Plan Review Details - Permit 20081283
Plan Review Stops For Permit 20081283
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-02 Cont ID  
Sent By equinone Date 2021-04-02 Time 12:32 Rev Time 0.00
Received By equinone Date 2021-04-02 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-29 Cont ID  
Sent By equinone Date 2021-03-29 Time 14:55 Rev Time 0.00
Received By equinone Date 2021-03-29 Time 14:55 Sent To  
Notes
2021-03-29 15:05:36CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) NEW ELECTRICAL DIAGRAM SUBMITTED HAS DIFFERENT
 INFORMATION (PUMP SIZE, ETC.) THAN PREVIOUSLY SUBMITTED
 DIAGRAM. PLEASE CLARIFY WHICH ONE IS THE ONE THAT NEEDS
 TO BE REVIEWED OR CLARIFY HOW THEY ARE RELATED. FBC 107
 2) DRAWINGS NEED TO HAVE NAME, SIGNATURE, AND LICENSE
 NUMBER OF ELECTRICAL QUALIFIERS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 [email protected]
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By equinone Date 2021-01-07 Time 14:14 Rev Time 0.00
Received By equinone Date 2021-01-07 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-02 Cont ID  
Sent By equinone Date 2021-04-02 Time 12:32 Rev Time 0.00
Received By equinone Date 2021-04-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-29 Cont ID  
Sent By equinone Date 2021-03-29 Time 14:57 Rev Time 0.00
Received By equinone Date 2021-03-25 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-07 Cont ID  
Sent By equinone Date 2021-01-07 Time 14:24 Rev Time 0.00
Received By equinone Date 2020-12-31 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:39 Rev Time 0.00
Received By lcrespo Date 2020-09-05 Time 14:45 Sent To  
Notes
2020-09-05 14:46:00ROUTED TO PLUMBING BIN

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 09:39 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 09:39 Sent To  
Notes
2020-09-08 09:40:2409/08/20 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/IRRIGATION)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-04-02 Cont ID  
Sent By equinone Date 2021-04-02 Time 12:32 Rev Time 0.00
Received By equinone Date 2021-04-02 Time 12:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-03-29 Cont ID  
Sent By equinone Date 2021-03-29 Time 14:56 Rev Time 0.00
Received By equinone Date 2021-03-29 Time 14:55 Sent To  
Notes
2021-03-29 14:56:53CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SAME COMMENTS AS FIRST REVIEW.
  
 1) PER THE WPB AMENDMENTS TO THE FBC, ELECTRICAL PLAN
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON MUST BE
 A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By equinone Date 2021-01-07 Time 14:21 Rev Time 0.00
Received By equinone Date 2021-01-07 Time 14:19 Sent To  
Notes
2021-01-07 14:23:54CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PER THE WPB AMENDMENTS TO THE FBC, ELECTRICAL PLAN
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON MUST BE
 A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  