Plan Review Details - Permit 20081374
Plan Review Stops For Permit 20081374
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 14:31 Rev Time 0.00
Received By shill Date 2020-09-12 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By jleahy Date 2020-10-20 Time 08:04 Rev Time 0.00
Received By jleahy Date 2020-10-20 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-04 Cont ID  
Sent By cthroop Date 2020-09-04 Time 15:29 Rev Time 0.00
Received By cthroop Date 2020-09-04 Time 14:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 11:07 Rev Time 0.00
Received By lcrespo Date 2020-10-22 Time 11:07 Sent To  
Notes
2020-10-22 11:08:0310/22/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-11 Cont ID  
Sent By medwards Date 2020-09-11 Time 08:34 Rev Time 0.00
Received By medwards Date 2020-09-11 Time 07:45 Sent To  
Notes
2020-09-11 08:34:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081374
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT APPLICATION SPECIFIES THIS TO BE A LP GAS
 SYSTEM WITH A 500 GAL. TANK BUT THE DRAWING INDICATES
 THIS TO BE AN EXISTING ? LB NATURAL GAS SYSTEM WITH THE
 ADDITION OF THIS GENERATOR. PLEASE CORRECT THIS AND
 RESUBMIT. CANNOT DO A COMPLETE REVIEW AT THIS TIME. FBC
 FS 107.2.1
  
 2) PLEASE PROVIDE A GAS RISER DIAGRAM SHOWING THE
 COMPLETE (EXISTING APPLIANCES AND THE NEW GENERATOR)
 FUEL GAS SYSTEM. PLEASE PROVIDE THE BTU?S FOR EACH
 APPLIANCE AND PROVIDE THE DISTANCE TO THE MOST REMOTE
 APPLIANCE ON THIS SYSTEM. ON THIS GAS RISER DIAGRAM
 PLEASE SHOW ALL SHUT OFF VALVES, REGULATORS AND DRIP
 LEGS USED IN THIS SYSTEM. FBC FS 107.2.1
  
 3) PLEASE IDENTIFY WHICH MODEL OF GENERATOR IS USED FOR
 THIS PROJECT. FBC FS 107.2.1
  
 4) PLEASE PROVIDE SPECS FOR REGULATORS USED, IDENTIFY
 WHICH MODEL IS USED FOR THIS PROJECT. FBC FS 107.2.1
  
 5) PLEASE PROVIDE THE SPECS FOR THE SPRING USED IN THE
 REGULATORS USED, IDENTIFY WHICH SPRING IS USED FOR THIS
 PROJECTS GAS VOLUME. FBC FS 107.2.1
  
 6) PLEASE PROVIDE SPECS FOR THE FUEL TANK USED FOR THIS
 PROJECT. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 11:08 Rev Time 0.00
Received By lcrespo Date 2020-10-05 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 14:31 Rev Time 0.00
Received By shill Date 2020-09-01 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 11:06 Rev Time 0.00
Received By lcrespo Date 2020-10-22 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-11 Cont ID  
Sent By medwards Date 2020-09-11 Time 08:34 Rev Time 0.00
Received By medwards Date 2020-09-11 Time 08:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By lcrespo Date 2020-10-22 Time 11:07 Rev Time 0.00
Received By lcrespo Date 2020-10-22 Time 11:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-11 Cont ID  
Sent By medwards Date 2020-09-11 Time 08:49 Rev Time 0.00
Received By medwards Date 2020-09-11 Time 08:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-09 Cont ID  
Sent By rthermid Date 2020-09-09 Time   Rev Time  
Received By rthermid Date 2020-09-09 Time   Sent To I
Notes
***NONE***