Plan Review Details - Permit 20090339
Plan Review Stops For Permit 20090339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-28 Cont ID  
Sent By pvalenti Date 2020-11-28 Time 10:28 Rev Time 0.00
Received By pvalenti Date 2020-11-28 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:32 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:01 Sent To  
Notes
2020-10-03 10:35:54PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE
 SELECTION), THE LOCATION OF EXHAUST TERMINATION SHOULD
 BE INDICATED ON PLAN, MUST BE NO LESS THAN 10'
 HORIZONTALLY OR 3' ABOVE THE OPERABLE OPENINGS OF THE
 STRUCTURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By fgiaquin Date 2020-12-03 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2020-12-03 Time 21:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By jleahy Date 2020-09-29 Time 17:00 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 17:00 Sent To  
Notes
2020-09-29 17:07:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NE ELECTRICAL RISER SUBMITTED, 215.5
  
 SUBMIT RISER DIAGRAM FOR REVIEW

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By ccole Date 2020-11-20 Time 17:05 Rev Time 0.00
Received By ccole Date 2020-11-20 Time 17:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By ccole Date 2020-09-25 Time 16:34 Rev Time 0.00
Received By ccole Date 2020-09-25 Time 15:16 Sent To  
Notes
2020-09-25 16:34:281ST REVIEW FBC-2017 RES.
 PERMIT- 20090339
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 9018 LAKES
 BLVD. SHOW GAS PERMIT #99071571 ISSUED 9/17/1999 FOR
 INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS
 INDICATE A TOTAL LOAD OF 448,000 BTU'S: POOL HEATER-
 325,000. GRILL- 35,000. COOKTOP- 30,000. DRYER- 22,000.
 WATER HEATER- 36,000. REVISE THE RISER TO SHOW THE
 COMPLETE PIPING SYSTEM INCLUDING PIPE RUNS TO ALL NEW
 AND EXISTING APPLIANCES AND EQUIPMENT, AND SHOW THE
 CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM-
 SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE
 NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS
 INDICATED TO BE 60FT., AND THE POOL HEATER AND GRILL
 WERE LISTED AS OPTIONAL ON THE APPROVED PLAN. PLEASE
 VERIFY IN FIELD THAT THE APPLIANCES ARE INSTALLED
 BEFORE RESUBMITTING PLANS.
  
 A) REVISE THE DRAWING TO SHOW THE TOTAL LENGTH OF THE
 INTERIOR PIPING RUN AND THE TOTAL DEVELOPED LENGTH OF
 THE ENTIRE SYSTEM- SECTIONS G2413.4.1 AND G2413.4.2 FBC
 RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER
 TO INDICATE 870,000 BTUH.
  
 C) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION
 G2413.3 FBC RES. TABLE 402.4(3) FBC FG WITH A 3.0 IN.
 PRESSURE DROP LISTED ON THE PLANS IS NOT A SIZING TABLE
 FOUND IN THE FBC RES. TYPICALLY PRESSURE DROP IN
 RESIDENTIAL LOW PRESSURE SYSTEMS IS 0.5 IN. W.C. PLEASE
 REVIEW SECTION G2413.5 (402.5 ) ALLOWABLE PRESSURE DROP
 WHICH INDICATES:
 THE DESIGN PRESSURE LOSS IN ANY PIPING SYSTEM UNDER
 MAXIMUM PROBABLE FLOW CONDITIONS, FROM THE POINT OF
 DELIVERY TO THE INLET CONNECTION OF THE APPLIANCE,
 SHALL BE SUCH THAT THE SUPPLY PRESSURE AT THE APPLIANCE
 IS GREATER THAN OR EQUAL TO THE MINIMUM PRESSURE
 REQUIRED BY THE APPLIANCE.
  
 D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS
 G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH.
 INDICATE THE TABLES USED TO SIZE THE SCHEDULE 40
 METALLIC- SEE TABLES G2413.4(1)- G2413.4(8). PLEASE
 NOTE IF USING THE LONGEST LENGTH METHOD TO SIZE THE
 SCHED. 40 METALLIC, THE MAIN PIPE FROM THE METER TO THE
 1ST TEE, ACCORDING TO TABLE G2413.4(1) [402.4(2)] SHALL
 BE MINIMUM 1-1/2 IN. FOR A 754,000 BTUH LOAD AT 60 FT.
 DEVELOPED LENGTH.
  
 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5FT. AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA
 37, AND A MINIMUM OF 10 FT. FROM MECHANICAL OR GRAVITY
 AIR INTAKES (WINDOW AND DOOR OPENINGS) INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. CORRECT THE NOTES ON
 THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-21 Cont ID  
Sent By fgiaquin Date 2020-12-21 Time 11:21 Rev Time 0.00
Received By shill Date 2020-11-19 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-08 Cont ID  
Sent By lmarchan Date 2020-10-08 Time 06:55 Rev Time 0.00
Received By lmarchan Date 2020-09-14 Time 09:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-20 Cont ID  
Sent By ccole Date 2020-11-20 Time 17:06 Rev Time 0.00
Received By ccole Date 2020-11-20 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By ccole Date 2020-09-25 Time 16:37 Rev Time 0.00
Received By ccole Date 2020-09-25 Time 16:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-28 Cont ID  
Sent By pvalenti Date 2020-11-28 Time 10:29 Rev Time 0.00
Received By pvalenti Date 2020-11-28 Time 09:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-03 Cont ID  
Sent By pvalenti Date 2020-10-03 Time 10:31 Rev Time 0.00
Received By pvalenti Date 2020-10-03 Time 09:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-18 Cont ID  
Sent By kalexand Date 2020-12-18 Time 13:09 Rev Time 0.00
Received By kalexand Date 2020-12-18 Time 13:09 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-02 Cont ID  
Sent By kalexand Date 2020-10-02 Time 13:38 Rev Time 0.00
Received By kalexand Date 2020-10-02 Time 13:38 Sent To I
Notes
***NONE***