Plan Review Details - Permit 20090118
Plan Review Stops For Permit 20090118
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-10-15 Cont ID  
Sent By jwitmer Date 2020-10-15 Time 08:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-10-14 13:10:09ASBESTOS FORM UPLOADED IN PROJECTDOX. CC

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By jwitmer Date 2020-10-05 Time 16:07 Rev Time 0.00
Received By jwitmer Date 2020-10-05 Time 14:17 Sent To  
Notes
2020-10-05 16:06:36COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By jwitmer Date 2020-09-14 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2020-09-14 Time 08:41 Sent To  
Notes
2020-09-14 10:46:58COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:44
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-05 Cont ID  
Sent By jwitmer Date 2020-10-05 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2020-10-05 Time 14:17 Sent To  
Notes
2020-10-05 15:55:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090118
 ADD: 4847 DAVID S MACK DR.
 CONT: IBIS BUILDING CORP.
 TEL: 561-568-2570
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT.05TH/2020
 ACTION: BUILDING PROVISO
 1) LIFE SAFETY SHEETS LS1 & LS2.RESPONSE STEPHEN BORUFF
 AIA. THE PLAN SYMBOL FOR THE DOORS IN QUESTION MAYBE A
 BIT MISLEADING. THESE DOORS SWING INTO THE CENTRAL
 BATHING ROOM, BUT THEY WILL BE FITTED WITH RESCUE
 ASSISTANCE HARDWARE TO ALLOW MEDICAL STAFF TO OPEN THE
 DOOR OUT IN THE RARE EVENT A USER NEEDS ASSISTANCE AND
 ANY OBSTRUCTION PREVENTS THE DOOR FROM SWINGING IN.
 THIS WOULD ONLY OCCUR IN A RARE, TEMPORARY EMERGENCY.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By jwitmer Date 2020-09-14 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2020-09-14 Time 08:40 Sent To  
Notes
2020-09-14 10:45:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090118
 ADD: 4847 DAVID S MACK DR.
 CONT: IBIS BUILDING CORP.
 TEL: 561-568-2570
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT. 14TH/2020
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET 1 & 2 FOR FLOORS 1, 2, 3 & 4
 THE DOUBLE DOORS FROM SMOKE COMPARTMENT M AND THE
 NURSES CENTRAL STATION AND CENTRAL BATHING STATION ARE
 IN CONFLICT WITH EACH OTHER. ON ALL 4 FLOORS THE
 CENTRAL BATHING STATION SHOWS A DOUBLE ACTING PIVOT
 DOOR THAT SWINGS INTO THE SMOKE COMPARTMENT EGRESS
 DOORS. PLEASE REVIEW THE 017 FBC-B SECTION 1005.7.1.
 DOORS, WHEN FULLY OPEN, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES. DOORS IN ANY POSITION
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN
 ONE-HALF.
 2) SHEET A4 SHOWS IN ALL THE CENTRAL BATHING FACILITIES
 GYPSUM WALL BOARD AND EPOXY PAINT. PLEASE REVIEW 2017
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN
 RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE. WALLS & PARTITIONS WITHIN
 2 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT
 FOR STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH
 WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED
 BY MOISTURE.
  
  
 2B) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 2C) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 2D) SHEET A5 DETAIL P-3 INDICATES WITH A NOTE THAT THE
 SHOWER WATERPROOFING BUILDING PANEL SYSTEM PER
 MANUFACTURERS RECOMMENDATIONS. NO PRODUCT INFORMATION
 WAS SUBMITTED THIS REVIEW. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By jleahy Date 2020-10-01 Time 14:47 Rev Time 0.00
Received By jleahy Date 2020-10-01 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-03 Cont ID  
Sent By jleahy Date 2020-09-03 Time 13:34 Rev Time 0.00
Received By jleahy Date 2020-09-03 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By pdeluc Date 2020-10-06 Time   Rev Time 0.00
Received By pleduc Date 2020-10-06 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By pleduc Date 2020-09-03 Time   Rev Time 0.00
Received By pleduc Date 2020-09-03 Time 12:26 Sent To  
Notes
2020-09-03 12:34:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEETS A 1.1 & 1.2 - DOORS N 185, 285, 385 AND 485
 ARE INDICATING THAT THEY OPEN BOTH INSWING AND OUTSWING
 INTO THE EXIT CORRIDOR. THESE DOUBLE SMOKE PARTITION
 DOORS ARE DIRECTLY OUSIDE THESE DOORS WITH THE DOOR
 CLOSET TO THIS NEW SPACE OPENING INTO THE EXIT TRAVEL
 PATH ON THE SIDE OF THE CORRIDOR. THE BATH DOOR OPEN
 INTO THAT EXIT TRAVEL PATH AND ENCROACHES ON THE EGRESS
 WIDTH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 BECAUSE THE EGRESS PATH OF THE CORRIDOR IS ON THE SAME
 SIDE OF THE BATH DOOR THAT OPENS INTO THE CORRIDOR, IT
 RESTRICTS THE EGRESS WITH. A PERSON CAN NOT OPEN THE
 OTHER CORRIDOR DOOR IN THAT PATH OF TRAVEL.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRTIVE.
  
  
  
  
 2) THERE ARE NO INDICATIONS OF FIRE DEVICES WITHIN THE
 ROOMS. FIRE ALARM DEVICES ARE REQUIRED WITHIN THE ROOMS
 AS THERE ARE NOW OCCUPIABLE BY THE GENRAL PUBLIC.
  
 PER NFPA 101, CH 33
  
 33.3.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
  
 33.3.3.4.4 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION
 SHALL BE
 PROVIDED AUTOMATICALLY, WITHOUT DELAY, BY INTERNAL
 AUDIBLE ALARM
 IN ACCORDANCE WITH 9.6.3.
  
 9.6.3 OCCUPANT NOTIFICATION.
 9.6.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED TO
 ALERT OCCUPANTS
 OF A FIRE OR OTHER EMERGENCY WHERE REQUIRED BY OTHER
 SECTIONS OF
 THIS CODE.
  
 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH
 9.6.3.5.8,
 NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE
 AUDIBLE, AND
 VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM
 AND SIGNALING CODE.
  
 THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 PLEASE CORRECT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-15 Cont ID  
Sent By jwitmer Date 2020-10-15 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2020-10-14 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-07 Cont ID  
Sent By jwitmer Date 2020-10-07 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2020-09-30 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-22 Cont ID  
Sent By lmarchan Date 2020-09-22 Time 07:58 Rev Time 0.00
Received By ccarvaja Date 2020-09-30 Time 08:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-09-07 Cont ID  
Sent By medwards Date 2020-09-07 Time 09:54 Rev Time 0.00
Received By medwards Date 2020-09-07 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-05 Cont ID  
Sent By lcrespo Date 2020-10-05 Time 16:17 Rev Time 0.00
Received By lcrespo Date 2020-10-05 Time 16:17 Sent To  
Notes
2020-10-05 16:18:0110/05/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By lcrespo Date 2020-09-17 Time 15:21 Rev Time 0.00
Received By lcrespo Date 2020-09-10 Time 14:40 Sent To  
Notes
2020-09-17 15:19:0009/17/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE STATE THE OCCUPANCY TYPE AND AS TO WHY THERE
 IS ONLY ONE ACCESSIBLE TOILET RESTROOM, SO PLEASE SITE
 THE APPLICABLE CODE SECTION THAT ALLOWS ONLY ONE.
  
 2. ON THE SHEETS ADA 1.0 AND 1.1 PLEASE DELETE WATER
 FOUNTAIN AND ANY OTHER PLUMBING DETAILS THAT DO NOT
 PURITAN TO THIS PROJECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON THE SHEET, A-3 THE LAUNDRY ROOM SHOWS THREE
 WASHING MACHINES AND ON ISOMETRIC, THERE ARE TWO SHOWN
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE LAUNDRY ROOM REQUIRES A LINT TRAP PER THE 2017
 FBC SEC. P 1003.6, PLEASE PROVIDE SPECIFICATION AND OR
 DETAIL ON PLANS.
  
 5. PLEASE SHOW THE LOCATION OF LAUNDRY VALVES THAT
 SHALL ACCESSIBLE WITHOUT MOVING UNITS PER THE 2017 FBC
 SEC. 606.3 ACCESS TO VALVES.
  
 6. ON THE SHEET, P 3.1 PLEASE PROVIDE A WATER RISER FOR
 THE LAUNDRY ROOM ON ISOMETRIC RISER PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE NOTE THAT IS USING A
 COMMERCIAL MACHINE THEY MAY REQUIRE A 3/4" INCH SUPPLY
 PER MANUFACTURE SPECIFICATION.
  
 7. ON SHEET A-3 PLEASE GIVE THE DIMENSION'S ACCESSIBLE
 CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM PER THE 2017 FBC
 ACC SEC. 611.
  
 8. ON THE SHEET, A-3 DETAIL 2/A-3 THE SHOWER GRAB BARS
 SHALL BE 36" TO TOP OF THE BAR PER THE 2017 ACC SEC.
 609.4.
  
 9. ON THE SHEET, A-3 PLEASE SHOW THE HEIGHT OF THE
 SPRAY UNIT PER THE 2017 FBC ACC. SEC. 608.6.
  
 10. ON THE SHEET, A-3 PLEASE SHOW FLOOR SPACE FOR
 SHOWER AND GIVE DEMISSION FOR ALL CLEAR FLOOR SPACE ON
 ALL ACCESSIBILITY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. ON THE SHEET, P 3.1 THE ISOMETRIC FOR THE DISCHARGE
 OF THE WASHING MACHINE SHOWS A DOUBLE SANITARY TEE
 PATTERN THIS IS NOT ALLOWED PER THE 2017 FBC SEC.
 706.3.
  
 12. ON SHEET P 3.1 FOR P-2 RISER IS PRESENT ANT IT
 REPRESENTS N-143 AND N-171 BUT THESE BATHROOM GROUPS
 ARE MISSING THE LAVS AND SHOWER WATER AND SANITARY
 RISER DIAGRAMS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13. ON THE SHEET, A1.1 FOR ACCESSIBLE CLEAR FLOOR SPACE
 OF THE SHOWER IS MISSING PLEASE SHOW ON ALL PAGES (
 A1.2, A 2.1 AND A2.2 ) PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. ON THE SHEET, P 3.1 PLEASE REFER TABLE 906.1 ON THE
 VENT FOR P-3 AND RECALCULATE TOTAL FIXTURE UNITS FOR 2"
 VENT AS IT MAY NEED TO BE INCREASED IF A THIRD WASHING
 MACHINE IS ADDED PER 2017 FBC SEC. P 906.
  
 15. ON THE SHEET, P 3.1 FOR EVERY TIME THAT WATER GOES
 INTO A UNIT FROM A WATER RISER WITH A VALVE THAT IS
 ACCESSIBLE SHALL BE FULLY OPEN PER THE 2017 FBC SEC. P
 606.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By jwitmer Date 2020-10-07 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2020-10-07 Time 09:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 07:45 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 07:16 Sent To  
Notes
2020-09-22 07:46:23THE DESIGNER MUST DIGITALLY SIGN AND SEAL THE ADA
 SHEETS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By eschneid Date 2020-09-21 Time 15:52 Rev Time 0.25
Received By eschneid Date 2020-09-21 Time 15:44 Sent To  
Notes
2020-09-21 15:53:30INTERIOR WORK ONLY. NO ADDITIONAL UNITS/BEDS.