Plan Review Details - Permit 20090208
Plan Review Stops For Permit 20090208
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By medwards Date 2020-09-17 Time 11:53 Rev Time 0.00
Received By medwards Date 2020-09-17 Time 11:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By medwards Date 2020-09-12 Time 09:02 Rev Time 0.00
Received By medwards Date 2020-09-12 Time 09:02 Sent To  
Notes
2020-09-12 09:02:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090208
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW ON DRAWING THE METHOD USED TO SIZE THIS
 NATURAL GAS SYSTEM. FBC FG 402.4
  
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017
 FBC RES. SEC. G2408.1.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 4) PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 5) SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC FG SEC.304.9.3 OR 2017 FBC RES. SEC. G2407.9.3.
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 7) GAS TABLE NUMBER IN PARENTHESIS FOR THE 12?
 W.C./INTERIOR IS BLURRED AND I CAN?T READ IT. PLEASE
 REWRITE THIS NUMBER. FBC FS 107.2.1
  
  
 8) PLEASE CHECK THE TABLES USED FOR THE 12? W.C.
 INTERIOR PIPING TABLE 402.4 (17) IS FOR NATURAL GAS;
 LESS THAN 2 PSI; PRESSURE DROP 6.0IN W.C.; SPECIFIC
 GRAVITY 0.60. PLEASE MAKE SURE THE PRESSURE DROP IS THE
 SAME FOR EACH TABLE FOR EACH MATERIAL USED. FBC FG 402
  
 9) PLEASE SHOW OUTLET PRESSURES FOR EACH MP REGULATOR
 IN THIS SYSTEM. FBC FG 410.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-16 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-14 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-10 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-09-18 Cont ID  
Sent By ccole Date 2020-09-17 Time 17:24 Rev Time 0.00
Received By ccole Date 2020-09-17 Time 17:13 Sent To  
Notes
2020-09-17 17:30:22PLUMBING APPROVED UNDER MASTER PERMIT- 20030956
 CCOLE- 9/17/2020
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By ccole Date 2020-09-14 Time 11:04 Rev Time 0.00
Received By ccole Date 2020-09-14 Time 10:00 Sent To  
Notes
2020-09-14 11:05:19 
 1ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20090208
 9/14/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
  
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
  
 FS- FLORIDA STATUTES
  
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE NEW TANKLESS WATER HEATER
 SUPPLYING THE CABANA FIXTURES- SECTION G2448.1 M2005.1
 FBC RES. THE SPECS SHALL INDICATE THE HOT WATER GPM
 CAPACITY OF THE UNIT BASED ON THE MANUFACTURER?S
 TEMPERATURE RISE CHART; AND SHALL SHOW THE EFFICIENCY
 RATING OF THE UNIT- SEE TABLE C404.2 FBC EC. PLEASE
 INCLUDE A LIST OF FIXTURES TO BE SUPPLIED BY THE WATER
 HEATER.
  
 2) PROVIDE A BASIC ELEVATION PLAN DETAIL SHOWING THE
 MOUNTING LOCATION OF THE WATER HEATER AND CLEARANCE
 DISTANCES FROM GRADE, OVERHEAD CONSTRUCTION, AND
 OPERABLE OPENINGS INTO THE BUILDING- SECTION G2448.1.
 PROVIDE A NOTE OR DETAIL TO INDICATE THAT CONDENSATE
 FOR THE HEATER WILL DISCHARGE A MINIMUM OF 1FT. FROM
 THE BUILDING- SECTION R318.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
  
 MECHANICAL/PLUMBING PLANS EXAMINER
  
 401 CLEMATIS STREET
  
 WEST PALM BEACH FL 33401
  
 561-805-6719
  
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By medwards Date 2020-09-17 Time 12:05 Rev Time 0.00
Received By medwards Date 2020-09-17 Time 12:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By medwards Date 2020-09-12 Time 09:05 Rev Time 0.00
Received By medwards Date 2020-09-12 Time 09:04 Sent To  
Notes
2020-09-12 09:05:45PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  