Plan Review Details - Permit 20090347
Plan Review Stops For Permit 20090347
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-13 Cont ID  
Sent By pvalenti Date 2020-11-13 Time 10:26 Rev Time 0.00
Received By pvalenti Date 2020-11-13 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-03 Cont ID  
Sent By pvalenti Date 2020-11-03 Time 07:29 Rev Time 0.00
Received By pvalenti Date 2020-11-03 Time 06:00 Sent To  
Notes
2020-11-03 07:30:48PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND BUILDING REVIEW DENIED:
 FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE
 SELECTIONS), THE LOCATION OF EXHAUST TERMINATION SHOULD
 BE INDICATED ON PLAN, MUST BE AT NO LESS THAN 10'
 HORIZONTALLY OR 3' VERTICALLY ABOVE THE OPERABLE
 OPENINGS OF THE STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:23 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:00 Sent To  
Notes
2020-10-03 10:27:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE
 SELECTIONS), THE LOCATION OF EXHAUST TERMINATION SHOULD
 BE INDICATED ON PLAN, MUST BE AT NO LESS THAN 10'
 HORIZONTALLY OR 3' VERTICALLY ABOVE THE OPERABLE
 OPENINGS OF THE STRUCTURE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By jleahy Date 2020-09-29 Time 16:55 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 16:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 15:54 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 15:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-22 Cont ID  
Sent By ccole Date 2020-10-22 Time 09:29 Rev Time 0.00
Received By ccole Date 2020-10-22 Time 09:29 Sent To  
Notes
2020-10-22 09:30:402ND REVIEW FBC-2017 RES.
 PERMIT- 20090347
 10/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 IT APPEARS NO CORRECTIONS WERE MADE TO THE GAS RISER
 DRAWING. PLEASE COMPLY WITH THE 1ST AND 2ND REVIEW
 COMMENTS LISTED BELOW.
  
 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7945 VIA
 VILLAGIO SHOW GAS PERMIT #04040274 ISSUED 4/10/2004 FOR
 INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS
 INDICATE A TOTAL LOAD OF 564,000 BTU'S: POOL HEATER-
 400,000. GRILL- 50,000. COOKTOP- 42,000. DRYER- 22,000.
 WATER HEATER- 50,000. REVISE THE RISER TO SHOW THE
 CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM-
 SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE
 NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS
 INDICATED TO BE 88 FT.
  
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER
 TO INDICATE 870,000 BTUH.
  
 C) USING THE PIPE SIZING TABLE 402.4(3) FBC FG SHOWN ON
 THE RISER, THE 3/4 IN. GALVANIZED MAIN RISER PIPE WILL
 SUPPLY A MAXIMUM 289,000 BTU'S. THE RISERS MUST BE
 INCREASED IN SIZE TO 1-1/4 IN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 16:42 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 15:23 Sent To  
Notes
2020-09-24 16:44:051ST REVIEW FBC-2017 RES.
 PERMIT- 20090347
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7945 VIA
 VILLAGIO SHOW GAS PERMIT #04040274 ISSUED 4/10/2004 FOR
 INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS
 INDICATE A TOTAL LOAD OF 564,000 BTU'S: POOL HEATER-
 400,000. GRILL- 50,000. COOKTOP- 42,000. DRYER- 22,000.
 WATER HEATER- 50,000. REVISE THE RISER TO SHOW THE
 CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM-
 SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE
 NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS
 INDICATED TO BE 88 FT.
  
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER
 TO INDICATE 870,000 BTUH.
  
 C) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION
 G2413.3 FBC RES. TABLE 402.4(3) FBC FG WITH A 3.0 IN.
 PRESSURE DROP LISTED ON THE PLANS IS NOT A SIZING TABLE
 FOUND IN THE FBC RES. TYPICALLY PRESSURE DROP IN
 RESIDENTIAL LOW PRESSURE SYSTEMS IS 0.5 IN. W.C. PLEASE
 REVIEW SECTION G2413.5 (402.5 ) ALLOWABLE PRESSURE DROP
 WHICH INDICATES: THE DESIGN PRESSURE LOSS IN ANY PIPING
 SYSTEM UNDER MAXIMUM PROBABLE FLOW CONDITIONS, FROM THE
 POINT OF DELIVERY TO THE INLET CONNECTION OF THE
 APPLIANCE, SHALL BE SUCH THAT THE SUPPLY PRESSURE AT
 THE APPLIANCE IS GREATER THAN OR EQUAL TO THE MINIMUM
 PRESSURE REQUIRED BY THE APPLIANCE.
  
 D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS
 G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH.
 INDICATE THE TABLES USED TO SIZE THE SCHEDULE 40
 METALLIC- SEE TABLES G2413.4(1)- G2413.4(8). PLEASE
 NOTE IF USING THE LONGEST LENGTH METHOD TO SIZE THE
 SCHED. 40 METALLIC, THE MAIN PIPE FROM THE METER TO THE
 1ST TEE, ACCORDING TO TABLE G2413.4(1) [402.4(2)] SHALL
 BE MINIMUM 2 IN. FOR A 870,000 BTUH LOAD AT 88 FT.
 DEVELOPED LENGTH. THE BRANCH LEG FROM THE TEE TO THE
 GENERATOR REGULATOR SHALL BE 1-1/4 IN., AND THE BRANCH
 LEG TO THE EXISTING APPLIANCES SHALL BE 1-1/2 IN.
  
 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5 FT. AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA
 37, AND A MINIMUM OF 10 FT. FROM MECHANICAL OR GRAVITY
 AIR INTAKES (WINDOW AND DOOR OPENINGS) INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. CORRECT THE NOTES ON
 THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-20 Cont ID  
Sent By jleahy Date 2020-11-20 Time 09:32 Rev Time 0.00
Received By jleahy Date 2020-11-12 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-03 Cont ID  
Sent By pvalenti Date 2020-11-03 Time 07:31 Rev Time 0.00
Received By pvalenti Date 2020-10-21 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:27 Rev Time 0.00
Received By pvalenti Date 2020-09-14 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 15:54 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-22 Cont ID  
Sent By ccole Date 2020-10-22 Time 09:30 Rev Time 0.00
Received By ccole Date 2020-10-22 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 16:44 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 15:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By pvalenti Date 2020-11-13 Time 10:26 Rev Time 0.00
Received By pvalenti Date 2020-11-13 Time 10:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:20 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-11-19 Cont ID  
Sent By rthermid Date 2020-11-19 Time   Rev Time 0.00
Received By rthermid Date 2020-11-19 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-10-27 Time   Rev Time 0.00
Received By   Date 2020-10-27 Time   Sent To I
Notes
2020-10-27 12:52:07ADDRESS PREVIOUS ZONING COMMENTS. THE GENERATOR MUST BE
 SETBACK A MINIMUM OF 3.5 FEET FROM THE SIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By rthermid Date 2020-09-29 Time   Rev Time  
Received By rthermid Date 2020-09-29 Time   Sent To I
Notes
2020-09-29 09:17:10ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/29/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. THE REQUIRED
 SETBACK IS 8 FEET; THE GENERATOR MUST BE A MINIMUM OF
 3.5 FEET FROM THE SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved