Plan Review Stops For Permit 20080987 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-11-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-11-17 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-11-17 |
Time |
08:01 |
Sent To |
|
|
Notes |
2020-11-17 09:50:40 | PROVISO: PROVIDE ICC-ES REPORT FOR SPRAY FOAM | | INSULATION TO CITY INSPECTOR. CT | | | | NOTICE: PROPERTY IS LOCATED IN A SFHA. FLOOD ZONE AE | | W/BFE'S OF 6.0 ' AND 7.0' NAVD. PROJECT DOES NOT | | QUALIFY AS A S/I PER FEMA. | | IMPROVEMENT VALUE PER PAPA - $1,159,654. VALUE OF | | PERMIT W/5 YR TAIL - $126,325. CT |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-04-23 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-04-23 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2021-04-23 |
Time |
10:12 |
Sent To |
|
|
Notes |
2021-04-23 10:31:41 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW. | | | | 1) SPACING OF RECEPTACLES NEEDS TO COMPLY WITH NEC | | 210.52(A). FLOOR RECEPTACLES NEED TO BE LOCATED WITHIN | | 18 INCHES OF THE WALL TO COUNT FOR THE REQUIRED NUMBER | | OF RECEPTACLES. NEC 210.52(A) | | | | CORRECTED | | | | 2) EXISTING RISER DIAGRAM SHOWS #2/0 FEEDERS FROM 200 | | AMPS BREAKERS TO ELECTRICAL PANELS. SIZE #2/0 IS ONLY | | GOOD FOR 175 AMPS AND BECAUSE THIS AMPACITY MATCHES A | | 175 AMPS STANDARD SIZE BREAKER YOU ARE NOT ALLOWED TO | | JUMP TO THE NEXT STANDARD SIZE AND A #3/0 CU IS | | REQUIRED. PLEASE DOUBLE CHECK WHAT SIZE IS CURRENTLY | | EXISTING TO MAKE SURE INSTALLATION COMPLIES WITH NEC | | 240.4 (B)(2). | | | | RISER SHOWS 2 SETS OF #2/0 | | | | | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-17 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-17 |
Time |
10:59 |
Sent To |
|
|
Notes |
2021-03-08 11:29:32 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1) SPACING OF RECEPTACLES NEEDS TO COMPLY WITH NEC | | 210.52(A). FLOOR RECEPTACLES NEED TO BE LOCATED WITHIN | | 18 INCHES OF THE WALL TO COUNT FOR THE REQUIRED NUMBER | | OF RECEPTACLES. NEC 210.52(A) | | 2) EXISTING RISER DIAGRAM SHOWS #2/0 FEEDERS FROM 200 | | AMPS BREAKERS TO ELECTRICAL PANELS. SIZE #2/0 IS ONLY | | GOOD FOR 175 AMPS AND BECAUSE THIS AMPACITY MATCHES A | | 175 AMPS STANDARD SIZE BREAKER YOU ARE NOT ALLOWED TO | | JUMP TO THE NEXT STANDARD SIZE AND A #3/0 CU IS | | REQUIRED. PLEASE DOUBLE CHECK WHAT SIZE IS CURRENTLY | | EXISTING TO MAKE SURE INSTALLATION COMPLIES WITH NEC | | 240.4 (B)(2). | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR | | MS | | | | ENRIQUE QUINONEZ P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-05-14 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-14 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-13 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-12-03 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-11-02 |
Time |
17:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-05-29 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-05-29 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-05-25 |
Time |
13:44 |
Sent To |
|
|
Notes |
2021-05-29 08:32:32 | RECEIPT MU-2021-26367 - $0.00 NO FEES DUE | 2021-05-25 13:44:29 | 5/25/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-05-14 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-14 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-14 |
Time |
13:44 |
Sent To |
|
|
Notes |
2021-05-14 13:44:53 | 2ND FLOOR AC SPACE ADDED - - | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-04-22 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-22 |
Time |
08:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-04 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-04 |
Time |
15:02 |
Sent To |
|
|
Notes |
2020-11-04 15:40:56 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20080987 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SHOW ON THE DRAWING HOW THE CONDENSATION WILL | | BE REMOVED. FBC RES M1411.3 | | | | 2) PLEASE SHOW HOW THE CONDENSING UNIT WILL BE ANCHORED | | DOWN. FBC RES M1307.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2021-05-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-05-15 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-05-15 |
Time |
11:25 |
Sent To |
|
|
Notes |
2021-05-15 11:26:47 | NOTICE: PROPERTY IS LOCATED IN A SFHA. FLOOD ZONE AE | | W/BFE'S OF 6.0 ' AND 7.0' NAVD. PROJECT DOES NOT | | QUALIFY AS A S/I PER FEMA 50% RULE. | | IMPROVEMENT VALUE PER PAPA - $1,159,654. VALUE OF | | PERMIT W/5 YR TAIL - $126,325. CT |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-04 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-11-04 |
Time |
09:35 |
Sent To |
|
|
Notes |
2020-11-04 09:36:31 | PER PLANS THERE IS NO PLUMBING ON THE SCOPE OF WORK. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2020-11-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-11-17 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-11-17 |
Time |
08:01 |
Sent To |
|
|
Notes |
2020-11-17 09:46:33 | PROVISO: SEPERATE ROOFING PERMIT REQUIRED. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-04-22 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-22 |
Time |
08:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-04 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-04 |
Time |
15:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2021-05-11 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-05-11 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2021-05-11 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-11-05 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-11-05 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-11-05 |
Time |
|
Sent To |
I |
|
Notes |
2020-11-05 13:24:23 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 11/5/2020 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICATING | | THE SETBACKS OF THE PROPOSED WORK TO ALL PROPERTY | | LINES. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|