 16:13 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 16:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By ccole Date 2021-03-22 Time 13:53 Rev Time 0.00
Received By ccole Date 2021-03-22 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 11:19 Rev Time 0.00
Received By ccole Date 2020-10-29 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By ccole Date 2021-03-22 Time 13:53 Rev Time 0.00
Received By ccole Date 2021-03-22 Time 13:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 11:32 Rev Time 0.00
Received By ccole Date 2020-10-29 Time 10:12 Sent To  
Notes
2020-10-29 11:33:35SIGNATURE REVIEW
 10/29/2020
  
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWINGS
 SHALL PROVIDE HIS COMPLETE SIGNATURE- FIRST AND LAST
 NAME- ON BOTH PLANS- SECTION 107.2.1 WPB, AND FLORIDA
 STATUTES 471.003(2)(H) & 471.025.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER