Plan Review Details - Permit 20090061
Plan Review Stops For Permit 20090061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 13:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 15:55 Sent To  
Notes
2020-09-24 16:00:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS INTO A BUILDING AND THE SURVEY SHOWS THE
 GENERATOR IS 5' FROM OPENINGS. FBC-M501.3.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By cthroop Date 2020-09-08 Time 14:00 Rev Time 0.00
Received By cthroop Date 2020-09-08 Time 13:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 15:13 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 15:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By ccole Date 2020-09-14 Time 17:15 Rev Time 0.00
Received By ccole Date 2020-09-14 Time 15:00 Sent To  
Notes
2020-09-14 17:15:581ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090061
 9/14/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER DRAWING AND SURVEY INDICATE AN
 EXISTING 500-GALLON LP TANK. I HAVE RESEARCHED THE
 BUILDING DEPARTMENT RECORDS AND I CANNOT LOCATE A
 PERMIT OR PLANS FOR THE TANK. AT THIS TIME THE TANK
 WILL BE REVIEWED AS A NEW INSTALLATION PENDING EVIDENCE
 IS PROVIDED TO INDICATE IT WAS PERMITTED AND INSPECTED
 BY THE WPB BUILDING DEPARTMENT- SECTION 1005.1 &
 107.2.1 WPB AMENDMENTS TO THE FBC-17.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LP TANK
 SHOWING THE TANK MEETS THE CURRENT TESTING, LISTING AND
 COMPLIANCE STANDARDS IN ACCORDANCE WITH SECTION 5.2.1.1
 NFPA 58.
  
 3) PROVIDE A SURVEY DRAWING MARKED UP TO SHOW THE
 REQUIRED 10 FT. UG TANK CLEARANCE DISTANCES TO THE
 HOUSE AND ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA
 58. PLEASE NOTE THAT IF THE TANK IS LESS THAN 10 FT.
 FROM THE DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18
 IN. BELOW GRADE OR VEHICULAR BARRIER PROTECTION WILL BE
 REQUIRED- SECTIONS 6.6.6.1 (A). (PLEASE NOTE THE
 SUBMITTED SURVEY COPY FOR A RESIDENCE ON SOUTHWICK WAY
 APPEARS TO BE SUBMITTED IN ERROR.)
  
 4) THE GAS RISER DRAWING SHOWS AN INCOMPLETE ANCHORING
 DETAIL FOR THE TANK. PLEASE PROVIDE ENGINEERING FOR
 ANCHORING THE TANK TO PREVENT FLOTATION, COLLAPSE, OR
 LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA 58. INCLUDE A
 FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE BURIAL
 DEPTH, TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS.
  
 5) THE TANK SHALL BE PROTECTED AGAINST CORROSION BY
 INSTALLATION OF A CATHODIC PROTECTION SYSTEM CONSISTING
 OF A SACRIFICIAL ANODE OR AN IMPRESSED CURRENT ANODE
 PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA 58. INDICATE
 THE TYPE OF PROTECTION AND HOW IT WILL BE TESTED-
 SECTION 6.17.1 NFPA 58.
  
 6) GAS ISOMETRIC DRAWING:
 A) INDICATE THE PE PIPE SIZING TABLE ON THE DRAWING-
 SEE TABLES G2413.4(1)- G2413.4(8) FBC RES.
 B) INDICATE THE MAKES AND MODELS OF THE REGULATORS ON
 THE DRAWING AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 MARKED UP TO SHOW THE INLET AND OUTLET SIZES AND
 PRESSURES, AND ORIFICE SIZES- SECTION G2421.1 & G2421.2
 FBC RES.
 C) SHOW THE SHUTOFF VALVE FOR THE GAS SUPPLY TO THE
 GENERATOR, AND THE REQUIRED PIPE UNION AT THE
 REGULATOR- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 D) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
 E) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3
 F) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 FLEX CONNECTOR OR METALLIC PIPE PER SECTIONS G2415.17.1
 & G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS
 RISERS AND PE/METALLIC PIPE CONNECTORS SHALL BE LISTED
 AND LABELED.
 G) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 7) AS NOTED ABOVE AN INCORRECT SURVEY DRAWING HAS BEEN
 SUBMITTED. PLEASE PROVIDE THE LOCATION OF THE GENERATOR
 ON THE RE-SUBMITTED SURVEY WITH CLEARANCE DISTANCES TO
 THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND
 THE ADJACENT PROPERTY LINES- SECTION 107.2.1 WPB.
 PLEASE ALSO SUBMIT INSTALLATION GUIDELINES FROM GENERAC
 TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE SURVEY.
  
 8) PLEASE PROVIDE A TITLE BLOCK WITH THE SIGNATURE ON
 THE DRAWING TO CLEARLY INDICATE THE LICENSED CONTRACTOR
 OR QUALIFIERS NAME AND LICENSE NUMBER- SECTION 107.2.1
 WPB.
  
 9) A SUB-PERMIT FOR THE LP TANK AND GAS PIPING
 INSTALLATIONS IS REQUIRED- SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 10:45 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-08 Cont ID  
Sent By shill Date 2020-10-08 Time 08:36 Rev Time 0.00
Received By shill Date 2020-09-04 Time 07:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 15:13 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-14 Cont ID  
Sent By ccole Date 2020-09-14 Time 17:16 Rev Time 0.00
Received By ccole Date 2020-09-14 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 13:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 15:56 Sent To  
Notes
2020-09-08 14:04:44VERIFIED CONTRACTORS SIGNATURE ON ELECTRICAL RISER AND
 LOAD CALC'S. CT

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By rthermid Date 2020-11-23 Time   Rev Time 0.00
Received By rthermid Date 2020-11-23 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By rthermid Date 2020-10-07 Time   Rev Time  
Received By rthermid Date 2020-10-07 Time   Sent To I
Notes
2020-10-07 07:31:33ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10/07/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. BASED ON THE DRAWING, THE GENERATOR IS LOCATED 3
 FEET FROM THE PROPERTY LINE. PURSUANT TO THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
 THE GENERATOR MUST BE SETBACK A MINIMUM OF 3.5 FEET
 FROM THE SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH