Plan Review Details - Permit 20081115
Plan Review Stops For Permit 20081115
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-19 Cont ID  
Sent By cthroop Date 2020-10-19 Time 07:57 Rev Time 0.00
Received By cthroop Date 2020-10-19 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 09:18 Rev Time 0.00
Received By cthroop Date 2020-10-02 Time 08:05 Sent To  
Notes
2020-10-02 09:37:59PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS
  
 1ST REVIEW COMMENTS:
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ACKNOWLEDGED
  
 2. CORRECTED
  
 3. FBC B 1609, FBC R 301, PROVIDE THE FLORIDA STATE
 PRODUCT APPROVAL COVER PAGE WHICH SHOWS THE APPROVAL
 NUMBER AND STATUS (WINDOWS). (NOT ADDRESSED)
  
 NEW COMMENT:
 (THE COVER PAGE PROVIDES THE CURRENT CODE INFORMATION
 AND THE PRODUCT CATEGORY. THE 2ND PAGE PROVIDES A LIST
 OF AVAILABLE MODELS TO BE INSTALLED. THE MODEL SELECTED
 PROVIDES THE IMPACT RATING OF THAT MODEL. THE
 INSTALLATION INSTRUCTIONS ARE REQUIRED FOR THE MODEL
 SELECTED. THE DESIGNER, SHALL REVIEW AND APPROVE THE
 PRODUCT APPROVAL. NAME AND SIGNATURE REQUIRED).
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 4. FBC B 1609, FBC R 301, UPLOAD THE COMPLETE DOOR
 PRODUCT APPROVAL INTO SUPPORTING DOCS FOLDER (COVER
 PAGE, EVALUATION REPORT, INSTALLATION INSTRUCTIONS).
 (PARTIAL COMPLIANCE)
  
 NEW COMMENT:
 ( COVER PAGE MISSING) (PRODUCT EVALUATION PROVIDED)
 (PAGE FL22513 R2 FL0211 SUBMITTED FOR REVIEW IS THE
 INSTALLATION INSTRUCTIONS FOR A MASONITE DOUBLE DOOR
 W/SIDELITES. THERE ARE NO DOUBLE DOORS AT THIS SITE)
  
  
 THESE DOCUMENTS ARE REQUIRED PER 2017 FLORIDA BUILDING
 CODE, 6TH EDITION W/2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION
 SECTION 107.2 CONSTRUCTION DOCUMENTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 09:21 Rev Time 0.00
Received By shill Date 2020-09-12 Time 09:12 Sent To  
Notes
2020-09-12 09:15:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 105, THIS ADDRESS HAS AN EXPIRED AC CHANGEOUT
 PERMIT AND A NEW AC UNIT WAS INSTALLED WITHOUT A
 PERMIT. OBTAIN A PERMIT FOR THAT WORK BY HAVING A
 LICENSED CONTRACTOR EMAIL A PERMIT APPLICATION TO
 [email protected].
  
 2. INFORMATIONAL ONLY - DOCUMENTS WERE ADDED TO THE
 "SIGNATURE" FOLDER; PLEASE SEE PROJECTDOX INSTRUCTIONS,
 ALL DOCUMENTS FOR REVIEW SHOULD BE UPLOADED TO DRAWINGS
 (SINGLE PAGES) OR SUPPORTING DOCS FOLDERS. FOR A WINDOW
 PERMIT IT IS ACCEPTABLE THAT ALL DOCUMENTS ARE UPLOADED
 INTO SUPPORTING DOCS. THESE DOCUMENTS HAVE BEEN
 REMOVED, NO ACTION NECESSARY.
  
 3. FBC B 1609, FBC R 301, PROVIDE THE FLORIDA STATE
 PRODUCT APPROVAL COVER PAGE WHICH SHOWS THE APPROVAL
 NUMBER AND STATUS (WINDOWS).
  
 4. FBC B 1609, FBC R 301, UPLOAD THE COMPLETE DOOR
 PRODUCT APPROVAL INTO SUPPORTING DOCS FOLDER (COVER
 PAGE, EVALUATION REPORT, INSTALLATION INSTRUCTIONS).
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-19 Cont ID  
Sent By cthroop Date 2020-10-19 Time 07:57 Rev Time 0.00
Received By cthroop Date 2020-10-07 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 09:38 Rev Time 0.00
Received By cthroop Date 2020-09-22 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 09:21 Rev Time 0.00
Received By shill Date 2020-08-25 Time 14:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-02 Cont ID  
Sent By cthroop Date 2020-10-02 Time 09:38 Rev Time 0.00
Received By cthroop Date 2020-10-02 Time 08:05 Sent To  
Notes
***NONE***