Plan Review Details - Permit 20090076
Plan Review Stops For Permit 20090076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-09 Cont ID  
Sent By rmcphers Date 2020-10-09 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2020-10-09 Time 13:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By rmcphers Date 2020-09-25 Time 07:52 Rev Time 0.00
Received By rmcphers Date 2020-09-25 Time 07:51 Sent To  
Notes
2020-09-25 08:59:32DOOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE STRUCTURAL CALCULATIONS TO DETERMINE
 THE OPENING REQUIRED WIND DESIGN PRESSURES OR PROVIDE
 SIGNED AND SEALED WIND DESIGN PRESSURES FOR THE OPENING
 FROM AN ARCHITECT OR ENGINEER FBC 1609.1.1 (RISK
 CATEGORY IV BUILDING - 180MPH WIND SPEEDS)
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By rmcphers Date 2020-09-25 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 14:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-10-09 Cont ID  
Sent By rmcphers Date 2020-10-09 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2020-10-09 Time 13:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By rmcphers Date 2020-09-25 Time 07:52 Rev Time 0.00
Received By rmcphers Date 2020-09-25 Time 07:52 Sent To  
Notes
2020-09-25 09:01:17SEE BUILDING PLAN REVIEW