Plan Review Details - Permit 20090166
Plan Review Stops For Permit 20090166
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By lcrespo Date 2020-09-15 Time 06:53 Rev Time 0.00
Received By lcrespo Date 2020-09-15 Time 06:53 Sent To  
Notes
2020-09-15 06:54:3609/11/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:26 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 09:26 Sent To  
Notes
2020-09-08 09:28:3009/08/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE COOK TO NEED TO BE FULL LOAD, IT IS LABELED AT
 18 BTU'S AND THERE IS 6 BURNERS AND A GRILL EACH AT 18
 X 7 EQUALS 126 BTU'S PLEASE CHANGE AND RECALCULATE FOR
 SIZING IF NEEDED PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE LABEL THE TYPE OF PIPE MATERIAL BEING
 INSTALLED AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 6. POOL HEATER IS MISSED LABELED AT 440 BTU'S AND SPECS
 SAYS 400 BTU'S PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR (DRYER SHOW
 LOCATION, IF IN CLOSET ARE LOUVER BEING USED, AND
 RANGE) GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED
 BY THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE
 SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE
 IN ADDITION TO THE REQUIRED VENTILATION AIR PER THE
 2017 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR
 AND VENTILATION AIR SYSTEM.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 9. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) FOR THE TANKLESS HEATER
 INSIDE PER THE 2017 FBC RES. SECS. G2426 THRU G2429.1.
  
 11. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER
 A ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 12. IF THE GAS GRILL IS IN A COVERED PATIO, AND A HOOD
 IS REQUIRED A SEPARATE PERMIT FOR THE HOOD IS REQUIRED
 PLEASE NOT ON PLANS PER THE 2017 FBC RES. SEC. G2408.1.
  
 13. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2.
  
 14. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 15. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED,
 EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER
 THE 2017 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 16. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND
 LABELED PER THE 2017 FBC FG RES. SEC. G2404.3. THE
 MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT
 ARE BEING EXHAUSTED BY THE DRYER.
  
 17. ON THE HOUSE PLAN SHOW THE LOCATION OF THE TANKLESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By lcrespo Date 2020-09-15 Time 07:49 Rev Time 0.00
Received By lcrespo Date 2020-09-14 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:26 Rev Time 0.00
Received By lcrespo Date 2020-09-03 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-09-15 Cont ID  
Sent By lcrespo Date 2020-09-15 Time 06:54 Rev Time 0.00
Received By lcrespo Date 2020-09-15 Time 06:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:26 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:26 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 09:26 Sent To  
Notes
***NONE***