Plan Review Details - Permit 20090311
Plan Review Stops For Permit 20090311
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2020-09-30 Cont ID  
Sent By cpuell Date 2020-09-30 Time 09:37 Rev Time 0.00
Received By cpuell Date 2020-09-30 Time 09:37 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2020-09-09 Cont ID  
Sent By cpuell Date 2020-09-09 Time 10:03 Rev Time 0.00
Received By cpuell Date 2020-09-09 Time 10:03 Sent To  
Notes
2020-09-09 10:06:12WORKING ON ESTABLISHING IS ADDRESS IS 300 OR 350, SPOKE
 WITH APPLICANT MOST IMPORTANT THAT EDGE MASTER ASSN INC
 BE THE OWNERS

Review Stop AD ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2020-09-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By rmcdouga Date 2020-10-13 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2020-10-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By rmcdouga Date 2020-09-25 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2020-09-25 Time 07:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-18 Cont ID  
Sent By pleduc Date 2020-09-18 Time   Rev Time 0.00
Received By pleduc Date 2020-09-18 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By rmcdouga Date 2020-10-13 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2020-10-13 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-30 Cont ID  
Sent By rmcdouga Date 2020-09-30 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2020-09-16 Time 16:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-29 Cont ID  
Sent By jgomez Date 2020-10-29 Time 13:44 Rev Time 0.00
Received By jgomez Date 2020-10-29 Time 13:34 Sent To  
Notes
2020-10-29 13:46:04HARDCOPY STUCCO REPAIR DOCUMENTS WITH ENGINEER''S
 EMBOSSED SEAL AND ORIGINAL SIGNATURE SENT TO STORAGE.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-13 Cont ID  
Sent By rmcdouga Date 2020-10-13 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2020-10-13 Time 16:04 Sent To  
Notes
2020-10-13 16:48:25ALL OF THE DOCUMENTS FROM THE ENGINEER ARE NOT
 DIGITALLY SIGNED. THE THREE SECTION DRAWINGS ARE NOT
 DIGITALLY SIGNED BY THE ENGINEER. THE STUCCO REPAIR
 DOCUMENT IS NOT DIGITALLY SIGNED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By rmcdouga Date 2020-09-25 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2020-09-25 Time 07:00 Sent To  
Notes
2020-09-25 07:17:00ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
 THE SECTION DRAWINGS ARE NOT DIGITALLY SIGNED BY THE
 ENGINEER. THE ENGINEER'S DIGITAL SIGNATURE ON THE
 OVERHEAD PROTECTION PLAN IS SELF CERTIFIED BY THE
 ENGINEER. THE FBPE REQUIRES ENGINEER'S DIGITAL
 SIGNATURES TO BE CERTIFIED BY AN APPROVED THIRD PARTY.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By rmcdouga Date 2020-10-13 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2020-10-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By rmcdouga Date 2020-09-30 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2020-09-30 Time 10:24 Sent To  
Notes
2020-09-30 11:18:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FORMS THAT WERE SUBMITTED ARE OLDER AND HAVE
 BEEN REPLACED WITH UPDATED ONES. I WILL BE HAPPY TO
 EMAIL THE CURRENT FORMS IF YOU PROVIDE ME WITH YOUR
 EMAIL ADDRESS. FBC 107
  
 2) THE ADDRESS ON THE FORMS IS FOR 300 S. AUSTRALIAN
 AVE. AND THE ADDRESS ON THE PERMIT APPLICATION IS 350
 S. AUSTRALIAN AVE. PLEASE COORDINATE. FBC 107.2.1
  
 3) THE ADDRESS ON THE PLANS ARE ALSO REQUIRED TO MATCH
 THE OTHER PERMIT DOCUMENTS. FBC 107.2.1