Plan Review Details - Permit 20090357
Plan Review Stops For Permit 20090357
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By rmcphers Date 2020-09-25 Time 09:54 Rev Time 0.00
Received By rmcphers Date 2020-09-25 Time 09:53 Sent To  
Notes
2020-09-25 09:55:21DRAWINGS DO NOT SHOW ANY NEW STRUCTURAL OR BUILDING
 WORK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By jleahy Date 2021-02-17 Time 09:54 Rev Time 0.00
Received By jleahy Date 2021-02-17 Time 09:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-01-27 Cont ID  
Sent By jleahy Date 2021-01-27 Time 14:40 Rev Time 0.00
Received By jleahy Date 2021-01-27 Time 14:29 Sent To  
Notes
2021-01-27 14:42:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NOT ALLOWED TO HAVE MORE THAN ONE BRANCH CIRCUIT FEED
 AN OUT BUILDING, NEED TO ADD A PANEL TO THE GUEST HOUSE
 AND DRIVE GROUND RODS PER 250. 66, 225.30, 225.31,
 225.32

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 13:51 Rev Time 0.00
Received By jleahy Date 2020-09-21 Time 13:48 Sent To  
Notes
2020-09-21 13:52:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONLY SMOKE ALARMS ARE SHOWN IS THIS EXTENT OF THE WORK?

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 10:41 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By jleahy Date 2021-02-17 Time 09:58 Rev Time 0.00
Received By jleahy Date 2021-02-11 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-27 Cont ID  
Sent By jleahy Date 2021-01-27 Time 14:46 Rev Time 0.00
Received By jleahy Date 2021-01-22 Time 16:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By shill Date 2020-09-25 Time 11:12 Rev Time 0.00
Received By shill Date 2020-09-14 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-01-25 Cont ID  
Sent By medwards Date 2021-01-25 Time 07:24 Rev Time 0.00
Received By medwards Date 2021-01-25 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 14:24 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 14:07 Sent To  
Notes
2020-09-16 14:26:40PROVIDE SPECIFICATIONS FOR SECURING THE OUTDOOR
 CONDENSING UNIT. FBC RES M1307.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-01-27 Cont ID  
Sent By lcrespo Date 2021-01-27 Time 08:41 Rev Time 0.00
Received By lcrespo Date 2021-01-27 Time 08:30 Sent To  
Notes
2021-01-27 08:42:5501/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By abelisle Date 2020-09-16 Time 14:34 Rev Time 0.00
Received By abelisle Date 2020-09-16 Time 11:30 Sent To  
Notes
2020-09-16 11:31:231ST REVIEW FBC-2017 PLUMBING
 PERMIT-20090357
 9/16/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. A SUB IRRIGATION PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. THE PLUMBING PLAN SHALL BEAR THE TITLE BLOCK AND
 ELECTRONIC SEAL AND SIGNATURE OF THE FL. LICENSED
 ARCHITECT OR ENGINEER WHO PREPARED THE DRAWING- SECTION
 107.2.1 WPB, FL. STATUTES 471.025 & 481.221, AND
 SECTIONS 61G15-23.005 & 61G1-16.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By jleahy Date 2021-02-17 Time 09:54 Rev Time 0.00
Received By jleahy Date 2021-02-17 Time 09:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-27 Cont ID  
Sent By jleahy Date 2021-01-27 Time 14:43 Rev Time 0.00
Received By jleahy Date 2021-01-27 Time 14:43 Sent To  
Notes
2021-01-27 14:46:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 14:31 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 14:31 Sent To  
Notes
2020-09-16 14:31:27PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  