2020-10-16 13:18:40 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20081228 |
| 10/16/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A1.0: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND |
| DIMENSIONS FOR THE DRINKING FOUNTAIN AND BREAKROOM |
| SINK- SECTIONS 305.3 & 305.5 FBC ACC. |
| |
| 2) A1.0: SHOW THE DEPTH DIMENSION OF THE DF ALCOVE- |
| SECTION 305.7 FBC ACC. |
| |
| 3) A3.4: PROVIDE DETAILS SHOWING THE DF KNEE AND TOE |
| CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS- SECTION |
| 602.2 FBC ACC. |
| |
| 4) A3.4: PLEASE PROVIDE THE FOLLOWING MISSING |
| ACCESSIBILITY DETAILS. |
| |
| A) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORY- |
| SECTION 606.2. |
| B) SHOW THE COMPLETE ARC OF THE DOOR TO VERIFY IT WILL |
| NOT SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY- |
| SECTION 602.2.3 FBC ACC. |
| C) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| D) HEIGHTS OF THE FRONT RIM OF THE LAVATORIES FROM THE |
| FINISHED FLOORS- SECTION 606.3 |
| E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| 306. |
| H) GRAB BAR LENGTHS, SPACINGS FROM ADJACENT WALLS, AND |
| MOUNTING HEIGHTS FROM THE FINISHED FLOOR TO THE TOP OF |
| THE GRIPPING SURFACES- SECTION 604.5 & 609.4 |
| J) THE CENTERLINES OF THE TOILET PAPER DISPENSERS |
| MEASURED FROM THE FRONT EDGES OF THE WATER CLOSETS- |
| SECTION 604.7. |
| L) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3. |
| |
| 5) INDICATE THE TYPE AND DIMENSIONS OF WALL BACKING |
| MATERIAL TO BE INSTALLED AT THE MOP SINK- SECTION 310.3 |
| FBC P AND SECTION 1210.2.2 FBC B. |
| |
| 6) P0.0: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| HEATER AND SUBMIT A MANUFACTURER'S SPEC SHEET TO VERIFY |
| COMPLIANCE WITH TABLE C404.2 FBC EC. |
| |
| 7) P0.0: PROVIDE A DEVICE SCHEDULE SHOWING MAKES, |
| MODELS AND LISTINGS FOR THE WATER HAMMER ARRESTORS, |
| MIXING VALVES, BACKFLOW PREVENTERS, AND TRAP PRIMERS- |
| SECTIONS 604.9, 607.1.2, 608.1, & 1002.4.1.1 FBC P. |
| |
| 8) P2.0: SHOW THE LOCATION OF THE REQUIRED CLEANOUT AT |
| THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER |
| LINE- SECTION 708.1.3 FBC P. |
| |
| 9) P2.0: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 |
| WPB. SHOW THE WIDTH OF THE REPAIR; THE MINIMUM |
| THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED; THE |
| SIZE, SPACING, AND EMBEDMENT DEPTH OF THE DOWELS; AND |
| THE ANCHORING MATERIAL FOR THE DOWELS. THE REPAIR SHALL |
| ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND THE |
| REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. PLEASE |
| NOTE A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| FOR FINAL INSPECTION APPROVAL. |
| |
| 10) P4.0: THE LOCATIONS OF THE TRAP PRIMERS FOR THE |
| FLOOR DRAINS IN THE RESTROOMS ARE NOT CLEARLY |
| IDENTIFIED- SECTION 1002.4.1.1 FBC P. |
| |
| 11) SUBMIT A PLUMBING SUB-PERMIT APPLICATION AS |
| REQUIRED BY SECTION 105.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |