Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By pleduc Date 2020-09-08 Time   Rev Time 0.00
Received By pleduc Date 2020-09-08 Time 10:47 Sent To  
Notes
2020-09-08 11:00:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FOLLOWING CODE REFERENCE ON SHEET 1 OF 3 DOES
 NOT APPLY: 25.2.1.6 MODIFICATIONS THAT CANNOT BE
 ISOLATED, SUCH AS RELOCATED DROPS, SHALL NOT REQUIRE
 TESTING IN EXCESS OF SYSTEM WORKING PRESSURE.
  
 PER NFPA 13
  
 25.2 ACCEPTANCE REQUIREMENTS.
  
 25.2.1* HYDROSTATIC TESTS.
  
 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
  
 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
  
  
 PLEASE ENSURE COMPLIANCE AND REQUIRED TESTING P.S.I.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-08 Cont ID  
Sent By ccarvaja Date 2020-09-08 Time 14:32 Rev Time 0.00
Received By ccarvaja Date 2020-09-04 Time 13:40 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved