Plan Review Details - Permit 20090271
Plan Review Stops For Permit 20090271
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By mcdouga Date 2020-11-04 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2020-11-03 Time 12:13 Sent To  
Notes
2020-11-04 07:25:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND SPEED FOR THIS PROJECT IS SPECIFIED AS 175
 MPH ON THE DRAWINGS AND CALCULATIONS. THE ACTUAL WIND
 SPEED IS 170 MPH VULT. USING THIS LOWER WIND SPEED
 SHOULD LOWER THE REQUIRED OPENING PRESSURES. FBC1609
  
 2) THE DESIGN PRESSURE CALCULATIONS USED ASCE 7-16.
 THIS EDITION OF ASCE IS NOT REFERENCED IN THE CURRENT
 CODE (2017 FBC). PLEASE USE ASCE 7-10 TO DETERMINE THE
 OPENING PRESSURES. FBC CHAPTER 35
  
 3) IN THE SCHEDULE ON SHEET A-1, THE COLUMN WITH THE
 PRESSURES REQUIRED FOR THE SPECIFIC OPENINGS DO NOT
 MATCH THE PRESSURES THAT ARE IN THE CLOUDED AREAS ON
 THE DETAILED ELEVATIONS. PLEASE COORDINATE. FBC 107.2
  
 4) THE POSITIVE PRESSURE IN THE CLOUDED AREA ON THE
 DETAILED ELEVATION FOR OPENING #7 IS +102.3 PSF AND THE
 PRESSURE IN THE SCHEDULE FROM THE PRODUCT APPROVAL IS
 +80 PSF. THIS DOES NOT MEET THE REQUIRED OPENING
 PRESSURE. PLEASE CORRECT. FBC 107.2 & 1609

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 10:45 Sent To  
Notes
2020-10-02 11:30:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY D.
 PLEASE REVISE DESIGN PARAMETERS ON SHEET A-1. FBC
 1609.4
  
 2) THE OPENING PRESSURES APPEAR TO BE LOW FOR A
 BUILDING IN EXPOSURE CATEGORY D WITH 170 MPH VULT WIND
 SPEED AND A ROOF HEIGHT OF 250'. SPECIFY THE WALL ZONE
 FOR EACH OF THE OPENINGS. PROVIDE THE CALCULATIONS THAT
 WERE USED TO DETERMINE THE OPENING PRESSURES OR THE
 WIND TUNNEL TEST REPORT. FBC 107 & 1609
  
 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT WINDOWS (GLASS
 TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 4) CIRCLE OR HI- LIGHT THE APPROPRIATE ITEMS (SUCH AS
 SIZE, GLASS TYPE, DESIGN PRESSURE, ETC.) IN THE PRODUCT
 APPROVAL FOR THE WINDOWS, DOORS AND MULLIONS. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2020-11-13 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-04 Cont ID  
Sent By rmcdouga Date 2020-11-04 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2020-10-28 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 10:45 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved