Plan Review Details - Permit 20081174
Plan Review Stops For Permit 20081174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2020-09-03 Cont ID  
Sent By rmcdouga Date 2020-09-03 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2020-09-03 Time 09:09 Sent To  
Notes
2020-09-03 09:14:03THE PRODUCT APPROVALS SUBMITTED FOR THE ROLL UP DOORS
 AT THE GARAGE ARE NOT REQUIRED BY STATUTE OR BUILDING
 CODE. THE GARAGE AREA IS DESIGNED AS PARTICALLY
 ENCLOSED. SEE MEMO FROM ENGINEER OF RECORD IN THE FILE
 CONFIRMING THE PARTICALLY ENCLOSED DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-27 Cont ID  
Sent By rmcdouga Date 2020-08-27 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2020-08-27 Time 11:01 Sent To  
Notes
2020-08-27 11:27:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS (FL10545-R4) THAT WERE
 SUBMITTED FOR THE ROLL UP GARAGE DOORS HAVE A MAXIMUM
 DESIGN PRESSURE OF +/- 45 PSF. THE (2) LOADING BERTH
 DOORS ARE 12'-8" X16'-0" AND THE (4) GARAGE DOORS ARE
 (2) AT 10'-8" X 9'-0 AND (2) AT 10'-8" X 9'-6". THE
 WORST CASE CLADDING LOADS FROM THE WIND TUNNEL TESTING
 REPORT HAS +90, -180 PSF FOR THE DOORS AT LEVEL P1.
 PLEASE CLARIFY HOW THESE DOORS WILL MEET THE REQUIRED
 WIND PRESSURES.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-27 Cont ID  
Sent By rmcdouga Date 2020-08-27 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2020-08-26 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-08-27 Cont ID  
Sent By rmcdouga Date 2020-08-27 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2020-08-27 Time 11:01 Sent To  
Notes
***NONE***