Plan Review Details - Permit 20090345
Plan Review Stops For Permit 20090345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-07 Cont ID  
Sent By pvalenti Date 2020-11-07 Time 11:56 Rev Time 0.00
Received By pvalenti Date 2020-11-07 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:40 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:02 Sent To  
Notes
2020-10-03 10:43:47PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE
 SELECTION), THE LOCATION OF EXHAUST TERMINATION SHOULD
 BE INDICATED ON PLAN, MUST BE 10' HORIZONTALLY OR 3'
 ABOVE THE OPERABLE OPENINGS OF THE STRUCTURE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By jleahy Date 2020-09-29 Time 16:53 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 16:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-09-18 Cont ID  
Sent By ccole Date 2020-09-18 Time 17:14 Rev Time 0.00
Received By ccole Date 2020-09-18 Time 15:51 Sent To  
Notes
2020-09-18 17:15:081ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090435
 9/18/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
 A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM,
 AND THE LENGTHS OF THE BRANCHES TO THE INTERIOR AND THE
 POOL HEATER- SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 B) INDICATE THE TOTAL LOAD OF THE SYSTEM- 1,126,000
 BTUH PER SECTION G2413.2
 C) PIPE SIZING TABLE 402.4(3) SHOWN ON THE RISER HAS AN
 INITIAL SUPPLY PRESSURE OF 8.0 IN. WC. AND A PRESSURE
 DROP OF 3.0 IN. WC. THIS APPEARS TO BE THE INCORRECT
 SIZING TABLE BECAUSE COMMON RESIDENTIAL LOW PRESSURE
 PIPING SYSTEMS ARE DESIGNED AT A PRESSURE AROUND 7 IN.
 WC. AND A PRESSURE DROP OF 0.5 IN. WC. THE PIPING MUST
 BE SIZED SUFFICIENTLY ENOUGH SO THAT THE PRESSURE DROP
 IS A HALF AN INCH OF WATER COLUMN OR LESS, WHEN ALL THE
 GAS APPLIANCES ARE ON. THE CALCULATED DROPPED PRESSURE
 (THE STATIC PRESSURE MINUS THE 3.0 IN. PRESSURE DROP),
 MUST BE GREATER THAN THE HIGHEST MINIMUM GAS PRESSURE
 REQUIRED BY ANY OF THE GAS APPLIANCES ON THE SYSTEM.
 PLEASE REFER TO TABLES G2413.4(1)- G2413.4(8) FBC RES.
 TABLE G2413.4(1) IS THE TYPICAL LOW PRESSURE SIZING
 TABLE USED. THE RELATIVE TABLE IN THE FBC FG IS
 {402.4(2). USING THIS TABLE THE 1 IN. SCHEDULE 40
 METALLIC PIPES SHOWN DOWNSTREAM OF THE REGULATOR AND
 METER, AT A MINIMUM SHALL BE SIZED AT 1-1/2 INCHES FOR
 THE TOTAL 1,126,000 BTUH LOAD. PLEASE NOTE THE 1-1/2
 IN. PIPE WILL MAX OUT FOR THE SYSTEM AT A TOTAL
 DEVELOPED LENGTH OF 30 FT. A SECOND OPTION WOULD BE TO
 INSTALL A 2.0 PSI REGULATOR AT THE METER IF POSSIBLE
 AND LOW PRESSURE REGULATORS FOR THE BRANCHES AND
 APPLIANCES.
 D) PROVIDE THE MAKE AND MODEL OF THE SELECTED REGULATOR
 ON THE RISER, AND MARK UP OR HIGHLIGHT THE SPEC SHEETS
 TO SHOW THE MODEL, INLET AND OUTLET PRESSURES, SPRING
 SELECTION, AND ORIFICE SIZE- SECTION G2421.1 & G2421.2.
 E) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 2) SURVEY: CORRECT THE 5 FT. CLEARANCE TO WINDOW AND
 DOOR OPENINGS PER SECTION R303.5.1 FBC RES. A MINIMUM
 10 FT. CLEARANCE IS REQUIRED. VERIFY THE ADJACENT HOUSE
 WALL IS NON-COMBUSTIBLE AND HAS A 1-HR. FIRE-RESISTANCE
 RATING, OTHERWISE A 5 FT. CLEARANCE IS REQUIRED PER
 SEC. 4.1.4 NFPA 37. PROVIDE THE CLEARANCE DISTANCE TO
 THE ADJACENT PROPERTY LINE- IT IS INDICATED AS 8.5 FT.
 FROM THE STRUCTURE- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-15 Cont ID  
Sent By cpuell Date 2020-11-15 Time 19:31 Rev Time 0.00
Received By cpuell Date 2020-11-02 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-22 Cont ID  
Sent By shill Date 2020-10-22 Time 10:55 Rev Time 0.00
Received By shill Date 2020-09-14 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-18 Cont ID  
Sent By ccole Date 2020-09-18 Time 17:20 Rev Time 0.00
Received By ccole Date 2020-09-18 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-07 Cont ID  
Sent By pvalenti Date 2020-11-07 Time 11:56 Rev Time 0.00
Received By pvalenti Date 2020-11-07 Time 11:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By kalexand Date 2020-11-13 Time 16:45 Rev Time 0.00
Received By kalexand Date 2020-11-13 Time 16:45 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-22 Cont ID  
Sent By kalexand Date 2020-10-22 Time 10:19 Rev Time 0.00
Received By kalexand Date 2020-10-22 Time 10:19 Sent To I
Notes
2020-10-22 10:21:18ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CORRECT SETBACK CALCULATIONS.
 ____________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved