Plan Review Details - Permit 20081351
Plan Review Stops For Permit 20081351
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-17 Cont ID  
Sent By rmcphers Date 2020-11-17 Time 11:13 Rev Time 0.00
Received By rmcphers Date 2020-11-17 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-20 Cont ID  
Sent By rmcphers Date 2020-10-20 Time 12:10 Rev Time 0.00
Received By rmcphers Date 2020-10-20 Time 12:10 Sent To  
Notes
2020-10-20 12:15:00SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING NEEDS TO BE SIGNED AND SEALED BY THE
 ENGINEER OR ARCHITECT - DRAWING NEEDS TO SHOW THE WIND
 DESIGN PARAMETERS - DRAWING NEEDS TO SHOW THE AMOUNT OF
 ANCHORS. (PREVIOUSLY APPROVED DRAWING HAS BEEN
 VERSIONED OVER IN PROJECTDOX BY THE REVISED DRAWING
 ADDED).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2020-09-23 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-17 Cont ID  
Sent By equinone Date 2020-11-17 Time 12:33 Rev Time 0.00
Received By equinone Date 2020-11-17 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-10-22 Cont ID  
Sent By equinone Date 2020-10-22 Time 09:37 Rev Time 0.00
Received By equinone Date 2020-10-22 Time 09:37 Sent To  
Notes
2020-10-22 09:39:05FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6746
 [email protected]
  
 FROM PREVIOUS REVIEW:
  
 1) CORRECTED.
  
 2) VALUE FOR SIGN TOO LOW. SUBMIT A SIGNED CONTRACT FOR
 WORK INVOLVED. SEE 2ND REVIEW NOTES.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT, EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2ND REVIEW:
  
 3) UNSIGNED CONTRACT RECEIVED BUT IT INCLUDES A SECOND
 SIGN, BUT NO PLAN SUBMITTED FOR THE OTHER SIGN FBC 107,
 SCOPE NOT CLEAR. PERMIT VALUE NOT YET ADJUSTED.
  
 4) PREVIOUS PLANS WERE SIGNED AND SEALED BY AN
 ENGINEER, THE SECOND SUBMISSION DOES NOT INCLUDE THE
 SEAL AND SIGNATURE. PLANS NEED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC
 107.2.1, 107.3.5; FS 471, 481.
  
 ENRIQUE QUINONEZ
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By jleahy Date 2020-09-14 Time 11:00 Rev Time 0.00
Received By jleahy Date 2020-09-14 Time 10:42 Sent To  
Notes
2020-09-14 11:05:08FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO DISCONNECT SHOWN FOR SIGN 600.0(A)(1)
  
 600. 6 DISCONNECTS (A) LOCATION.
 (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE
 DISCONNECT SHALL BE LOCATED AT THE POINT THE FEEDER
 CIRCUIT OR BRANCH CIRCUIT(S)
 SUPPLYING A SIGN OR OUTLINE LIGHTING SYSTEM ENTERS A
 SIGN ENCLOSURE OR A POLE IN ACCORDANCE WITH 600.5(C)(3)
 AND SHALL DISCONNECT
 ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF THE SIGN OR
 POLE.
  
 2) VALUE FOR SIGN TOO LOW. SUBMIT A SIGNED CONTRACT FOR
 WIRK INVILVED.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-24 Cont ID  
Sent By lmarchan Date 2020-11-24 Time 14:32 Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-06 Cont ID  
Sent By lmarchan Date 2020-11-06 Time 08:55 Rev Time 0.00
Received By lmarchan Date 2020-10-08 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2020-08-28 Time 14:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-17 Cont ID  
Sent By rmcphers Date 2020-11-17 Time 11:13 Rev Time 0.00
Received By rmcphers Date 2020-11-17 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-20 Cont ID  
Sent By rmcphers Date 2020-10-20 Time 12:15 Rev Time 0.00
Received By rmcphers Date 2020-10-20 Time 12:15 Sent To  
Notes
2020-10-20 12:16:21PREVIOUSLY APPROVED DRAWING HAS BEEN VERSIONED OVER IN
 PROJECTDOX - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-14 Cont ID  
Sent By jleahy Date 2020-09-14 Time 11:05 Rev Time 0.00
Received By jleahy Date 2020-09-14 Time 11:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-11-24 Cont ID  
Sent By kalexand Date 2020-11-24 Time 08:17 Rev Time 0.00
Received By kalexand Date 2020-11-24 Time 08:17 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-05 Cont ID  
Sent By kalexand Date 2020-11-05 Time 15:38 Rev Time 0.00
Received By kalexand Date 2020-11-05 Time 15:38 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-16 Cont ID  
Sent By kalexand Date 2020-09-16 Time 13:53 Rev Time 0.00
Received By kalexand Date 2020-09-16 Time 13:53 Sent To I
Notes
***NONE***