Plan Review Details - Permit 20090442
Plan Review Stops For Permit 20090442
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-02-18 Cont ID  
Sent By cpuell Date 2021-02-18 Time 11:11 Rev Time 0.00
Received By cpuell Date 2021-02-18 Time 11:11 Sent To  
Notes
2021-02-18 11:11:34ADDRESS IS 2606 FLORIDA AVE PERMIT UPDATED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By cpuell Date 2021-02-16 Time 13:43 Rev Time 0.00
Received By cpuell Date 2021-02-16 Time 13:43 Sent To  
Notes
2021-02-16 13:45:40PLAN COVER SHEET STATES 2600 FLORIDA AVE SUITE B THIS
 IS NOT CURRENTLY A LEGAL ADDRESS IN OUR SYSTEM. PERMIT
 APPLICATION HAS NOT SUITE NUMBER AT ALL. PLEASE CONTACT
 [email protected] TO ESTABLISH A LEGAL ADDRESS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2021-03-03 Time 07:54 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 14:15 Sent To  
Notes
2021-02-10 14:16:24PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 14:15 Sent To  
Notes
2021-03-03 07:50:37BUILDING PERMIT APPLICATION REQUIRED - CANNOT BE OWNER
 BUILDER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By rmcphers Date 2020-10-05 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2020-10-05 Time 09:07 Sent To  
Notes
2020-10-05 11:21:55BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING SHOW "SCOPE OF WORK" AS "VANILLA SHELL" -
 PLEASE CORRECT "SCOPE OF WORK" OR THE DRAWINGS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-04 Cont ID  
Sent By jleahy Date 2021-02-04 Time 14:38 Rev Time 0.00
Received By jleahy Date 2021-02-04 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-03 Cont ID  
Sent By jleahy Date 2020-10-03 Time 10:32 Rev Time 0.00
Received By jleahy Date 2020-10-03 Time 10:31 Sent To  
Notes
2020-10-03 10:55:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM DOES NOT SHOW SIZE OF CONDUCTORS.
 PLEASE INDICATE THE SIZE OF THE FEEDER CONDUCTORS.
  
 2) FAULT CURRENT CALCULATION REQUIRED FOR SERVICE AND
 NEW PANEL 110.9, 110.10. PROVIDE LABEL AT SERVICE FOR
 AIC RATING PER 110.24
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 3) PLEASE INDICATE LIGHTING LAYOUT AND LIGHTING
 CONTROL, SHOW NUMBER OF USB OUTLETS UNDER THE COUNTER.
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  
 4) LOAD CALCULATION DOES NOT INCLUDE RECEPTACLE
 OUTLETS, SIGN CIRCUIT, DISPLAY LIGHTING, USB OUTLETS,
 ECT. ECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-22 Cont ID  
Sent By pleduc Date 2020-09-22 Time   Rev Time 0.00
Received By pleduc Date 2020-09-22 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 07:56 Rev Time 0.00
Received By rmcphers Date 2021-02-17 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-16 Cont ID  
Sent By cpuell Date 2021-02-16 Time 13:46 Rev Time 0.00
Received By cpuell Date 2021-01-29 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-05 Cont ID  
Sent By rmcphers Date 2020-10-05 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 17:13 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 17:13 Sent To  
Notes
2021-02-23 17:14:4002/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 16:18 Rev Time 0.00
Received By ccole Date 2021-02-05 Time 12:59 Sent To  
Notes
2021-02-05 16:18:252ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20090442
 2/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 WATER ISOMETRIC AND WATER PLAN:
  
 A) INSTA-HOT WATER HEATERS LABELED ON PLAN NOT SHOWN ON
 THE ISOMETRIC- SECTION 107.2.1 WPB.
  
 B) LOCATION OF WATER HEATER EXPANSION TANK SHOWN ON HOT
 WATER PIPE IS NOT IN COMPLIANCE WITH SECTION 607.3 FBC
 P. CORRECT LOCATION ON THE COLD WATER INLET PIPE IS
 SHOWN IN THE WATER HEATER DETAIL.
  
 C) TWO BATCH BREWERS ARE SHOWN BUT THE ISOMETRIC AND
 PLAN SHOW ONLY ONE FILTERED WATER LINE CONNECTION-
 SECTION 107.2.1 WPB.
  
 D) WATER SUPPLY CONNECTION TO ESPRESSO MACHINE AND
 RINSER SHOWN ON THE ISOMETRIC BUT ON THE PLAN- SECTION
 107.2.1 WPB.
  
 E) PROVIDE A BACKFLOW DEVICE FOR THE WATER SUPPLY TO
 THE RINSER AND INDICATE THE MAKE AND MODEL OF ALL
 BACKFLOW DEVICES SHOWN ON THE RISER- SECTION 608.3 FBC
 P.
  
 F) PROVIDE WATER HAMMER ARRESTORS FOR SUPPLY LINES TO
 THE FILTRATION SYSTEM, BATCH BREWERS, EXPRESSO MACHINE
 ETC.- SECTION 604.9 FBC P.
  
 G) THERE IS A NOTE INDICATING WATER SUPPLY TO THE
 KETTLES HOWEVER THE WATER SUPPLY LINES ARE NOT SHOWN-
 SECTION 107.2.1 WPB.
  
 H) INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO THE
 LAVATORY- SEE SECTIONS 416.5 AND 607.1.2 FBC P.
  
 I) IT APPEARS A 3/4 IN. HOT WATER PIPE IS SUPPLYING THE
 NEW LAVATORY. PLEASE SEE SECTION C404.5.1 AND TABLE
 C404.5.1 FBC EC- A 3/4 IN. PIPE IS LIMITED TO A MAXIMUM
 LENGTH OF 0.5 FT. FROM THE NEAREST HOT WATER SOURCE.
  
 2) SHEET P1.0: THE SANITARY ISOMETRIC APPEARS TO SHOW A
 SINGLE DRAIN PIPE FROM THE 3-COMPARTMENT SINK
 DISCHARGING INTO THE FLOOR SINK. PLEASE SEE SECTION
 802.1.1 FBC P AND PROVIDE A DETAIL SHOWING EACH WELL OF
 THE SINK DISCHARGING INDEPENDENTLY INTO THE FLOOR SINK.
 3) P1.0: PLEASE ADD SLAB CUTTING FOR UNDERGROUND DRAINS
 AND WATER SUPPLY PIPING IN THE PLUMBING DEMOLITION
 NOTES- SECTION 107.2.1 WPB. REFERENCE IS MADE TO A SLAB
 REPAIR DETAIL ON SHEET A4.0 HOWEVER THERE IS NO SHEET
 A4.0 IN THE SET- SECTION 107.2.1 WPB.
  
 4) P1.0 PLUMBING SPECIFICATIONS: PROVIDE DWV AND WATER
 SUPPLY AND FILTERED WATER SUPPLY PIPING MATERIAL
 SPECIFICATIONS, AND THE TYPE AND SIZE OF HOT WATER PIPE
 INSULATION- SECTIONS303.1 & 303.2 FBC P, AND TABLE
 C403.2.10 FBC EC.
  
 5) P1.0: INDICATE HOW UNDER SLAB WATER PIPING WILL
 PROTECTED FROM CORROSION- SECTION 305.1 FBC P.
  
 6) P1.0- MISSING ACCESSIBILITY DETAILS- FBC- ACC.
 A) WATER CLOSET AND LAVATORY CLEAR FLOOR SPACE
 DIMENSIONS- SECTIONS 604.3 & 606.2.
 B) GRAB LOCATIONS AND LENGTHS NOT SHOWN CORRECTLY
 ACCORDING TO SECTION 604.5 & FIGURES 604.5.1 & 604.5.2
 C) LAVATORY KNEE AND TOE CLEARANCES- SECTION 606.2.
  
 7) 2ND REQUEST FOR PLUMBING FIXTURES CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By jesmith Date 2020-09-24 Time 17:15 Rev Time  
Received By jesmith Date   Time   Sent To  
Notes
2020-09-24 17:15:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090442 2600 FLORIDA AVE
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE BUILDING
 KEY PLAN AND INDICATE THE TENANT SPACE FOOTPRINT IN THE
 BUILDING
 ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS FOR SIZING OF GREASE INTERCEPTOR
  
 1.A REVIEW OF PUBLIC RECORDS PRESENT AN UNCLEAR
 UNDERSTANDING OF THE EXISTING SPACE. BY ALL ACCOUNTS
 THE LAST CHANGE OF OCCUPANCY WAS FROM AUTO REPAIR TO
 ART STUDIO (SEE PAST PERMITS 14100679 EXPIRED AND
 SUBSEQUENT PERMIT 15020882 DATED 2/26/2015 FOR
 INSPECTION DUE TO FAILED COP) THERE ARE NO PERMIT PLANS
 ON RECORD FOR THAT CHANGE OF OCCUPANCY. AS SUCH, THE
 PERMIT NEEDS TO ADDRESS THE EXISTING CONDITIONS AS WELL
 AS THE REQUESTED CHANGES AND SHALL COMPLY WITH 2017
 FLORIDA BUILDING CODE, 2017 FLORIDA ACCESSIBILITY CODE
 AND 2017 FLORIDA PLUMBING CODE PER WPB FBC SECTION
 107.3.5.1.3 PLUMBING .
 2.PER WPB FBC 107.2.1, PROVIDE PLAN AND ELEVATION
 DETAILS OF BATHROOM SHOWING COMPLIANCE WITH THE
 PROVISION OF FBC ACC CHAPTERS 3 AND 6.
 3.PER WPB FBC 107.2.1, PROVIDE WALL SCHEDULE/DETAILS
 FOR BATHROOM SHOWING COMPLIANCE WITH FBC 1210.2.1 AND
 1210.2.2.
 4.P-1 PLAN VIEW SHOWS HOT AND COLD WATER TO NEW SINKS
 CONNECTED TO ADJACENT TENANT SPACE. CONNECT WITHIN THE
 TENANT SPACE BEING PERMITTED. PER WPB FBC 107.2.1,
 PROVIDE SIZED HOT AND COLD WATER RISER DIAGRAM OF
 COMPLETE SYSTEM (INCLUDING FILTERED). SHOW ALL VALVES,
 REQUIRED BACKFLOW DEVICES, EQUIPMENT AND APPURTENANCES
 (WATER HEATER, FILTERS, COFFEE BREWER, ETC.). FLOOR
 PLAN AND RISER DIAGRAM SHALL BE IN AGREEMENT.
 5.PROVIDE SCHEDULE AND DETAIL OF WATER HEATER SHOWING
 HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, HW,
 VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC
 PL 504.2) , THERMAL EXPANSION CONTROL DEVICE (INCLUDING
 SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER
 HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER WPB
 FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, 504.1,
 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2.
 6.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR WATER FILTRATION
 SYSTEM.
 7.PER FBC PL 1003.1, PROVIDE A GREASE INTERCEPTOR FOR
 THE THREE-COMPARTMENT SINK. PER WPB FBC 107.2.1,
 PROVIDE SPECIFICATION FOR INTERCEPTOR AND DETAIL OF
 SINK AND INTERCEPTOR, SHOWING HOW DISCHARGED TO
 SANITARY FLOOR SINK.
 8.PER WPB FBC 107.2.1, INDICATE ON PLAN ALL ITEMS (I.E.
 EXPRESSO MACHINE, FILTRATION SYSTEM) THAT ARE TO
 DISCHARGE TO SANITARY AND HOW THEY WILL DISCHARGE (I.E.
 TO HUB DRAIN THROUGH (SIZED) INDIRECT WASTE WITH AIR
 GAP)
 9.SANITARY RISER DIAGRAM AND FLOOR PLAN SHALL BE
 COMPLETE AND SHALL BE IN AGREEMENT.
 10.CLEANOUT REQUIRED AT JUNCTION OF SANITARY BUILDING
 DRAIN AND BUILDING SEWER PER FBC PL 708.1.3.
 11.PER FBC PL 904.1, THE VENT SYSTEM SERVING EACH
 BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT PIPE
 THAT EXTENDS TO THE OUTDOORS.
 12.1002.4.1TRAP SEAL PROTECTION.PER FBC PL 1002.4.1,
 TRAP SEALS OF FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT
 TO EVAPORATION SHALL BE PROTECTED BY ONE OF THE METHODS
 IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090442 2600 FLORIDA AVE

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 17:12 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 17:12 Sent To  
Notes
2021-02-23 17:13:32A SEPARATE SUB-PERMIT FOR THE GREASE INTERCEPTOR IS
 REQUIRED BY A LICENSED CONTRACTOR FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2021-03-03 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-05 Cont ID  
Sent By rmcphers Date 2020-10-05 Time 11:34 Rev Time 0.00
Received By rmcphers Date 2020-10-05 Time 11:34 Sent To  
Notes
***NONE***