Plan Review Details - Permit 20080940
Plan Review Stops For Permit 20080940
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-25 Cont ID  
Sent By medwards Date 2020-11-25 Time 09:02 Rev Time 0.00
Received By medwards Date 2020-11-25 Time 09:02 Sent To  
Notes
2020-11-25 09:04:24REVISION PERMIT # 20111126 IS FOR CORRECTING THAT THE
 COOKTOP AND WATER HEATER IS NOT GAS AS STATED ON THE
 ELECTRICAL CALCULATIONS FOR THIS PROJECT.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 13:33 Rev Time 0.00
Received By medwards Date 2020-11-23 Time 13:33 Sent To  
Notes
2020-11-23 13:34:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080940
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GENERATOR LOAD CALCULATIONS FROM THE MASTER PLAN
 STILL REFLECTS THAT THE COOK TOP AND WATER HEATER ARE
 GAS APPLIANCES. PLEASE UPDATE THE GENERATOR LOAD
 CALCULATIONS ON THE MASTER PERMIT OR SHOW THE GAS
 LINES, DISTANCES AND BTU?S FOR THE COOKTOP AND WATER
 HEATER ON THE GAS LINE DIAGRAM. FBX 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By jesmith Date 2020-09-03 Time 13:49 Rev Time 0.00
Received By jesmith Date 2020-09-03 Time 09:36 Sent To  
Notes
2020-09-03 13:49:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. A REVIEW OF PUBLIC RECORDS DOES NOT SHOW THAT ANY
 GAS PERMIT AND PLAN(S) HAVE BEEN APPLIED FOR THE
 EXISTING GAS POOL HEATER NOTED ON THE GAS PLAN, NOR FOR
 THE GAS WATER HEATER AND THE GAS COOKTOP INDICATED IN
 MASTER PERMIT FOR GENERATOR #20070805. IF SYSTEM IS NOT
 TO COMPLIANT WITH 2017 FBC RES/FBC FG, IT MAY REQUIRE
 TO BE BROUGHT UP TO CODE AT OWNER EXPENSE WITH A NEW
 PERMIT AND REVIEW. THIS MAY REQUIRE INSPECTIONS AND
 TESTING TO ASCERTAIN THE COMPLIANCE AND INTEGRITY OF
 THE SYSTEM(S) AS DETERMINED BY THE INSPECTOR.
 RECORDS OF ORIGINAL PERMIT #95008841 INDICATES ALL
 ELECTRIC APPLIANCES.
 PER WPB FBC 107.2.1, SUBMIT A COMPLETE GAS RISER
 SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED
 LENGTH TO THE FURTHEST GAS OUTLET OF 2PSI SYSTEM AND
 SYSTEMS DOWNSTREAM OF MP REGULATORS, THE BTU LOAD OF
 EACH APPLIANCE, THE PSI OF THE SYSTEM(S), THE TYPE OF
 GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. PROVIDE TABLE
 FOR SYSTEMS DOWNSTREAM OF MP REGULATORS.
  
 2. PER WPB FBC 107.2.1, CONFIRM THAT THE FIREPLACE HAS
 NOT BEEN CONVERTED TO NATURAL GAS .IF IT HAS THEN
 INCLUDE IN THE RISER AND CALCULATIONS.
  
 3. RE: 2PSI SYSTEM; DISTANCE FROM METER TO FURTHEST
 APPLIANCE (GENERATOR) EXCEEDS 100 FEET; IT IS
 APPROXIMATELY 115 FEET PER THE GAS RISER DIAGRAM.
 SUBMITTED FBC FG TABLE 402.4(18) INDICATES 100 FEET.
 PER WPB FBC 107.2.1, REVISE AND RESUBMIT.
  
 4. RISER DIAGRAM INDICATES 3/4 INCH CSST. PER WPB FBC
 107.2.1 PROVIDE CORRECT TUBE SIZE (EHD) TO CORRESPOND
 WITH SUBMITTED FBC FG TABLE 402.4(18).
  
 5. GAS PIPING PLAN SHOWS EXISTING POOL HEATER AT 400
 MBTU. PLEASE NOTE THAT ALTHOUGH THERE DOES NOT APPEAR
 TO BE A GAS PERMIT APPLIED FOR, PERMIT #96002653 FOR A
 POOL INDICATES A NATURAL GAS FIRED POOL HEATER AT 75
 MBTU. THIS NEEDS TO BE CLARIFIED.
  
 6. SUBMIT A HOUSE PLAN SHOWING THE FOLLOWING:
 A.THE LOCATION OF THE TYPE OF WATER HEATER(TANK TYPE OR
 TANK-LESS) AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER OR THE VENTING OF SAID WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 B. ALL OTHER GAS APPLIANCES AS WELL AS LOCATION OF
 METER.
  
 PLEASE NOTE, THE HOUSE PLAN CAN BE HAND DRAWN. REFER TO
 WPB FBC 107.2.1. A PLAN OF RECORD IS AVAILABLE FROM THE
 WPB BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON
 AT 561-805-6684; EMAIL [email protected].
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
 AN ORIGINAL SIGNED PLAN(S) SHALL BE SUBMITTED PRIOR TO
 PERMIT ISSUE. CALL 561-805-6724 OR EMAIL [email protected]
 FOR ADDITIONAL INFORMATION.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080940 8453 EGRET MEADOW LN
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 13:35 Rev Time 0.00
Received By medwards Date 2020-11-12 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-03 Cont ID  
Sent By jesmith Date 2020-09-03 Time 13:57 Rev Time 0.00
Received By jesmith Date 2020-09-03 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 13:35 Rev Time 0.00
Received By medwards Date 2020-11-23 Time 13:34 Sent To  
Notes
2020-11-23 13:35:33PLEASE SEE 1ST PLUMBING REVIEW COMMENTS. ME

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-03 Cont ID  
Sent By jesmith Date 2020-09-03 Time 13:55 Rev Time 0.00
Received By jesmith Date 2020-09-03 Time 13:49 Sent To  
Notes
2020-09-03 13:54:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FS = FLORIDA STATUTES
  
  
 PLUMBING COMMENTS: SUBJECT TO INFORMATION REQUESTED IN
 GAS REVIEW CONCERNING THE WATER HEATER A SEPARATE
 PLUMBING PERMIT MAY BE REQUIRED.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080940 8453 EGRET MEADOW LN
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-09-03 Cont ID  
Sent By jesmith Date 2020-09-03 Time 13:57 Rev Time 0.00
Received By jesmith Date 2020-09-03 Time 13:57 Sent To  
Notes
2020-09-03 13:57:16AN ORIGINAL SIGNED PLAN(S) SHALL BE SUBMITTED PRIOR TO
 PERMIT ISSUE. CALL 561-805-6724 OR EMAIL [email protected]
 FOR ADDITIONAL INFORMATION.
  
  