2020-09-24 16:56:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQIUIRED TO BE A MINIMUM
 OF 10' FROM OPENINGS INTO A BUILDING. FBC M501.3

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By cthroop Date 2020-09-08 Time 13:57 Rev Time 0.00
Received By cthroop Date 2020-09-08 Time 13:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 14:52 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 13:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-14 Cont ID  
Sent By ccole Date 2020-10-14 Time 09:02 Rev Time 0.00
Received By ccole Date 2020-10-14 Time 07:40 Sent To  
Notes
2020-10-14 09:03:052ND REVIEW FBC-2017 RES.
 PERMIT- 20090066
 10/14/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 A REVISED GAS RISER DRAWING WAS NOT SUBMITTED. COMMENTS
 LISTED BELOW WERE NOT ADDRESSED.
  
 1) GAS ISOMETRIC DRAWING:
 A) THE SPECS SUBMITTED FOR THE GENERATOR INDICATE
 327,000 BTUH AT FULL LOAD. PLEASE NOTE THE UPDATED
 SPECS FOR GENERAC 22KW GENERATORS ARE LISTED AT 306
 BTUH AT FULL LOAD- SECTION G2413.2 FBC RES. AND SECTION
 107.2.1 WPB.
 B) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 C) PROVIDE THE EHD OF THE 3/4"TRAC PIPE- TABLE
 G2413.4(6) [402.4(18)]
 D) INDICATE ON THE RISER WHICH B42 REGULATOR MODEL WILL
 BE INSTALLED- MODEL R, N, OR H AND SUBMIT HIGHLIGHTED
 OR MARKED UP SPEC SHEETS SHOWING THE MAX INLET AND
 OUTLET SIZE AND PRESSURES, SPRING DATA, AND ORIFICE
 SIZE- SECTION G2421.1 & G2421.2.
 E) SHOW THE SHUTOFF VALVE FOR THE GAS SUPPLY TO THE
 GENERATOR, AND THE REQUIRED PIPE UNIONS AT THE
 REGULATOR- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 F) SHOW THE LOCATION OF THE DRIP LEG AT THE GENERATOR-
 SECTION G2419.2.
 2) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL
 BE ON THE RISER DRAWING- SECTION 107.2.1 WPB, AND
 FL.STATUTES 471.003(2) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By ccole Date 2020-09-15 Time 14:56 Rev Time 0.00
Received By ccole Date 2020-09-15 Time 13:31 Sent To  
Notes
2020-09-15 14:56:211ST REVIEW FBC-2017 RES.
 PERMIT- 20090066
 9/15/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
 A) THE SPECS SUBMITTED FOR THE GENERATOR INDICATE
 327,000 BTUH AT FULL LOAD. PLEASE NOTE THE UPDATED
 SPECS FOR GENERAC 22KW GENERATORS ARE LISTED AT 306
 BTUH AT FULL LOAD- SECTION G2413.2 FBC RES. AND SECTION
 107.2.1 WPB.
 B) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 C) PROVIDE THE EHD OF THE 3/4"TRAC PIPE- TABLE
 G2413.4(6) [402.4(18)]
 D) INDICATE ON THE RISER WHICH B42 REGULATOR MODEL WILL
 BE INSTALLED- MODEL R, N, OR H AND SUBMIT HIGHLIGHTED
 OR MARKED UP SPEC SHEETS SHOWING THE MAX INLET AND
 OUTLET SIZE AND PRESSURES, SPRING DATA, SPRING COLOR
 OUTLET PRESSURE RANGE AND ORIFICE SIZE- SECTION G2421.1
 & G2421.2.
 E) SHOW THE SHUTOFF VALVE FOR THE GAS SUPPLY TO THE
 GENERATOR, AND THE REQUIRED PIPE UNION AT THE
 REGULATOR- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
 G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 FLEX CONNECTOR AND TO THE SCHEDULE 40 METALLIC PIPE PER
 SECTIONS G2415.17.1 & G2415.17.2. PLEASE NOTE THAT
 SPECS FOR ANODELESS RISERS AND PE/METALLIC PIPE
 CONNECTORS SHALL BE LISTED AND LABELED.
 I) SHOW THE LOCATION OF THE DRIP LEG AT THE GENERATOR-
 SECTION G2419.2.
  
 2) PLEASE SUBMIT INSTALLATION GUIDELINES FROM GENERAC
 TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE SURVEY ARE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS- SECTION G2406.2 FBC RES.
  
 3) PLEASE PROVIDE A TITLE BLOCK WITH THE SIGNATURE ON
 THE DRAWING TO CLEARLY INDICATE THE LICENSED CONTRACTOR
 OR QUALIFIERS NAME AND LICENSE NUMBER- SECTION 107.2.1
 WPB.
  
 4) A SUB-PERMIT FOR THE GAS PIPING INSTALLATION IS
 REQUIRED- SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 10:37 Rev Time 0.00
Received By jleahy Date 2020-11-18 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-27 Cont ID  
Sent By rmcdouga Date 2020-10-27 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2020-10-13 Time 13:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2020-09-04 Time 07:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 14:52 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-14 Cont ID  
Sent By ccole Date 2020-10-14 Time 09:06 Rev Time 0.00
Received By ccole Date 2020-10-14 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By ccole Date 2020-09-15 Time 14:58 Rev Time 0.00
Received By ccole Date 2020-09-15 Time 13:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-27 Cont ID  
Sent By rmcdouga Date 2020-10-27 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2020-10-27 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 16:54 Sent To  
Notes
2020-09-08 14:06:01VERIFIED CONTRACTORS SIGNATURE ON ELECTRIC RISER AND
 LOAD CALC'S. CT

Review Stop Z ZONING
Rev No 3 Status P Date 2020-12-02 Cont ID  
Sent By rthermid Date 2020-12-02 Time   Rev Time 0.00
Received By rthermid Date 2020-12-02 Time   Sent To I
Notes
2020-12-02 11:47:50PASSED WITH A PROVISO
  
 GENERATOR MUST BE SETBACK A MINIMUM OF 11 FEET FROM THE
 REAR PROPERTY LINE AS MECHANICAL CANNOT ENCROACH MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By rthermid Date 2020-10-20 Time   Rev Time 0.00
Received By rthermid Date 2020-10-20 Time   Sent To I
Notes
2020-10-20 09:25:40PROVISO -
 THE PROPOSED GENERATOR MUST BE SETBACK A MINIMUM OF 11
 FEET FROM THE REAR PROPERTY LINE

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By rthermid Date 2020-09-15 Time   Rev Time  
Received By rthermid Date 2020-09-15 Time   Sent To I
Notes
2020-09-15 08:23:37ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/15/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED GENERATOR IS IN THE FRONT SETBACK; IT
 ALSO ENCROACHES MORE THAN 4 FEET INTO A REQUIRED
 SETBACK. PURSUANT THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved