Plan Review Details - Permit 20090017
Plan Review Stops For Permit 20090017
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 14:50 Rev Time 0.00
Received By jleahy Date 2020-10-13 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 11:54 Rev Time 0.00
Received By jleahy Date 2020-09-15 Time 11:54 Sent To  
Notes
2020-09-15 11:56:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SHOW WHERE POWER COMES FROM, LOCATION OF METER, PANEL,
 OR DISTRIBUTION AND DISTANCE TO ROOF. 215.5
  
 NEED TO DO AN AIC RATING CALCULATION 110.9,110,10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 14:51 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 12:04 Rev Time 0.00
Received By jleahy Date 2020-09-01 Time 13:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 14:50 Rev Time 0.00
Received By jleahy Date 2020-10-13 Time 14:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 12:03 Rev Time 0.00
Received By jleahy Date 2020-09-15 Time 12:03 Sent To  
Notes
2020-09-15 12:03:55NO PLAN SUBMITTED JLEAHY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved