Plan Review Details - Permit 20080891
Plan Review Stops For Permit 20080891
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-02-18 Cont ID  
Sent By mcphers Date 2021-02-18 Time 12:15 Rev Time 0.00
Received By rmcphers Date 2021-02-18 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2021-01-13 Time 10:25 Sent To  
Notes
2021-01-13 10:28:12SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SIGN DESIGN HAS BEEN CHANGED FROM A WALL MOUNTED
 SIGN TO A CEILING MOUNTED SIGN. SIGN IS SUBJECT TO WIND
 LOADS PLEASE PROVIDE THE STRUCTURAL CALCULATIONS AND
 ATTACHMENT DETAILS FOR THE SIGN OR PROVIDE SIGNED AND
 SEALED ATTACHMENT DETAILS FOR THE "NEW SIGN DESIGN"
 FROM AN ARCHITECT OR ENGINEER. SHOW THE WIND DESIGN
 CRITERIA USED FOR DESIGN ON THE DRAWINGS FBC 1609
 2) BE SURE TO HAVE THE NEW DESIGN MARKED APPROVED BY
 CITY PLACE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-12-11 Cont ID  
Sent By rmcphers Date 2020-12-11 Time 15:27 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 15:19 Sent To  
Notes
2020-12-11 15:27:17SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED ATTACHMENT DETAILS
 FOR THE "NEW SIGN DESIGN" FROM AN ARCHITECT OR
 ENGINEER. SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN
 ON THE DRAWINGS FBC 1609
 2) BE SURE TO HAVE THE NEW DESIGN MARKED APPROVED BY
 CITY PLACE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By rmcdouga Date 2020-10-22 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2020-10-22 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 17:38 Rev Time 0.00
Received By shill Date 2020-09-15 Time 17:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-26 Cont ID  
Sent By equinone Date 2020-10-26 Time 16:07 Rev Time 0.00
Received By equinone Date 2020-10-26 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-05 Cont ID  
Sent By fgiaquin Date 2020-09-05 Time 23:00 Rev Time 0.00
Received By fgiaquin Date 2020-09-05 Time 22:19 Sent To  
Notes
2020-09-05 23:00:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL DRAWING SUBMITTED???
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-02-18 Cont ID  
Sent By rmcphers Date 2021-02-18 Time 12:15 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 19:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2020-12-30 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-15 Cont ID  
Sent By lmarchan Date 2020-12-15 Time 14:05 Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-29 Cont ID  
Sent By cpuell Date 2020-10-29 Time 17:35 Rev Time 0.00
Received By cpuell Date 2020-10-13 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-06 Cont ID  
Sent By shill Date 2020-10-06 Time 07:15 Rev Time 0.00
Received By shill Date 2020-08-20 Time 07:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-02-18 Cont ID  
Sent By rmcphers Date 2021-02-18 Time 12:15 Rev Time 0.00
Received By rmcphers Date 2021-02-18 Time 12:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2021-01-13 Time 10:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-11 Cont ID  
Sent By rmcphers Date 2020-12-11 Time 15:27 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 15:27 Sent To  
Notes
2020-12-11 15:27:58SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN DROP OFF THE ORIGINAL
 SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE FRONT DESK
 IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-22 Cont ID  
Sent By rmcdouga Date 2020-10-22 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2020-10-22 Time 07:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 17:32 Rev Time 0.00
Received By shill Date 2020-09-15 Time 17:32 Sent To  
Notes
2020-08-20 07:51:50DIGITALLY SIGNED FILE IN 'SIGNATURES' FOLDER

Review Stop Z ZONING
Rev No 4 Status P Date 2021-01-11 Cont ID  
Sent By eschneid Date 2021-01-11 Time 12:13 Rev Time 0.50
Received By eschneid Date 2021-01-11 Time 10:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-12-15 Cont ID  
Sent By eschneid Date 2020-12-15 Time 11:56 Rev Time 0.50
Received By eschneid Date 2020-12-15 Time 10:41 Sent To  
Notes
2020-12-15 11:58:47FAILED
  
 CEILING MOUNTED BLADE SIGN
  
 1) PROVIDE AN UPDATED CITYPLACE RETAIL APPROVAL OF THIS
 NEW SIGN DESIGN.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT
 CEILING MOUNTED BLADE SIGNS TO USE EITHER PUSH THOUGH
 WHITE ACRYLIC LETTERS OR PAINTED METAL PANELS.
 CITYPLACE RETAIL IS AUTHORIZED TO GRANT A WAIVER I TO
 PERMIT THE USE OF ALTERNATIVE MATERIALS FROM THOSE
 SPECIFIC IN THE MASTER PLAN. CITYPLACE RETAIL NEEDS TO
 WRITTEN APPROVAL OF THE WAIVER I TO ALLOW THE USE OF
 THE ACRYLIC AND VINYL COPY INSTEAD OF PAINTED COPY.
  
 3) WHILE IT APPEARS ON THE ELEVATION DRAWING THAT THE
 CEILING MOUNTED BLADE SIGN IS CENTERED IN THE ARCADE
 CEILING, PLEASE INCLUDE A NOTATION ON THE PLANS TO
 VERIFY COMPLIANCE WITH THIS REQUIREMENT OF THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA.
  
 WINDOW GRAPHICS NOT PART OF THIS PERMIT REVIEW.
  
 THIS DOES NOT COUNT AS A ZONING RESUBMITTAL REVIEW AS
 THE REVISED SIGN DESIGN ADDRESSED THE PREVIOUS REPEAT
 COMMENTS. THESE COMMENTS ARE NEW COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-10-29 Cont ID  
Sent By eschneid Date 2020-10-29 Time 16:06 Rev Time 0.25
Received By eschneid Date 2020-10-23 Time 15:31 Sent To  
Notes
2020-10-29 16:07:24BLADE SIGN
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT THE SIGN COPY AREA SHALL MAINTAIN
 A MARGIN AT LEAST THREE (3) INCHES FROM ANY EDGE OF THE
 PERCEIVED SIGN AREA. PROVIDE A DETAIL OF THE SIGN FACE
 THAT VERIFIES THIS REQUIREMENT. THE COMMENT NOTE ON THE
 PLANS STATES THAT THE BLADE SIGN DESIGN IS THE BRAND
 LOGO, WHICH DOES NOT EXEMPT IT FROM MEETING THE
 REQUIREMENT. A POSSIBLE SOLUTION IS TO HAVE THE CIRCLE
 MOUNTED ON A PANEL THAT WOULD PROVIDE THE THREE (3)
 INCH MARGIN FOR THE SIGN COPY (IT WOULD APPEAR SIMILAR
 TO THE NIGHT VIEW DEPENDING ON THE PANEL COLOR).
  
 WINDOW GRAPHICS NOT PART OF THIS PERMIT REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By eschneid Date 2020-10-02 Time 17:19 Rev Time 0.25
Received By eschneid Date 2020-10-02 Time 17:13 Sent To  
Notes
2020-10-02 17:19:18BLADE SIGN
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT
 LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED
 SIGN AREA. PROVIDE A DETAIL OF THE SIGN FACE THAT
 VERIFIES THIS REQUIREMENT.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION OF THIS REQUIREMENT ON THE
 PLANS. THIS IS NOT SPECIFIED ON THE PLANS.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA ONLY PERMIT
 WHITE, NOT CLEAR, ACRYLIC FOR PUSH THROUGH
 APPLICATIONS. THE USE OF ALTERNATIVE MATERIALS IS ONLY
 PERMITTED AS A WAIVER I. A WAIVER I REQUIRES WRITTEN
 APPROVAL FROM CITYPLACE RETAIL.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT BLADE SIGNS UTILIZING HALO ILLUMINATION MAY ONLY
 BE RECTANGULAR IN SHAPE. THE USE OF ALTERNATIVE DESIGN
 IS ONLY PERMITTED AS A WAIVER I. A WAIVER I REQUIRES
 WRITTEN APPROVAL FROM CITYPLACE RETAIL.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. VERIFY THAT THE MOUNTING SCREWS
 MEET THIS REQUIREMENT.
  
 6) NO ELECTRICAL DETAILS PROVIDED. REMEMBER: THE
 ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES THAT ALL
 CONDUIT, CROSSOVERS, WIRING NECESSARY FOR THE SIGN'S
 ELECTRICAL CONNECTION TO BE CONCEALED AND NOT VISIBLE
 TO THE PUBLIC. THE PLANS STATE THAT ALL WIRING WILL BE
 CONCEALED. THE CONDUIT THAT THE WIRING IS IN ALSO NEEDS
 TO BE CONCEALED. PROVIDE HOW THIS WILL OCCUR.
  
  
 WINDOW GRAPHICS NOT PART OF THIS PERMIT REVIEW.
  
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  