Plan Review Details - Permit 20081264
Plan Review Stops For Permit 20081264
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-23 Cont ID  
Sent By ppetty Date 2020-09-23 Time 09:00 Rev Time 0.00
Received By ppetty Date 2020-09-23 Time 09:00 Sent To  
Notes
2020-09-23 09:00:41NO CHANGE ON PLAN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-10 Cont ID  
Sent By fgiaquin Date 2020-09-10 Time 22:30 Rev Time 0.00
Received By fgiaquin Date 2020-09-10 Time 22:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 21:20 Rev Time 0.00
Received By fgiaquin Date 2020-09-03 Time 20:44 Sent To  
Notes
2020-09-03 21:20:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLEASE PROVIDE A LEGEND FOR SYMBOLS ON PLAN. FBC
 107.2.1
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL SHOWING UL
 LISTINGS OF DEVICES. NEC 110.2 110.3B FBC 107.2.1
  
 4. VALUE LOW FOR AMOUNT OF WORK SHOWN PROVIDE SIGNED
 CONTRACT FROM OWNER AND CONTRACTOR FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-09-23 Cont ID  
Sent By ppetty Date 2020-09-23 Time 09:00 Rev Time 0.00
Received By ppetty Date 2020-09-23 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 21:24 Rev Time 0.00
Received By fgiaquin Date 2020-08-27 Time 11:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By shill Date 2020-09-17 Time 12:47 Rev Time 0.00
Received By shill Date 2020-09-17 Time 12:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 21:24 Rev Time 0.00
Received By fgiaquin Date 2020-09-03 Time 21:23 Sent To  
Notes
2020-09-03 21:23:58CONTRACTOR MUST SIGN PLAN
  
  