Plan Review Stops For Permit 20090001 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-01-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-01-20 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-01-20 |
Time |
11:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-21 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-21 |
Time |
16:16 |
Sent To |
|
|
Notes |
2020-10-21 16:37:25 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT SIGNED AND SEALED ENGINEERED DRAWINGS FOR THE | | PRE-FAB GENERATOR PAD WITH GENERATOR TO PAD ANCHORING | | DETAILS. FBC 107.2.1 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-02-23 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-02-23 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2021-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-01-28 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-01-28 |
Time |
13:15 |
Sent To |
|
|
Notes |
2021-01-28 13:20:06 | SEE COMMENTS FROM ORIGINAL REVIEW JLEAHY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-21 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-21 |
Time |
14:57 |
Sent To |
|
|
Notes |
2020-10-21 15:02:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | PLAN SHOWS 2/0 WHERE IT IS NOT FEEDING THE ENTIRE LOAD. | | | | 120/240-VOLT, SINGLE-PHASE DWE LLING SERVICES AND | | FEEDERS. FOR ONE-FAMILY DWELLINGS AND THE INDIVIDUAL | | DWELLING UNITS OF TWO-FAMILY AND MULTIFAMILY DWELLINGS, | | SERVICE AND FEEDER CONDUCTORS SUPPLIED BY A | | SINGLE-PHASE, 120/240-VOLT SYSTEM SHALL BE PERMITTED BE | | SIZED IN ACCORDANCE WITH 310.15(B)(7) (1) THROUGH (4). | | | | (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS | | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL | | DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, | | SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 | | PERCENT OF THE SERVICE RATING | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2021-04-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-23 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-22 |
Time |
16:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2021-02-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-02-22 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-02-22 |
Time |
16:52 |
Sent To |
|
|
Notes |
2021-02-22 16:53:14 | 3RD REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 200900001 | | 2/22/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW HAS NOT | | BEEN ADDRESSED AND THE PERMIT FOR THE GAS LINE TO THE | | GENERATOR CANNOT BE ISSUED UNTIL THE EXISTING GAS | | SYSTEM RECEIVES A PERMIT. YOUR SCOPE OF WORK SHOWS | | CONNECTION OF THE NEW GAS LINE TO THE EXISTING | | UNPERMITTED GAS LINE, BUT ALSO SHOWS THE EXISTING | | PIPING TO BE OUT OF YOUR SCOPE. CONNECTING TO AN | | UNPERMITTED AND UNINSPECTED GAS LINE COULD POTENTIALLY | | BE A LIFE SAFETY ISSUE. IN ORDER TO MOVE FORWARD, | | PLEASE CLARIFY IF YOUR PERMIT AND SCOPE OF WORK WILL | | INCLUDE THE EXISTING PIPING OR WILL BE LEGALLY | | PERMITTED BY ANOTHER LICENSED CONTRACTOR. | | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2224 EMBASSY | | DR. SHOW EXPIRED PERMITS FOR A NEW GENERATOR AND GAS | | PIPING TO THE GENERATOR: PERMITS- 06090324 & 06090326. | | THE GAS RISER YOU HAVE SUBMITTED FOR THE NEW GENERATOR | | INDICATES AN "EXISTING" 3/4 IN. UG PE PIPE, HOWEVER | | THERE IS NO PERMIT AND INSPECTION RECORD FOR THE | | INSTALLATION OF THE LINE. IT APPEARS THAT IT MAY HAVE | | BEEN INSTALLED WITHOUT A PERMIT. IN ADDITION, I AM | | UNABLE TO FIND ANY RECORDS FOR GAS PIPING INSTALLATIONS | | IN THE INTERIOR OF THE RESIDENCE, AND THE RISER IS | | INDICATING THESE GAS LOADS AS EXISTING. IT APPEARS THAT | | THE INTERIOR INSTALLATIONS MAY HAVE ALSO BEEN DONE | | WITHOUT A PERMIT, OR PRE-DATE RECORDS ON FILE. IF THE | | INSTALLATIONS WERE DONE WITHOUT A PERMIT, THEN THE | | ENTIRE SYSTEM MUST BE REVIEWED AS A NEW SYSTEM- | | SECTIONS 105.1 & 107.2.1 WPB. PLEASE PROVIDE A COMPLETE | | RISER DRAWING THAT INCLUDES THE BRANCH LINE TO THE | | INTERIOR APPLIANCES, BRANCH LINE TO THE GENERATOR, AND | | ANY OTHER EXISTING BRANCH LINES. SHOW THE TOTAL LENGTHS | | OF THE BRANCHES, AND THE TOTAL DEVELOPED LENGTH OF THE | | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. YOU | | ARE INDICATING THE EXISTING LOAD AT 135,000 BTUH. SHOW | | ON THE RISER THE INDIVIDUAL APPLIANCE LOCATIONS AND | | THEIR INDIVIDUAL LOADS- REFER TO SECTIONS G2412.3, | | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. | | | | NEW COMMENTS BASED ON RESUBMITTED DRAWINGS. | | | | 1) PLEASE INDICATE THE PURPOSE OF THE CAPPED 1-1/4 AND | | 1/2 IN. RIGID GAS PIPES ON THE NEW RISER DRAWING. ARE | | THESE THE LINES FOR FUTURE APPLIANCES AND ARE THE CAPS | | ON THE INTERIOR OR EXTERIOR OF THE HOUSE?- SECTIONS | | G2412.4 FBC RES. | | | | 2) PLEASE PROVIDE A GAS TIGHT CAP FOR THE PIPE TO THE | | REMOVED POOL HEATER. CLARIFY IF A NEW HEATER WILL BE | | INSTALLED IN THE FUTURE- SECTIONS G2412.4 & G2415.15. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-01-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-01-27 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-01-27 |
Time |
12:25 |
Sent To |
|
|
Notes |
2021-01-27 15:10:04 | 2ND REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 200900001 | | 1/27/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW HAS NOT | | BEEN ADDRESSED AND THE PERMIT FOR THE GAS LINE TO THE | | GENERATOR CANNOT BE ISSUED UNTIL THE EXISTING GAS | | SYSTEM RECEIVES A PERMIT. YOUR SCOPE OF WORK SHOWS | | CONNECTION OF THE NEW GAS LINE TO THE EXISTING | | UNPERMITTED GAS LINE, BUT ALSO SHOWS THE EXISTING | | PIPING TO BE OUT OF YOUR SCOPE. CONNECTING TO AN | | UNPERMITTED AND UNINSPECTED GAS LINE COULD POTENTIALLY | | BE A LIFE SAFETY ISSUE. IN ORDER TO MOVE FORWARD, | | PLEASE CLARIFY IF YOUR PERMIT AND SCOPE OF WORK WILL | | INCLUDE THE EXISTING PIPING OR WILL BE LEGALLY | | PERMITTED BY ANOTHER LICENSED CONTRACTOR. | | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2224 EMBASSY | | DR. SHOW EXPIRED PERMITS FOR A NEW GENERATOR AND GAS | | PIPING TO THE GENERATOR: PERMITS- 06090324 & 06090326. | | THE GAS RISER YOU HAVE SUBMITTED FOR THE NEW GENERATOR | | INDICATES AN "EXISTING" 3/4 IN. UG PE PIPE, HOWEVER | | THERE IS NO PERMIT AND INSPECTION RECORD FOR THE | | INSTALLATION OF THE LINE. IT APPEARS THAT IT MAY HAVE | | BEEN INSTALLED WITHOUT A PERMIT. IN ADDITION, I AM | | UNABLE TO FIND ANY RECORDS FOR GAS PIPING INSTALLATIONS | | IN THE INTERIOR OF THE RESIDENCE, AND THE RISER IS | | INDICATING THESE GAS LOADS AS EXISTING. IT APPEARS THAT | | THE INTERIOR INSTALLATIONS MAY HAVE ALSO BEEN DONE | | WITHOUT A PERMIT, OR PRE-DATE RECORDS ON FILE. IF THE | | INSTALLATIONS WERE DONE WITHOUT A PERMIT, THEN THE | | ENTIRE SYSTEM MUST BE REVIEWED AS A NEW SYSTEM- | | SECTIONS 105.1 & 107.2.1 WPB. PLEASE PROVIDE A COMPLETE | | RISER DRAWING THAT INCLUDES THE BRANCH LINE TO THE | | INTERIOR APPLIANCES, BRANCH LINE TO THE GENERATOR, AND | | ANY OTHER EXISTING BRANCH LINES. SHOW THE TOTAL LENGTHS | | OF THE BRANCHES, AND THE TOTAL DEVELOPED LENGTH OF THE | | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. YOU | | ARE INDICATING THE EXISTING LOAD AT 135,000 BTUH. SHOW | | ON THE RISER THE INDIVIDUAL APPLIANCE LOCATIONS AND | | THEIR INDIVIDUAL LOADS- REFER TO SECTIONS G2412.3, | | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. | | | | NEW COMMENTS BASED ON RESUBMITTED DRAWINGS. | | | | 1) PLEASE INDICATE THE PURPOSE OF THE CAPPED 1-1/4 AND | | 1/2 IN. RIGID GAS PIPES ON THE NEW RISER DRAWING. ARE | | THESE THE LINES FOR FUTURE APPLIANCES AND ARE THE CAPS | | ON THE INTERIOR OR EXTERIOR OF THE HOUSE?- SECTIONS | | G2412.4 FBC RES. | | | | 2) PLEASE PROVIDE A GAS TIGHT CAP FOR THE PIPE TO THE | | REMOVED POOL HEATER. CLARIFY IF A NEW HEATER WILL BE | | INSTALLED IN THE FUTURE- SECTIONS G2412.4 & G2415.15. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-10-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-10-07 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-10-07 |
Time |
15:51 |
Sent To |
|
|
Notes |
2020-10-07 16:22:19 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 200900001 | | 10/7/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2224 EMBASSY | | DR. SHOW EXPIRED PERMITS FOR A NEW GENERATOR AND GAS | | PIPING TO THE GENERATOR: PERMITS- 06090324 & 06090326. | | THE GAS RISER YOU HAVE SUBMITTED FOR THE NEW GENERATOR | | INDICATES AN "EXISTING" 3/4 IN. UG PE PIPE, HOWEVER | | THERE IS NO PERMIT AND INSPECTION RECORD FOR THE | | INSTALLATION OF THE LINE. IT APPEARS THAT IT MAY HAVE | | BEEN INSTALLED WITHOUT A PERMIT. IN ADDITION, I AM | | UNABLE TO FIND ANY RECORDS FOR GAS PIPING INSTALLATIONS | | IN THE INTERIOR OF THE RESIDENCE, AND THE RISER IS | | INDICATING THESE GAS LOADS AS EXISTING. IT APPEARS THAT | | THE INTERIOR INSTALLATIONS MAY HAVE ALSO BEEN DONE | | WITHOUT A PERMIT, OR PRE-DATE RECORDS ON FILE. IF THE | | INSTALLATIONS WERE DONE WITHOUT A PERMIT, THEN THE | | ENTIRE SYSTEM MUST BE REVIEWED AS A NEW SYSTEM- | | SECTIONS 105.1 & 107.2.1 WPB. PLEASE PROVIDE A COMPLETE | | RISER DRAWING THAT INCLUDES THE BRANCH LINE TO THE | | INTERIOR APPLIANCES, BRANCH LINE TO THE GENERATOR, AND | | ANY OTHER EXISTING BRANCH LINES. SHOW THE TOTAL LENGTHS | | OF THE BRANCHES, AND THE TOTAL DEVELOPED LENGTH OF THE | | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. YOU | | ARE INDICATING THE EXISTING LOAD AT 135,000 BTUH. SHOW | | ON THE RISER THE INDIVIDUAL APPLIANCE LOCATIONS AND | | THEIR INDIVIDUAL LOADS- REFER TO SECTIONS G2412.3, | | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. | | | | A) SHOW THE DELIVERY PRESSURE AT THE OUTLET OF THE NEW | | REGULATOR, AND THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF | | EITHER SIDE OF THE REGULATOR- SECTIONS G2421.1 & | | G2421.2(7). | | | | B) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE | | RISER AND MARK OR HIGHLIGHT THE SPECS TO SHOW THE | | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND | | PRESSURES, AND ORIFICE SIZE. | | | | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING | | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT | | INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-04-23 |
Time |
|
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2021-04-13 |
Time |
10:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-02-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-02-23 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-02-10 |
Time |
11:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-01-28 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-01-19 |
Time |
22:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-31 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-10-31 |
Time |
19:12 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-10-03 |
Time |
07:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-22 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-22 |
Time |
16:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2021-02-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-02-22 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2021-01-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-01-27 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-01-27 |
Time |
12:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-10-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-10-07 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-10-07 |
Time |
15:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2021-04-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-23 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-23 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-02-23 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-02-23 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-01-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-01-20 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-01-20 |
Time |
11:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-21 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-21 |
Time |
16:22 |
Sent To |
|
|
Notes |
2020-10-21 16:23:47 | THE PRE-FAB GENERATOR PAD ENGINEERING IS REQUIRED TO BE | | SIGNED AND SEALED. ELECTRONICALLY SUBMITTED DRAWINGS | | ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE | | ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED | | AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE | | ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN | | SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. | | NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | ACCEPTABLE. FS 471 & 61G15 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-10-30 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2020-10-30 |
Time |
17:17 |
Sent To |
I |
|
Notes |
|
|