2020-10-19 15:56:52 | PLAN REVIEW GENERATOR / BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE CURRENT GENERATOR SPECIFICATIONS FOR |
| PROPOSED 22KW GENERATOR. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE SITE WIND DESIGN REQUIREMENTS. INCLUDE VULT, |
| VASD, RISK CATEGORY AND EXPOSURE CATEGORY. |
| FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 3. PROVIDE WIND DESIGN PRESSURES FOR PROPOSED |
| GENERATOR. |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4) OR ASCE 7-10. |
| |
| 4. CAST-IN-PLACE PAD THICKNESS FROM TABLE ON PG. E3 |
| STATES 4 INCHES. PAD THICKNESS ON GENERATOR PAD DETAIL |
| STATES 6 INCHES. |
| PLEASE CLARIFY. |
| |
| 5. BOLT DIAMETER ON GENERATOR PAD DETAIL STATES 5-1/2". |
| PLEASE CLARIFY. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |