Plan Review Details - Permit 20081365
Plan Review Stops For Permit 20081365
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-10 Cont ID  
Sent By cthroop Date 2020-11-10 Time 15:33 Rev Time 0.00
Received By cthroop Date 2020-11-10 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-27 Cont ID  
Sent By cthroop Date 2020-10-27 Time 14:48 Rev Time 0.00
Received By cthroop Date 2020-10-27 Time 14:25 Sent To  
Notes
2020-10-27 14:51:33PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PRIOR COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
 SEE BELOW.
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE SLAB
 (INCLUDING ANCHORING SPECIFICATION/DETAIL), OR PROVIDE
 PREFAB SLAB ENGINEERING.
  
 CORRECTIONS LETTEER SUBMITTED ON 10/16/2020 STATES A
 PRE-CAST PAD DESIGN IS INCLUDED. NO PAD DETAIL
 SUBMITTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:53 Rev Time 0.00
Received By shill Date 2020-09-12 Time 13:53 Sent To  
Notes
2020-09-12 13:54:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE SLAB
 (INCLUDING ANCHORING SPECIFICATION/DETAIL), OR PROVIDE
 PREFAB SLAB ENGINEERING.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By cthroop Date 2020-08-31 Time 08:20 Rev Time 0.00
Received By cthroop Date 2020-08-31 Time 08:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-10 Cont ID  
Sent By medwards Date 2020-11-10 Time 14:36 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 14:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-27 Cont ID  
Sent By medwards Date 2020-10-27 Time 15:18 Rev Time 0.00
Received By medwards Date 2020-10-27 Time 15:18 Sent To  
Notes
2020-10-27 15:19:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20081365
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE LONGEST LENGTH OF PIPING FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET. THIS COULD
 EITHER BE THE EXISTING SYSTEM OR THE NEW PIPING BEING
 INSTALLED BUT I MUST HAVE THIS NUMBER AS IT IS THE
 NUMBER USED WHEN SIZING THE NEW GAS PIPING. FBC GF
 402.4.1
  
 2) PLEASE SEE NOTE 2 OF MY ORIGINAL REVIEW: PLEASE
 PROVIDE THE GENERATOR PAD SPECS. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By medwards Date 2020-09-10 Time 16:19 Rev Time 0.00
Received By medwards Date 2020-09-10 Time 15:51 Sent To  
Notes
2020-09-10 16:19:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081365
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE MARK (IDENTIFY) WHICH DORMONT CONNECTOR IS
 USED IN THIS INSTALLATION. FBC FS 107.2.1
  
 2) PROVIDE GENERATOR PAD SPEC SHEETS. FBC FS 107.2.1
  
 3) PROVIDE A COMPLETE GAS RISER DIAGRAM INCLUDING
 EXISTING APPLIANCES FROM PERMIT 12110107. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-13 Cont ID  
Sent By shill Date 2020-11-13 Time 15:30 Rev Time 0.00
Received By shill Date 2020-10-16 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-25 Cont ID  
Sent By shill Date 2020-09-25 Time 11:08 Rev Time 0.00
Received By shill Date 2020-08-28 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 15:59 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-10 Cont ID  
Sent By medwards Date 2020-09-10 Time 16:23 Rev Time 0.00
Received By medwards Date 2020-09-10 Time 16:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-10 Cont ID  
Sent By jgomez Date 2020-11-10 Time 13:08 Rev Time 0.00
Received By jgomez Date 2020-11-10 Time 13:08 Sent To  
Notes
2020-11-10 13:09:25PRECAST ENGINEERED PAD:
  
 ENGINEER?S EMERGENCY RULE
 EMERGENCY RULE APPLIED 61G15ER20-4
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-29 Cont ID  
Sent By shill Date 2020-10-29 Time 13:52 Rev Time 0.00
Received By shill Date 2020-10-27 Time 14:25 Sent To  
Notes
2020-10-29 13:53:05SIGNATURE REVIEW WILL BE DONE AFTER ENGINEERING OR
 DETAIL IS SUBMITTED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By medwards Date 2020-09-10 Time 16:21 Rev Time 0.00
Received By medwards Date 2020-09-10 Time 16:21 Sent To  
Notes
2020-09-10 16:23:12NO GAS RISER DIAGRAM WAS SUPPLIED WITH THIS PACKAGE.
 SIGNATURE REVIEW WILL NEED TO BE REVIEWED IN THE 2ND
 CYCLE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-09-02 06:47:44SIGNATURE VERIFIED ON ELECTRICAL PLAN. CT

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By kalexand Date 2020-11-13 Time 15:21 Rev Time 0.00
Received By kalexand Date 2020-11-13 Time 15:21 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By kalexand Date 2020-09-21 Time 16:31 Rev Time 0.00
Received By kalexand Date 2020-09-21 Time 16:31 Sent To I
Notes
2020-09-22 13:05:09ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. REQUIRED CORNER
 LOT SETBACK IS 12.5 FT
 2.
 3.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved