Plan Review Details - Permit 20090291
Plan Review Stops For Permit 20090291
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 17:17 Rev Time 0.00
Received By lcrespo Date 2020-10-19 Time 17:17 Sent To  
Notes
2020-10-19 18:30:31010/19/20 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS IS A RESTAURANT AND IT REQUIRES A CHANGE OF
 OCCUPANCY. THERE IS NO APPLICATION OR PERMITS FOR THIS
 SCOPE OF WORK. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY
 THIS INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. A GREASE TRAP MAY BE REQUIRED ALONG WITH SIZING, A
 SEPARATE PERMIT AND APPLICATION WILL BE NEED IF SO 2017
 FBC P 1003.1.
  
 3. SUBMIT PLANS SHOWING THE LOCATION OF THE TANK-LESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 5. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC FG SEC. 304.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
  
 7. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE
 GAS SYSTEM OR PLACE A NOTE ON SET OF PLANS LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT
 WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC
 FG SEC. 402.3.
  
 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
  
 9. PROVIDE THE SIGNATURE OF ALL INFORMATION OF DATA
 SHALL BEAR THE PRINTED NAME OF THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 16:06 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 16:06 Sent To  
Notes
2020-09-16 16:07:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090291
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SPECIFICATION SHEETS PROVIDED FOR THE NEW
 COOKING EQUIPMENT IS GENERIC FOR DIFFERENT MODELS THE
 BTU?S VARY ACCORDINGLY. IDENTIFY THE MODEL USED IN THIS
 PROJECT ON EACH APPLIANCE SPECIFICATION PACKAGE. FBC FS
 107.2.1
  
 2) THE NEW TANKLESS WATER HEATER APPEARS TO BE
 INSTALLED OUTDOORS. PLEASE SHOW THE REGULATOR IS
 APPROVED FOR OUTDOOR INSTALLATION. FBC FG 410.1
  
 3) PLEASE SHOW HOW THE APPLIANCES WILL BE CONNECTED TO
 THE GAS SYSTEM. FBC FG 411.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 18:29 Rev Time 0.00
Received By lcrespo Date 2020-10-05 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-16 Cont ID  
Sent By abelisle Date 2020-09-16 Time 17:09 Rev Time 0.00
Received By abelisle Date 2020-09-15 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 17:54 Rev Time 0.00
Received By lcrespo Date 2020-10-19 Time 17:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-16 Cont ID  
Sent By abelisle Date 2020-09-16 Time 17:09 Rev Time 0.00
Received By abelisle Date 2020-09-16 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-09-16 Cont ID  
Sent By shill Date 2020-09-16 Time 11:40 Rev Time 0.00
Received By shill Date 2020-09-16 Time 11:40 Sent To  
Notes
***NONE***