Plan Review Details - Permit 20090342
Plan Review Stops For Permit 20090342
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 12:40 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 12:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By rmcdouga Date 2020-10-05 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2020-10-05 Time 15:31 Sent To  
Notes
2020-10-05 15:44:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC R303.5.1 GENERATOR EXHAUST SHALL BE LOCATED AT
 LEAST10 FEET FROM OPENINGS INTO A BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-01 Cont ID  
Sent By fgiaquin Date 2020-10-01 Time 21:53 Rev Time 0.00
Received By fgiaquin Date 2020-10-01 Time 20:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 11:47 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 10:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By ccole Date 2020-09-30 Time 11:26 Rev Time 0.00
Received By ccole Date 2020-09-30 Time 10:20 Sent To  
Notes
2020-09-30 11:29:511ST REVIEW FBC-2017 RES.
 PERMIT- 20090342
 9/30/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PIPE SIZING FOR A SCHED. 40
 METALLIC 2-PSI SYSTEM SHALL BE IN ACCORDANCE WITH TABLE
 G2413.4(2) FBC RES. OR THE EQUIVALENT TABLE 402.4(5)
 FBC FG. A LOW PRESSURE PIPE SIZING TABLE 402.4(3) IS
 SHOWN ON THE DRAWING, HOWEVER YOU SHOW A 2-PSI
 REGULATOR AT THE METER. IS THIS A LOW PRESSURE SYSTEM
 OR A 2-PSI SYSTEM? WHAT IS THE REGULATOR OUTLET
 DELIVERY PRESSURE?
  
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE INDIVIDUAL AND TOTAL
 LOADS ON THE RISER- SECTION G2413.2 FBC RES. & 107.2.1
 WPB.
  
 C) SHOW THE INLET AND OUTLET PRESSURES AT THE B31
 REGULATOR- SECTION G2421.1 & G2421.2. PLEASE NOTE THAT
 THE MARKED UP OR HIGHLIGHTED SPECS SHALL BE ONSITE FOR
 INSPECTION. THE SPECS SHALL INDICATE THE REGULATOR IS
 RATED FOR OUTDOOR USE, AND BE MARKED TO SHOW THE
 SELECTED MODEL, PRESSURES, SPRING SELECTION, AND
 ORIFICE SIZE.
  
 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5' AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37,
 AND A MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR
 INTAKES (WINDOW AND DOOR OPENINGS) INTO THE BUILDING-
 SEC. R303.5.1 FBC RES. PLEASE CORRECT THE NOTES ON THE
 DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 12:40 Rev Time 0.00
Received By rmcdouga Date 2020-11-10 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-05 Cont ID  
Sent By rmcdouga Date 2020-10-05 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2020-09-17 Time 15:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 11:47 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 10:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-30 Cont ID  
Sent By ccole Date 2020-09-30 Time 11:26 Rev Time 0.00
Received By ccole Date 2020-09-30 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 12:40 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 12:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-05 Cont ID  
Sent By rmcdouga Date 2020-10-05 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2020-10-05 Time 15:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By rthermid Date 2020-11-19 Time   Rev Time 0.00
Received By rthermid Date 2020-11-19 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By rthermid Date 2020-09-29 Time   Rev Time  
Received By rthermid Date 2020-09-29 Time   Sent To I
Notes
2020-09-29 09:07:40ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/29/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.THE SIDE SETBACK
 REQUIREMENT FOR THIS LOT IS 8 FEET;THE GENERATOR MUST
 BE A MINIMUM OF 4 FEET FROM THE SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved